0,700 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.40 kW
4.40 kW
El input
0.85 kW
1.36 kW
COP
5.17
3.24
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 14825
Low temperature
Medium temperature
ηs
210.4 %
156.7 %
Prated
5.30 kW
4.90 kW
SCOP
5.34
3.99
Tbiv
-7.00 °C
-7.00 °C
TOL
-10.00 °C
-10.00 °C
Pdh Tj = -7°C
4.64 kW
4.42 kW
COP Tj = -7°C
3.40
2.59
Cdh Tj = -7 °C
1.00
1.00
Pdh Tj = +2°C
2.89 kW
2.72 kW
COP Tj = +2°C
5.29
3.94
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
2.73 kW
2.55 kW
COP Tj = +7°C
6.74
4.94
Cdh Tj = +7 °C
0.98
1.00
Pdh Tj = 12°C
3.14 kW
3.01 kW
COP Tj = 12°C
8.54
6.44
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
4.64 kW
4.42 kW
COP Tj = Tbiv
3.40
2.59
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.30 kW
4.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.01
2.27
WTOL
75.00 °C
75.00 °C
Poff
8.70 W
8.70 W
PTO
10.00 W
10.00 W
PSB
8.70 W
8.70 W
PCK
0.00 W
0.00 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.10 kW
Annual energy consumption Qhe
2052 kWh
2535 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.26 kW
6.10 kW
El input
1.28 kW
1.91 kW
COP
4.89
3.20
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 14825
Low temperature
Medium temperature
ηs
205.8 %
152.9 %
Prated
6.40 kW
6.10 kW
SCOP
5.22
3.90
Tbiv
-7.00 °C
-7.00 °C
TOL
-10.00 °C
-10.00 °C
Pdh Tj = -7°C
5.63 kW
5.40 kW
COP Tj = -7°C
3.04
2.40
Cdh Tj = -7 °C
1.00
1.00
Pdh Tj = +2°C
3.70 kW
3.13 kW
COP Tj = +2°C
5.20
3.79
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
2.74 kW
2.58 kW
COP Tj = +7°C
6.95
5.15
Cdh Tj = +7 °C
0.98
1.00
Pdh Tj = 12°C
3.14 kW
3.02 kW
COP Tj = 12°C
8.64
6.53
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
5.63 kW
5.40 kW
COP Tj = Tbiv
3.04
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.76 kW
5.37 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.00
2.25
WTOL
75.00 °C
75.00 °C
Poff
8.70 W
8.70 W
PTO
10.00 W
10.00 W
PSB
8.70 W
8.70 W
PCK
0.00 W
0.00 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.64 kW
0.73 kW
Annual energy consumption Qhe
2533 kWh
3233 kWh