0,700 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.90 kW
5.28 kW
El input
1.21 kW
1.71 kW
COP
4.87
3.09
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
31 dB(A)
32 dB(A)
Sound power level outdoor
49 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
181 %
134 %
Prated
6.52 kW
6.07 kW
SCOP
4.60
3.41
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
5.77 kW
5.37 kW
COP Tj = -7°C
2.94
2.19
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
3.57 kW
3.41 kW
COP Tj = +2°C
4.48
3.43
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
3.37 kW
3.09 kW
COP Tj = +7°C
6.49
4.49
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.86 kW
3.71 kW
COP Tj = 12°C
8.38
6.13
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
5.77 kW
5.37 kW
COP Tj = Tbiv
2.94
2.19
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.89 kW
5.40 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.70
1.85
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
12 W
12 W
PTO
22 W
22 W
PSB
12 W
12 W
PCK
30 W
30 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.63 kW
0.67 kW
Annual energy consumption Qhe
2927 kWh
3675 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
117 %
COP
2.92
Heating up time
2:22:12 h:min
Standby power input
38.0 W
Reference hot water temperature
44.2 °C
Mixed water at 40°C
218 l