2,200 kg
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
5.94 kW
4.80 kW
El input
1.16 kW
1.47 kW
COP
5.10
3.26
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
51 dB(A)
51 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
151 %
120 %
Prated
11.00 kW
11.00 kW
SCOP
3.85
3.08
Tbiv
-11 °C
-11 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.57 kW
6.68 kW
COP Tj = -7°C
3.16
2.40
Pdh Tj = +2°C
4.33 kW
4.18 kW
COP Tj = +2°C
5.57
4.44
Pdh Tj = +7°C
2.66 kW
2.54 kW
COP Tj = +7°C
6.38
5.29
Pdh Tj = 12°C
3.05 kW
2.98 kW
COP Tj = 12°C
7.04
6.92
Pdh Tj = Tbiv
8.06 kW
7.87 kW
COP Tj = Tbiv
2.20
1.74
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.04 kW
2.73 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.81
1.32
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.98
0.98
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
14 W
14 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
5.96 kW
8.27 kW
Annual energy consumption Qhe
7038 kWh
8797 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
51 dB(A)
51 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
193 %
148 %
Prated
7.50 kW
7.60 kW
SCOP
4.90
3.78
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.80 kW
6.83 kW
COP Tj = -7°C
2.88
2.01
Pdh Tj = +2°C
4.05 kW
4.06 kW
COP Tj = +2°C
5.21
3.94
Pdh Tj = +7°C
2.63 kW
2.57 kW
COP Tj = +7°C
6.24
5.14
Pdh Tj = 12°C
3.03 kW
2.94 kW
COP Tj = 12°C
7.17
6.53
Pdh Tj = Tbiv
7.67 kW
7.65 kW
COP Tj = Tbiv
2.25
1.51
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.67 kW
7.65 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.25
1.51
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.98
0.98
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
14 W
14 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
3163 kWh
4153 kWh