1,720 kg
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
7.90 kW
7.70 kW
El input
1.75 kW
2.78 kW
COP
4.52
2.76
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
0 dB(A)
0 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
162 %
123 %
Prated
7.00 kW
6.20 kW
SCOP
4.13
3.15
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.19 kW
5.48 kW
COP Tj = -7°C
2.80
1.85
Pdh Tj = +2°C
3.77 kW
3.34 kW
COP Tj = +2°C
3.97
3.22
Pdh Tj = +7°C
2.80 kW
2.63 kW
COP Tj = +7°C
5.90
4.13
Pdh Tj = 12°C
3.03 kW
3.15 kW
COP Tj = 12°C
6.32
5.91
Pdh Tj = Tbiv
6.19 kW
5.48 kW
COP Tj = Tbiv
2.80
1.85
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.83 kW
4.71 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.57
1.59
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.87
0.92
WTOL
55 °C
55 °C
Poff
5 W
5 W
PTO
60 W
50 W
PSB
5 W
5 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.20 kW
1.50 kW
Annual energy consumption Qhe
3505 kWh
4068 kWh