Certificate holders

Subtype

FDCM140VNX-W

Certificate Holder
Mitsubishi Heavy Industries Air Conditioning Europe
5 The Square
UB11 1ET Uxbridge, Middlesex
United Kingdom
Registration number
012-C700400 / Issue 1
Certification Body
RISE CERT
Subtype title
FDCM140VNX-W
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

2,900 kg

Certification Date
03.06.2025
Testing basis
EN 14511:2022, EN 14825:2022, EN 12102:2022
Testing laboratory
KIWA, NL
Generate PDF Export model CSV Download certificate
  • Number of models 1

Models

FDCM140VNX-W
Configure model
Model name
FDCM140VNX-W
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

14.50 kW

16.00 kW

El input

4.26 kW

6.40 kW

COP

3.40

2.50

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

63 dB(A)

63 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

181 %

133 %

Prated

12.00 kW

12.00 kW

SCOP

4.60

3.40

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.40 kW

10.50 kW

COP Tj = -7°C

2.90

2.06

Cdh Tj = -7 °C

0.970

0.970

Pdh Tj = +2°C

6.70 kW

6.30 kW

COP Tj = +2°C

4.29

3.18

Cdh Tj = +2 °C

0.970

0.970

Pdh Tj = +7°C

4.20 kW

4.10 kW

COP Tj = +7°C

6.37

4.83

Cdh Tj = +7 °C

0.970

0.970

Pdh Tj = 12°C

4.60 kW

4.60 kW

COP Tj = 12°C

8.82

7.42

Cdh Tj = +12 °C

0.970

0.970

Pdh Tj = Tbiv

10.40 kW

10.50 kW

COP Tj = Tbiv

2.90

2.06

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.70 kW

9.30 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.70

1.79

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.970

0.970

WTOL

60 °C

60 °C

Poff

28 W

28 W

PTO

31 W

31 W

PSB

31 W

31 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

2.30 kW

2.70 kW

Annual energy consumption Qhe

6175 kWh

8321 kWh