1,840 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
14.30 kW
14.10 kW
El input
3.10 kW
4.52 kW
COP
4.61
3.12
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
42 dB(A)
42 dB(A)
Sound power level outdoor
63 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
183 %
136 %
Prated
13.20 kW
13.00 kW
SCOP
4.61
3.49
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.64 kW
11.47 kW
COP Tj = -7°C
2.83
2.06
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
6.97 kW
6.93 kW
COP Tj = +2°C
4.40
3.38
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
6.23 kW
5.19 kW
COP Tj = +7°C
6.59
4.66
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
7.22 kW
6.66 kW
COP Tj = 12°C
9.52
7.51
Cdh Tj = +12 °C
1.000
0.990
Pdh Tj = Tbiv
11.64 kW
11.47 kW
COP Tj = Tbiv
2.83
2.06
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.27 kW
10.11 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.39
1.42
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
13 W
13 W
PTO
15 W
15 W
PSB
13 W
13 W
PCK
29 W
29 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.92 kW
2.86 kW
Annual energy consumption Qhe
5900 kWh
7687 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
16.20 kW
16.20 kW
El input
3.67 kW
5.59 kW
COP
4.41
2.90
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
42 dB(A)
42 dB(A)
Sound power level outdoor
67 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
184 %
136 %
Prated
14.40 kW
13.00 kW
SCOP
4.63
3.43
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.71 kW
11.52 kW
COP Tj = -7°C
2.71
2.13
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
7.79 kW
7.44 kW
COP Tj = +2°C
4.36
3.25
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
6.14 kW
5.46 kW
COP Tj = +7°C
6.63
4.88
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
6.68 kW
6.25 kW
COP Tj = 12°C
9.69
7.23
Cdh Tj = +12 °C
1.000
0.990
Pdh Tj = Tbiv
12.71 kW
11.52 kW
COP Tj = Tbiv
2.71
2.13
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.04 kW
8.81 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.56
1.40
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
13 W
13 W
PTO
15 W
15 W
PSB
13 W
13 W
PCK
29 W
29 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.32 kW
4.22 kW
Annual energy consumption Qhe
5900 kWh
7863 kWh