1,400 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.00 kW
12.00 kW
El input
2.53 kW
4.00 kW
COP
4.75
3.00
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
56 dB(A)
56 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
270 %
197 %
Prated
11.40 kW
11.40 kW
SCOP
6.81
5.01
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
11.59 kW
12.37 kW
COP Tj = +2°C
3.62
2.51
Cdh Tj = +2 °C
0.994
0.996
Pdh Tj = +7°C
7.76 kW
7.72 kW
COP Tj = +7°C
5.81
4.09
Cdh Tj = +7 °C
0.986
0.990
Pdh Tj = 12°C
3.48 kW
3.46 kW
COP Tj = 12°C
8.80
6.80
Cdh Tj = +12 °C
0.952
0.963
Pdh Tj = Tbiv
11.59 kW
12.37 kW
COP Tj = Tbiv
3.62
2.51
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.59 kW
12.37 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.62
2.51
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.994
0.996
WTOL
75 °C
75 °C
Poff
12 W
12 W
PTO
19 W
19 W
PSB
12 W
12 W
PCK
2 W
2 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2235 kWh
3042 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
56 dB(A)
56 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
170 %
134 %
Prated
11.30 kW
10.50 kW
SCOP
4.33
3.43
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
7.09 kW
6.51 kW
COP Tj = -7°C
3.55
2.84
Cdh Tj = -7 °C
0.990
0.992
Pdh Tj = +2°C
4.34 kW
4.07 kW
COP Tj = +2°C
5.25
4.11
Cdh Tj = +2 °C
0.977
0.981
Pdh Tj = +7°C
2.87 kW
2.72 kW
COP Tj = +7°C
7.35
5.60
Cdh Tj = +7 °C
0.951
0.961
Pdh Tj = 12°C
2.71 kW
2.62 kW
COP Tj = 12°C
8.15
6.86
Cdh Tj = +12 °C
0.943
0.950
Pdh Tj = Tbiv
9.36 kW
8.75 kW
COP Tj = Tbiv
2.57
2.06
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.88 kW
6.98 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.04
1.59
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.996
WTOL
75 °C
75 °C
Poff
12 W
12 W
PTO
19 W
19 W
PSB
12 W
12 W
PCK
2 W
2 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.40 kW
3.50 kW
Annual energy consumption Qhe
6440 kWh
7537 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.36
8.75
COP Tj = -15°C (if TOL<-20°C)
2.57
2.06
Cdh Tj = -15 °C
0.995
0.996
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
56 dB(A)
56 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
193 %
148 %
Prated
12.20 kW
12.10 kW
SCOP
4.90
3.77
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.07 kW
10.73 kW
COP Tj = -7°C
2.90
2.20
Cdh Tj = -7 °C
0.995
0.996
Pdh Tj = +2°C
6.52 kW
6.43 kW
COP Tj = +2°C
4.52
3.58
Cdh Tj = +2 °C
0.987
0.989
Pdh Tj = +7°C
4.26 kW
4.24 kW
COP Tj = +7°C
7.19
5.34
Cdh Tj = +7 °C
0.968
0.976
Pdh Tj = 12°C
2.78 kW
2.56 kW
COP Tj = 12°C
10.18
6.76
Cdh Tj = +12 °C
0.930
0.950
Pdh Tj = Tbiv
11.07 kW
10.73 kW
COP Tj = Tbiv
2.90
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.55 kW
10.48 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.76
2.05
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.996
WTOL
75 °C
75 °C
Poff
12 W
12 W
PTO
19 W
19 W
PSB
12 W
12 W
PCK
2 W
2 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.60 kW
1.60 kW
Annual energy consumption Qhe
5141 kWh
6639 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
15.00 kW
15.00 kW
El input
3.33 kW
5.26 kW
COP
4.50
2.85
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
253 %
190 %
Prated
13.00 kW
12.30 kW
SCOP
6.39
4.83
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
13.08 kW
12.74 kW
COP Tj = +2°C
3.36
2.44
Cdh Tj = +2 °C
0.995
0.996
Pdh Tj = +7°C
8.58 kW
8.54 kW
COP Tj = +7°C
5.69
4.02
Cdh Tj = +7 °C
0.987
0.991
Pdh Tj = 12°C
3.81 kW
3.85 kW
COP Tj = 12°C
7.89
6.42
Cdh Tj = +12 °C
0.961
0.968
Pdh Tj = Tbiv
13.08 kW
12.74 kW
COP Tj = Tbiv
3.36
2.44
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.08 kW
12.74 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.36
2.44
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.996
WTOL
75 °C
75 °C
Poff
12 W
12 W
PTO
19 W
19 W
PSB
12 W
12 W
PCK
2 W
2 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2720 kWh
3402 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
165 %
133 %
Prated
13.50 kW
12.80 kW
SCOP
4.20
3.40
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
8.25 kW
7.78 kW
COP Tj = -7°C
3.37
2.77
Cdh Tj = -7 °C
0.992
0.993
Pdh Tj = +2°C
5.11 kW
4.77 kW
COP Tj = +2°C
5.12
4.11
Cdh Tj = +2 °C
0.981
0.984
Pdh Tj = +7°C
3.29 kW
3.16 kW
COP Tj = +7°C
7.46
5.88
Cdh Tj = +7 °C
0.957
0.965
Pdh Tj = 12°C
2.71 kW
2.62 kW
COP Tj = 12°C
8.15
6.86
Cdh Tj = +12 °C
0.943
0.950
Pdh Tj = Tbiv
11.15 kW
10.46 kW
COP Tj = Tbiv
2.49
1.95
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.27 kW
8.59 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.04
1.59
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.996
WTOL
75 °C
75 °C
Poff
12 W
12 W
PTO
19 W
19 W
PSB
12 W
12 W
PCK
2 W
2 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.20 kW
4.20 kW
Annual energy consumption Qhe
7924 kWh
9284 kWh
Pdh Tj = -15°C (if TOL<-20°C)
11.15
10.46
COP Tj = -15°C (if TOL<-20°C)
2.49
1.95
Cdh Tj = -15 °C
0.996
0.996
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
186 %
146 %
Prated
14.00 kW
14.00 kW
SCOP
4.73
3.73
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.53 kW
12.47 kW
COP Tj = -7°C
2.74
2.10
Cdh Tj = -7 °C
0.996
0.997
Pdh Tj = +2°C
7.58 kW
7.67 kW
COP Tj = +2°C
4.37
3.55
Cdh Tj = +2 °C
0.989
0.991
Pdh Tj = +7°C
4.83 kW
4.81 kW
COP Tj = +7°C
7.04
5.39
Cdh Tj = +7 °C
0.972
0.979
Pdh Tj = 12°C
2.78 kW
2.56 kW
COP Tj = 12°C
10.18
6.76
Cdh Tj = +12 °C
0.930
0.950
Pdh Tj = Tbiv
12.53 kW
12.47 kW
COP Tj = Tbiv
2.74
2.10
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.55 kW
12.12 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.76
2.00
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.997
WTOL
75 °C
75 °C
Poff
12 W
12 W
PTO
19 W
19 W
PSB
12 W
12 W
PCK
2 W
2 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.40 kW
1.90 kW
Annual energy consumption Qhe
6115 kWh
7763 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.00 kW
12.00 kW
El input
2.53 kW
4.00 kW
COP
4.75
3.00
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
56 dB(A)
56 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
265 %
189 %
Prated
11.40 kW
11.40 kW
SCOP
6.71
4.80
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
11.44 kW
11.96 kW
COP Tj = +2°C
3.61
2.51
Cdh Tj = +2 °C
0.996
0.997
Pdh Tj = +7°C
7.51 kW
7.91 kW
COP Tj = +7°C
5.85
4.13
Cdh Tj = +7 °C
0.990
0.993
Pdh Tj = 12°C
3.47 kW
3.57 kW
COP Tj = 12°C
8.40
6.11
Cdh Tj = +12 °C
0.969
0.978
Pdh Tj = Tbiv
11.44 kW
11.96 kW
COP Tj = Tbiv
3.61
2.51
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.44 kW
11.96 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.61
2.51
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
12 W
12 W
PTO
13 W
13 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2271 kWh
3173 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
56 dB(A)
56 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
170 %
132 %
Prated
11.30 kW
10.50 kW
SCOP
4.33
3.36
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.95 kW
6.47 kW
COP Tj = -7°C
3.61
2.77
Cdh Tj = -7 °C
0.993
0.994
Pdh Tj = +2°C
4.19 kW
4.05 kW
COP Tj = +2°C
5.25
3.98
Cdh Tj = +2 °C
0.984
0.987
Pdh Tj = +7°C
2.82 kW
2.70 kW
COP Tj = +7°C
6.84
5.52
Cdh Tj = +7 °C
0.969
0.973
Pdh Tj = 12°C
2.69 kW
2.63 kW
COP Tj = 12°C
7.99
6.82
Cdh Tj = +12 °C
0.961
0.966
Pdh Tj = Tbiv
9.22 kW
8.61 kW
COP Tj = Tbiv
2.60
2.09
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.66 kW
6.78 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.08
1.58
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
12 W
12 W
PTO
13 W
13 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.60 kW
3.70 kW
Annual energy consumption Qhe
6435 kWh
7693 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.22
8.61
COP Tj = -15°C (if TOL<-20°C)
2.60
2.09
Cdh Tj = -15 °C
0.996
0.997
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
56 dB(A)
56 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
192 %
148 %
Prated
12.20 kW
12.10 kW
SCOP
4.88
3.76
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.22 kW
11.18 kW
COP Tj = -7°C
2.79
2.21
Cdh Tj = -7 °C
0.997
0.997
Pdh Tj = +2°C
6.67 kW
6.45 kW
COP Tj = +2°C
4.57
3.58
Cdh Tj = +2 °C
0.991
0.993
Pdh Tj = +7°C
4.23 kW
4.18 kW
COP Tj = +7°C
7.10
5.17
Cdh Tj = +7 °C
0.978
0.984
Pdh Tj = 12°C
2.77 kW
2.71 kW
COP Tj = 12°C
10.01
7.54
Cdh Tj = +12 °C
0.953
0.964
Pdh Tj = Tbiv
11.22 kW
11.18 kW
COP Tj = Tbiv
2.79
2.21
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.57 kW
10.16 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.61
2.00
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.997
WTOL
75 °C
75 °C
Poff
12 W
12 W
PTO
13 W
13 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.60 kW
1.90 kW
Annual energy consumption Qhe
5168 kWh
6642 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
15.00 kW
15.00 kW
El input
3.33 kW
5.26 kW
COP
4.50
2.85
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
250 %
190 %
Prated
13.00 kW
12.30 kW
SCOP
6.33
4.83
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
13.09 kW
12.39 kW
COP Tj = +2°C
3.37
2.50
Cdh Tj = +2 °C
0.997
0.997
Pdh Tj = +7°C
8.59 kW
8.30 kW
COP Tj = +7°C
5.80
4.11
Cdh Tj = +7 °C
0.991
0.994
Pdh Tj = 12°C
3.77 kW
3.84 kW
COP Tj = 12°C
7.56
6.23
Cdh Tj = +12 °C
0.974
0.979
Pdh Tj = Tbiv
13.09 kW
12.39 kW
COP Tj = Tbiv
3.37
2.50
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.09 kW
12.39 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.37
2.50
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.997
WTOL
75 °C
75 °C
Poff
12 W
12 W
PTO
13 W
13 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2744 kWh
3401 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
163 %
131 %
Prated
13.50 kW
12.80 kW
SCOP
4.15
3.36
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
8.25 kW
7.90 kW
COP Tj = -7°C
3.45
2.76
Cdh Tj = -7 °C
0.995
0.995
Pdh Tj = +2°C
4.96 kW
4.72 kW
COP Tj = +2°C
4.97
4.02
Cdh Tj = +2 °C
0.987
0.989
Pdh Tj = +7°C
3.22 kW
3.05 kW
COP Tj = +7°C
6.96
5.44
Cdh Tj = +7 °C
0.972
0.977
Pdh Tj = 12°C
2.69 kW
2.63 kW
COP Tj = 12°C
7.99
6.82
Cdh Tj = +12 °C
0.961
0.966
Pdh Tj = Tbiv
11.06 kW
10.47 kW
COP Tj = Tbiv
2.45
1.99
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.91 kW
8.40 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.04
1.65
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.997
WTOL
75 °C
75 °C
Poff
12 W
12 W
PTO
13 W
13 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.60 kW
4.40 kW
Annual energy consumption Qhe
8028 kWh
9404 kWh
Pdh Tj = -15°C (if TOL<-20°C)
11.06
10.47
COP Tj = -15°C (if TOL<-20°C)
2.45
1.99
Cdh Tj = -15 °C
0.997
0.998
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
187 %
145 %
Prated
14.00 kW
14.00 kW
SCOP
4.74
3.69
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.39 kW
12.85 kW
COP Tj = -7°C
2.68
2.10
Cdh Tj = -7 °C
0.997
0.998
Pdh Tj = +2°C
7.55 kW
7.54 kW
COP Tj = +2°C
4.45
3.49
Cdh Tj = +2 °C
0.992
0.994
Pdh Tj = +7°C
4.83 kW
4.78 kW
COP Tj = +7°C
6.93
5.25
Cdh Tj = +7 °C
0.981
0.986
Pdh Tj = 12°C
2.77 kW
2.71 kW
COP Tj = 12°C
10.01
7.54
Cdh Tj = +12 °C
0.953
0.964
Pdh Tj = Tbiv
12.39 kW
12.85 kW
COP Tj = Tbiv
2.68
2.10
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.54 kW
11.77 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.56
1.89
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.998
WTOL
75 °C
75 °C
Poff
12 W
12 W
PTO
13 W
13 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.50 kW
2.20 kW
Annual energy consumption Qhe
6097 kWh
7837 kWh