Certificate holders

Subtype

Split Heat pump-R32 KFS-120*

Certificate Holder
GZ AXEN Heat Pump Technology Co., Ltd.
No.22, Lianyun Erheng Road, Shiqi Village, Shiqi Town, Panyu District
511450 Guangzhou
China
Registration number
011-1W0945
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
Split Heat pump-R32 KFS-120*
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

1,750 kg

Certification Date
09.01.2025
Testing basis
HP KEYMARK certification scheme rules rev. 14
Testing laboratory
TÜV Rheinland (GuangDong) Ltd., CN
Generate PDF Export model CSV
  • Number of models 1

Models

Indoor unit: KFS-120B/EN8SBP and outdoor unit: KFS-120W/N8SBP
Configure model
Model name
Indoor unit: KFS-120B/EN8SBP and outdoor unit: KFS-120W/N8SBP
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

12.10 kW

11.70 kW

El input

2.68 kW

4.30 kW

COP

4.52

2.72

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

42 dB(A)

Sound power level outdoor

60 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

185 %

136 %

Prated

11.30 kW

10.70 kW

SCOP

4.70

3.47

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.02 kW

9.45 kW

COP Tj = -7°C

2.59

2.01

Cdh Tj = -7 °C

1.000

1.000

Pdh Tj = +2°C

6.07 kW

6.21 kW

COP Tj = +2°C

4.38

3.27

Cdh Tj = +2 °C

0.990

0.990

Pdh Tj = +7°C

4.21 kW

3.99 kW

COP Tj = +7°C

7.28

4.86

Cdh Tj = +7 °C

0.970

0.980

Pdh Tj = 12°C

4.94 kW

4.41 kW

COP Tj = 12°C

10.57

7.42

Cdh Tj = +12 °C

0.960

0.970

Pdh Tj = Tbiv

10.02 kW

9.45 kW

COP Tj = Tbiv

2.59

2.01

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.64 kW

9.37 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.41

1.78

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

60 °C

60 °C

Poff

10 W

10 W

PTO

19 W

19 W

PSB

10 W

10 W

PCK

28 W

28 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.68 kW

1.31 kW

Annual energy consumption Qhe

4977 kWh

6353 kWh