Certificate holders

Subtype

HP60 - 11/13 ; Assure HP55 - 11/13

Certificate Holder
BAXI Heating UK Limited
Brooks House, Coventry Road
CV34 4LL Warwick
United Kingdom
Registration number
ICIM-PDC-000328
Certification Body
ICIM S.p.A.
Subtype title
HP60 - 11/13 ; Assure HP55 - 11/13
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R290
Mass of Refrigerant

1,250 kg

Certification Date
05.05.2025
Testing basis
V12
Generate PDF Export model CSV Download certificate
  • Number of models 4

Models

HP60-11-1-PHMB ; Assure HP55-11-1-PHMB
Configure model
Model name
HP60-11-1-PHMB ; Assure HP55-11-1-PHMB
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.5 kW

11.5 kW

El input

2.37 kW

3.65 kW

COP

4.85

3.15

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

52 dB(A)

52 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

187.8 %

147.1 %

Prated

12.1 kW

12.1 kW

SCOP

4.77

3.75

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.68 kW

10.88 kW

COP Tj = -7°C

2.8

2.27

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

6.69 kW

6.56 kW

COP Tj = +2°C

4.55

3.63

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

5.3 kW

4.78 kW

COP Tj = +7°C

6.98

4.99

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

5.34 kW

5.83 kW

COP Tj = 12°C

7.7

6.55

Cdh Tj = +12 °C

0.98

0.99

Pdh Tj = Tbiv

10.68 kW

10.88 kW

COP Tj = Tbiv

2.8

2.27

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.66 kW

10.71 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.61

2.15

WTOL

75 °C

75 °C

Poff

10.1 W

10.1 W

PTO

15 W

15 W

PSB

10.1 W

10.1 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.44 kW

1.39 kW

Annual energy consumption Qhe

5240 kWh

6662 kWh

HP60-11-3-PHMB ; Assure HP55-11-3-PHMB
Configure model
Model name
HP60-11-3-PHMB ; Assure HP55-11-3-PHMB
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.5 kW

11.5 kW

El input

2.37 kW

3.65 kW

COP

4.85

3.15

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

52 dB(A)

52 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

187.8 %

147.1 %

Prated

12.1 kW

12.1 kW

SCOP

4.77

3.75

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.68 kW

10.88 kW

COP Tj = -7°C

2.8

2.27

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

6.69 kW

6.56 kW

COP Tj = +2°C

4.55

3.63

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

5.3 kW

4.78 kW

COP Tj = +7°C

6.98

4.99

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

5.34 kW

5.83 kW

COP Tj = 12°C

7.7

6.55

Cdh Tj = +12 °C

0.98

0.99

Pdh Tj = Tbiv

10.68 kW

10.88 kW

COP Tj = Tbiv

2.8

2.27

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.66 kW

10.71 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.61

2.15

WTOL

75 °C

75 °C

Poff

10.1 W

10.1 W

PTO

15 W

15 W

PSB

10.1 W

10.1 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.44 kW

1.39 kW

Annual energy consumption Qhe

5240 kWh

6662 kWh

HP60-13-1-PHMB ; Assure HP55-13-1-PHMB
Configure model
Model name
HP60-13-1-PHMB ; Assure HP55-13-1-PHMB
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

13.5 kW

13.5 kW

El input

2.93 kW

4.44 kW

COP

4.6

3.04

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

52 dB(A)

52 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

184.9 %

146.2 %

Prated

13.7 kW

13.7 kW

SCOP

4.7

3.73

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

12.03 kW

11.87 kW

COP Tj = -7°C

2.7

2.22

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

7.38 kW

7.37 kW

COP Tj = +2°C

4.46

3.56

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

5.24 kW

4.87 kW

COP Tj = +7°C

7.02

5.21

Cdh Tj = +7 °C

1

1

Pdh Tj = 12°C

5.28 kW

5.83 kW

COP Tj = 12°C

7.71

6.55

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

12.03 kW

11.87 kW

COP Tj = Tbiv

2.7

2.22

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.45 kW

11.2 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.54

2.07

WTOL

75 °C

75 °C

Poff

10.1 W

10.1 W

PTO

15 W

15 W

PSB

10.1 W

10.1 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

2.25 kW

2.5 kW

Annual energy consumption Qhe

6025 kWh

7588 kWh

HP60-13-3-PHMB ; Assure HP55-13-3-PHMB
Configure model
Model name
HP60-13-3-PHMB ; Assure HP55-13-3-PHMB
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

13.5 kW

13.5 kW

El input

2.93 kW

4.44 kW

COP

4.6

3.04

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

52 dB(A)

52 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

184.9 %

146.2 %

Prated

13.7 kW

13.7 kW

SCOP

4.7

3.73

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

12.03 kW

11.87 kW

COP Tj = -7°C

2.7

2.22

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

7.38 kW

7.37 kW

COP Tj = +2°C

4.46

3.56

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

5.24 kW

4.87 kW

COP Tj = +7°C

7.02

5.21

Cdh Tj = +7 °C

1

1

Pdh Tj = 12°C

5.28 kW

5.83 kW

COP Tj = 12°C

7.71

6.55

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

12.03 kW

11.87 kW

COP Tj = Tbiv

2.7

2.22

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.45 kW

11.2 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.54

2.07

WTOL

75 °C

75 °C

Poff

10.1 W

10 W

PTO

15 W

10 W

PSB

10.1 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

2.25 kW

2.5 kW

Annual energy consumption Qhe

6025 kWh

7588 kWh