1,200 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.18 kW
12.21 kW
El input
2.53 kW
3.79 kW
COP
4.81
3.22
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
49 dB(A)
52 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
190 %
150 %
Prated
11.2 kW
11.2 kW
SCOP
4.82
3.81
Tbiv
-9 °C
-9 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.47 kW
10.43 kW
COP Tj = -7°C
3.12
2.32
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
7.18 kW
6.56 kW
COP Tj = +2°C
4.58
3.76
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
4.56 kW
4.57 kW
COP Tj = +7°C
6.66
5.06
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
3.4 kW
3.2 kW
COP Tj = 12°C
9.01
6.83
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
11.12 kW
10.81 kW
COP Tj = Tbiv
3.01
2.23
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.86 kW
10.58 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.89
2.15
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
7 W
7 W
PTO
27 W
27 W
PSB
7 W
7 W
PCK
21 W
21 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.32 kW
0.58 kW
Annual energy consumption Qhe
4803 kWh
6069 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
123.1 %
COP
2.89
Heating up time
01:59 h:min
Standby power input
46 W
Reference hot water temperature
55.4 °C
Mixed water at 40°C
331 l