Certificate holders

Subtype

Aquarea T-CAP 20-25 kW (M Series)

Certificate Holder
Panasonic Marketing Europe GmbH
Hagenauer Strasse 43, Wiesbaden
65203 Wiesbaden
Germany
Registration number
011-1W0925
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
Aquarea T-CAP 20-25 kW (M Series)
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R290
Mass of Refrigerant

3,000 kg

Certification Date
14.11.2024
Testing basis
European KEYMARK Scheme for Heat Pumps V.14 (2024-04)
Generate PDF Export model CSV
  • Number of models 4

Models

WH-WXG20ME8 (Outdoor unit Stand-alone)
Configure model
Model name
WH-WXG20ME8 (Outdoor unit Stand-alone)
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

20.00 kW

20.00 kW

El input

4.16 kW

6.28 kW

COP

4.80

3.18

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

El input

6.62 kW

Cooling capacity

20.00

EER

3.02

EN 14825

+7°C/+12°C

Pdesignc

20.00 kW

SEER

4.45

Pdc Tj = 35°C

20.00 kW

EER Tj = 35°C

3.02

Cdc Tj = 35 °C

1.000

Pdc Tj = 30°C

14.74 kW

EER Tj = 30°C

4.39

Cdc Tj = 30 °C

0.990

Pdc Tj = 25°C

9.47 kW

EER Tj = 25°C

5.31

Cdc Tj = 25 °C

0.970

Pdc Tj = 20°C

6.39 kW

EER Tj = 20°C

5.13

Cdc Tj = 20 °C

0.960

Poff

40 W

PTO

50 W

PSB

40 W

PCK

0 W

Annual energy consumption Qce

1571 kWh

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

55 dB(A)

55 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

212 %

160 %

Prated

20.00 kW

20.00 kW

SCOP

5.37

4.07

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

20.00 kW

20.00 kW

COP Tj = +2°C

3.39

2.08

Cdh Tj = +2 °C

0.990

0.990

Pdh Tj = +7°C

12.80 kW

12.90 kW

COP Tj = +7°C

5.22

3.78

Cdh Tj = +7 °C

0.980

0.990

Pdh Tj = 12°C

8.60 kW

7.90 kW

COP Tj = 12°C

6.07

4.92

Cdh Tj = +12 °C

0.960

0.970

Pdh Tj = Tbiv

20.00 kW

20.00 kW

COP Tj = Tbiv

3.39

2.08

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

20.00 kW

20.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.39

2.08

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

0.990

WTOL

55 °C

55 °C

Poff

40 W

40 W

PTO

50 W

50 W

PSB

40 W

40 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

kW

kW

Annual energy consumption Qhe

4975 kWh

6559 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

55 dB(A)

55 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

120 %

100 %

Prated

20.00 kW

20.00 kW

SCOP

3.07

2.57

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

12.10 kW

12.10 kW

COP Tj = -7°C

2.43

1.97

Cdh Tj = -7 °C

0.990

0.990

Pdh Tj = +2°C

7.30 kW

7.30 kW

COP Tj = +2°C

3.49

3.06

Cdh Tj = +2 °C

0.980

0.980

Pdh Tj = +7°C

7.60 kW

7.00 kW

COP Tj = +7°C

4.63

3.78

Cdh Tj = +7 °C

0.970

0.970

Pdh Tj = 12°C

8.60 kW

8.10 kW

COP Tj = 12°C

6.01

5.28

Cdh Tj = +12 °C

0.970

0.970

Pdh Tj = Tbiv

16.30 kW

16.30 kW

COP Tj = Tbiv

2.37

1.86

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

19.00 kW

19.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

1.77

1.38

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

55 °C

55 °C

Poff

40 W

40 W

PTO

50 W

50 W

PSB

40 W

40 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

1.00 kW

1.00 kW

Annual energy consumption Qhe

16056 kWh

19167 kWh

Pdh Tj = -15°C (if TOL<-20°C)

16.30

16.30

COP Tj = -15°C (if TOL<-20°C)

2.37

1.86

Cdh Tj = -15 °C

0.990

0.990

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

55 dB(A)

55 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

171 %

141 %

Prated

20.00 kW

20.00 kW

SCOP

4.36

3.59

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

18.90 kW

22.20 kW

COP Tj = -7°C

2.99

2.19

Cdh Tj = -7 °C

0.990

1.000

Pdh Tj = +2°C

11.60 kW

10.90 kW

COP Tj = +2°C

4.12

3.54

Cdh Tj = +2 °C

0.980

0.980

Pdh Tj = +7°C

8.70 kW

8.70 kW

COP Tj = +7°C

5.96

4.71

Cdh Tj = +7 °C

0.970

0.970

Pdh Tj = 12°C

8.80 kW

9.80 kW

COP Tj = 12°C

6.12

5.92

Cdh Tj = +12 °C

0.970

0.970

Pdh Tj = Tbiv

22.50 kW

22.50 kW

COP Tj = Tbiv

2.40

1.91

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

22.50 kW

22.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.40

1.91

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

1.000

WTOL

55 °C

55 °C

Poff

40 W

40 W

PTO

50 W

50 W

PSB

40 W

40 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

kW

kW

Annual energy consumption Qhe

9483 kWh

11496 kWh

WH-CME8L / WH-WXG20ME8
Configure model
Model name
WH-CME8L / WH-WXG20ME8
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

20.00 kW

20.00 kW

El input

4.16 kW

6.28 kW

COP

4.80

3.18

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

El input

6.62 kW

Cooling capacity

20.00

EER

3.02

EN 14825

+7°C/+12°C

Pdesignc

20.00 kW

SEER

4.45

Pdc Tj = 35°C

20.00 kW

EER Tj = 35°C

3.02

Cdc Tj = 35 °C

1.000

Pdc Tj = 30°C

14.74 kW

EER Tj = 30°C

4.39

Cdc Tj = 30 °C

0.990

Pdc Tj = 25°C

9.47 kW

EER Tj = 25°C

5.31

Cdc Tj = 25 °C

0.970

Pdc Tj = 20°C

6.39 kW

EER Tj = 20°C

5.13

Cdc Tj = 20 °C

0.960

Poff

40 W

PTO

50 W

PSB

40 W

PCK

0 W

Annual energy consumption Qce

1571 kWh

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

55 dB(A)

55 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

212 %

160 %

Prated

20.00 kW

20.00 kW

SCOP

5.37

4.07

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

20.00 kW

20.00 kW

COP Tj = +2°C

3.39

2.08

Cdh Tj = +2 °C

0.990

0.990

Pdh Tj = +7°C

12.80 kW

12.90 kW

COP Tj = +7°C

5.22

3.78

Cdh Tj = +7 °C

0.980

0.990

Pdh Tj = 12°C

8.60 kW

7.90 kW

COP Tj = 12°C

6.07

4.92

Cdh Tj = +12 °C

0.960

0.970

Pdh Tj = Tbiv

20.00 kW

20.00 kW

COP Tj = Tbiv

3.39

2.08

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

20.00 kW

20.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.39

2.08

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

0.990

WTOL

55 °C

55 °C

Poff

40 W

40 W

PTO

50 W

50 W

PSB

40 W

40 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

kW

kW

Annual energy consumption Qhe

4975 kWh

6559 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

55 dB(A)

55 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

120 %

100 %

Prated

20.00 kW

20.00 kW

SCOP

3.07

2.57

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

12.10 kW

12.10 kW

COP Tj = -7°C

2.43

1.97

Cdh Tj = -7 °C

0.990

0.990

Pdh Tj = +2°C

7.30 kW

7.30 kW

COP Tj = +2°C

3.49

3.06

Cdh Tj = +2 °C

0.980

0.980

Pdh Tj = +7°C

7.60 kW

7.00 kW

COP Tj = +7°C

4.63

3.78

Cdh Tj = +7 °C

0.970

0.970

Pdh Tj = 12°C

8.60 kW

8.10 kW

COP Tj = 12°C

6.01

5.28

Cdh Tj = +12 °C

0.970

0.970

Pdh Tj = Tbiv

16.30 kW

16.30 kW

COP Tj = Tbiv

2.37

1.86

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

19.00 kW

19.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

1.77

1.38

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

55 °C

55 °C

Poff

40 W

40 W

PTO

50 W

50 W

PSB

40 W

40 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

1.00 kW

1.00 kW

Annual energy consumption Qhe

16056 kWh

19167 kWh

Pdh Tj = -15°C (if TOL<-20°C)

16.30

16.30

COP Tj = -15°C (if TOL<-20°C)

2.37

1.86

Cdh Tj = -15 °C

0.990

0.990

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

55 dB(A)

55 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

171 %

141 %

Prated

20.00 kW

20.00 kW

SCOP

4.36

3.59

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

18.90 kW

22.20 kW

COP Tj = -7°C

2.99

2.19

Cdh Tj = -7 °C

0.990

1.000

Pdh Tj = +2°C

11.60 kW

10.90 kW

COP Tj = +2°C

4.12

3.54

Cdh Tj = +2 °C

0.980

0.980

Pdh Tj = +7°C

8.70 kW

8.70 kW

COP Tj = +7°C

5.96

4.71

Cdh Tj = +7 °C

0.970

0.970

Pdh Tj = 12°C

8.80 kW

9.80 kW

COP Tj = 12°C

6.12

5.92

Cdh Tj = +12 °C

0.970

0.970

Pdh Tj = Tbiv

22.50 kW

22.50 kW

COP Tj = Tbiv

2.40

1.91

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

22.50 kW

22.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.40

1.91

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

1.000

WTOL

55 °C

55 °C

Poff

40 W

40 W

PTO

50 W

50 W

PSB

40 W

40 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

kW

kW

Annual energy consumption Qhe

9483 kWh

11496 kWh

WH-WXG25ME8 (Outdoor unit Stand-alone)
Configure model
Model name
WH-WXG25ME8 (Outdoor unit Stand-alone)
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

25.00 kW

25.00 kW

El input

5.55 kW

8.33 kW

COP

4.50

3.00

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

El input

8.74 kW

Cooling capacity

25.00

EER

2.86

EN 14825

+7°C/+12°C

Pdesignc

25.00 kW

SEER

4.58

Pdc Tj = 35°C

25.00 kW

EER Tj = 35°C

2.86

Cdc Tj = 35 °C

1.000

Pdc Tj = 30°C

18.42 kW

EER Tj = 30°C

4.31

Cdc Tj = 30 °C

0.990

Pdc Tj = 25°C

11.84 kW

EER Tj = 25°C

5.55

Cdc Tj = 25 °C

0.980

Pdc Tj = 20°C

6.56 kW

EER Tj = 20°C

5.29

Cdc Tj = 20 °C

0.960

Poff

40 W

PTO

50 W

PSB

40 W

PCK

0 W

Annual energy consumption Qce

1911 kWh

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

58 dB(A)

58 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

206 %

163 %

Prated

25.00 kW

25.00 kW

SCOP

5.22

4.14

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

25.00 kW

25.00 kW

COP Tj = +2°C

2.80

1.97

Cdh Tj = +2 °C

0.990

1.000

Pdh Tj = +7°C

16.00 kW

16.00 kW

COP Tj = +7°C

5.02

3.68

Cdh Tj = +7 °C

0.980

0.990

Pdh Tj = 12°C

8.70 kW

8.00 kW

COP Tj = 12°C

6.03

5.23

Cdh Tj = +12 °C

0.970

0.970

Pdh Tj = Tbiv

25.00 kW

25.00 kW

COP Tj = Tbiv

2.80

1.97

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

25.00 kW

25.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.80

1.97

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

1.000

WTOL

55 °C

55 °C

Poff

40 W

40 W

PTO

50 W

50 W

PSB

40 W

40 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

kW

kW

Annual energy consumption Qhe

6395 kWh

8063 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

58 dB(A)

58 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

123 %

105 %

Prated

25.00 kW

25.00 kW

SCOP

3.16

2.71

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

15.10 kW

15.10 kW

COP Tj = -7°C

2.45

2.02

Cdh Tj = -7 °C

0.990

0.990

Pdh Tj = +2°C

9.20 kW

9.20 kW

COP Tj = +2°C

3.76

3.33

Cdh Tj = +2 °C

0.980

0.980

Pdh Tj = +7°C

7.70 kW

7.10 kW

COP Tj = +7°C

4.45

4.03

Cdh Tj = +7 °C

0.970

0.970

Pdh Tj = 12°C

8.70 kW

8.10 kW

COP Tj = 12°C

5.80

5.20

Cdh Tj = +12 °C

0.970

0.970

Pdh Tj = Tbiv

20.30 kW

20.30 kW

COP Tj = Tbiv

2.41

1.93

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

19.00 kW

19.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

1.76

1.43

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

55 °C

55 °C

Poff

40 W

40 W

PTO

50 W

50 W

PSB

40 W

40 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

6.00 kW

6.00 kW

Annual energy consumption Qhe

19528 kWh

22759 kWh

Pdh Tj = -15°C (if TOL<-20°C)

20.30

20.30

COP Tj = -15°C (if TOL<-20°C)

2.41

1.93

Cdh Tj = -15 °C

0.990

1.000

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

58 dB(A)

58 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

167 %

140 %

Prated

25.00 kW

25.00 kW

SCOP

4.25

3.57

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

22.10 kW

24.40 kW

COP Tj = -7°C

2.42

2.09

Cdh Tj = -7 °C

0.990

1.000

Pdh Tj = +2°C

13.50 kW

13.90 kW

COP Tj = +2°C

4.24

3.55

Cdh Tj = +2 °C

0.980

0.990

Pdh Tj = +7°C

8.70 kW

9.80 kW

COP Tj = +7°C

5.88

4.78

Cdh Tj = +7 °C

0.970

0.980

Pdh Tj = 12°C

8.80 kW

9.80 kW

COP Tj = 12°C

6.08

5.74

Cdh Tj = +12 °C

0.970

0.970

Pdh Tj = Tbiv

26.10 kW

27.10 kW

COP Tj = Tbiv

2.19

1.62

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

26.10 kW

27.10 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.19

1.62

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

55 °C

55 °C

Poff

40 W

40 W

PTO

50 W

50 W

PSB

40 W

40 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

kW

kW

Annual energy consumption Qhe

12152 kWh

14462 kWh

WH-CME8L / WH-WXG25ME8
Configure model
Model name
WH-CME8L / WH-WXG25ME8
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

25.00 kW

25.00 kW

El input

5.55 kW

8.33 kW

COP

4.50

3.00

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

El input

8.74 kW

Cooling capacity

25.00

EER

2.86

EN 14825

+7°C/+12°C

Pdesignc

25.00 kW

SEER

4.58

Pdc Tj = 35°C

25.00 kW

EER Tj = 35°C

2.86

Cdc Tj = 35 °C

1.000

Pdc Tj = 30°C

18.42 kW

EER Tj = 30°C

4.31

Cdc Tj = 30 °C

0.990

Pdc Tj = 25°C

11.84 kW

EER Tj = 25°C

5.55

Cdc Tj = 25 °C

0.980

Pdc Tj = 20°C

6.56 kW

EER Tj = 20°C

5.29

Cdc Tj = 20 °C

0.960

Poff

40 W

PTO

50 W

PSB

40 W

PCK

0 W

Annual energy consumption Qce

1911 kWh

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

58 dB(A)

58 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

206 %

163 %

Prated

25.00 kW

25.00 kW

SCOP

5.22

4.14

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

25.00 kW

25.00 kW

COP Tj = +2°C

2.80

1.97

Cdh Tj = +2 °C

0.990

1.000

Pdh Tj = +7°C

16.00 kW

16.00 kW

COP Tj = +7°C

5.02

3.68

Cdh Tj = +7 °C

0.980

0.990

Pdh Tj = 12°C

8.70 kW

8.00 kW

COP Tj = 12°C

6.03

5.23

Cdh Tj = +12 °C

0.970

0.970

Pdh Tj = Tbiv

25.00 kW

25.00 kW

COP Tj = Tbiv

2.80

1.97

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

25.00 kW

25.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.80

1.97

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

1.000

WTOL

55 °C

55 °C

Poff

40 W

40 W

PTO

50 W

50 W

PSB

40 W

40 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

kW

kW

Annual energy consumption Qhe

6395 kWh

8063 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

58 dB(A)

58 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

123 %

105 %

Prated

25.00 kW

25.00 kW

SCOP

3.16

2.71

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

15.10 kW

15.10 kW

COP Tj = -7°C

2.45

2.02

Cdh Tj = -7 °C

0.990

0.990

Pdh Tj = +2°C

9.20 kW

9.20 kW

COP Tj = +2°C

3.76

3.33

Cdh Tj = +2 °C

0.980

0.980

Pdh Tj = +7°C

7.70 kW

7.10 kW

COP Tj = +7°C

4.45

4.03

Cdh Tj = +7 °C

0.970

0.970

Pdh Tj = 12°C

8.70 kW

8.10 kW

COP Tj = 12°C

5.80

5.20

Cdh Tj = +12 °C

0.970

0.970

Pdh Tj = Tbiv

20.30 kW

20.30 kW

COP Tj = Tbiv

2.41

1.93

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

19.00 kW

19.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

1.76

1.43

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

55 °C

55 °C

Poff

40 W

40 W

PTO

50 W

50 W

PSB

40 W

40 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

6.00 kW

6.00 kW

Annual energy consumption Qhe

19528 kWh

22759 kWh

Pdh Tj = -15°C (if TOL<-20°C)

20.30

20.30

COP Tj = -15°C (if TOL<-20°C)

2.41

1.93

Cdh Tj = -15 °C

0.990

1.000

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

58 dB(A)

58 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

167 %

140 %

Prated

25.00 kW

25.00 kW

SCOP

4.25

3.57

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

22.10 kW

24.40 kW

COP Tj = -7°C

2.42

2.09

Cdh Tj = -7 °C

0.990

1.000

Pdh Tj = +2°C

13.50 kW

13.90 kW

COP Tj = +2°C

4.24

3.55

Cdh Tj = +2 °C

0.980

0.990

Pdh Tj = +7°C

8.70 kW

9.80 kW

COP Tj = +7°C

5.88

4.78

Cdh Tj = +7 °C

0.970

0.980

Pdh Tj = 12°C

8.80 kW

9.80 kW

COP Tj = 12°C

6.08

5.74

Cdh Tj = +12 °C

0.970

0.970

Pdh Tj = Tbiv

26.10 kW

27.10 kW

COP Tj = Tbiv

2.19

1.62

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

26.10 kW

27.10 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.19

1.62

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

55 °C

55 °C

Poff

40 W

40 W

PTO

50 W

50 W

PSB

40 W

40 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

kW

kW

Annual energy consumption Qhe

12152 kWh

14462 kWh