Certificate holders

Subtype

iTec XTR L & XL 400V

Certificate Holder
Thermia
Snickaregatan 1
Arvika
Sweden
Registration number
011-1W1001
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
iTec XTR L & XL 400V
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R290
Mass of Refrigerant

1,250 kg

Certification Date
25.03.2025
Testing basis
HP KEYMARK certification scheme rules rev. 14
Generate PDF Export model CSV
  • Number of models 2

Models

iTec XTR L 400V
Configure model
Model name
iTec XTR L 400V
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

12.00 kW

12.00 kW

El input

2.50 kW

4.00 kW

COP

4.80

3.00

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

193 %

143 %

Prated

12.00 kW

12.00 kW

SCOP

4.90

3.65

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.62 kW

10.60 kW

COP Tj = -7°C

2.95

2.15

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

6.46 kW

6.46 kW

COP Tj = +2°C

4.83

3.60

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

4.15 kW

4.20 kW

COP Tj = +7°C

6.50

4.88

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

4.15 kW

4.20 kW

COP Tj = 12°C

8.00

5.95

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

10.60 kW

10.60 kW

COP Tj = Tbiv

2.95

2.15

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.62 kW

11.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.46

1.85

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

75 °C

75 °C

Poff

22 W

22 W

PTO

22 W

22 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.40 kW

0.50 kW

Annual energy consumption Qhe

5051 kWh

6784 kWh

iTec XTR XL 400V
Configure model
Model name
iTec XTR XL 400V
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16.00 kW

16.00 kW

El input

3.55 kW

5.52 kW

COP

4.51

2.90

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

65 dB(A)

65 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

185 %

139 %

Prated

15.50 kW

15.50 kW

SCOP

4.70

3.55

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

13.70 kW

13.71 kW

COP Tj = -7°C

2.50

1.95

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

8.35 kW

8.35 kW

COP Tj = +2°C

4.52

3.43

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

5.37 kW

5.40 kW

COP Tj = +7°C

7.10

5.18

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

4.20 kW

4.20 kW

COP Tj = 12°C

9.00

6.58

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

13.71 kW

13.70 kW

COP Tj = Tbiv

2.50

1.95

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.50 kW

13.30 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.31

1.75

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

75 °C

75 °C

Poff

22 W

22 W

PTO

22 W

22 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

2.00 kW

2.20 kW

Annual energy consumption Qhe

6793 kWh

8985 kWh