1,050 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
7.76 kW
7.94 kW
El input
1.56 kW
2.54 kW
COP
4.98
3.13
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
199 %
149 %
Prated
9.96 kW
9.87 kW
SCOP
5.05
3.80
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
8.81 kW
8.73 kW
COP Tj = -7°C
3.37
2.41
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
5.45 kW
5.35 kW
COP Tj = +2°C
4.97
3.72
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
5.40 kW
4.06 kW
COP Tj = +7°C
6.87
5.01
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
6.32 kW
4.88 kW
COP Tj = 12°C
8.70
6.89
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
8.81 kW
8.73 kW
COP Tj = Tbiv
3.37
2.41
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.73 kW
10.01 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.84
2.12
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
21 W
21 W
PSB
15 W
15 W
PCK
42 W
42 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.23 kW
0.00 kW
Annual energy consumption Qhe
4073 kWh
5369 kWh