4,400 kg
Brine/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
26.71 kW
22.39 kW
El input
5.81 kW
7.52 kW
COP
4.60
2.98
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
48 dB(A)
50 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
220 %
167 %
Prated
38.06 kW
35.62 kW
SCOP
5.70
4.38
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
38.06 kW
35.62 kW
COP Tj = +2°C
4.29
2.95
Pdh Tj = +7°C
24.47 kW
22.90 kW
COP Tj = +7°C
5.35
3.89
Pdh Tj = 12°C
12.71 kW
12.48 kW
COP Tj = 12°C
6.31
5.17
Pdh Tj = Tbiv
38.06 kW
35.62 kW
COP Tj = Tbiv
4.29
2.95
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
38.06 kW
35.62 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.29
2.95
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
0.99
WTOL
65 °C
65 °C
Poff
7 W
7 W
PTO
7 W
7 W
PSB
7 W
7 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
8920 kWh
10862 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
48 dB(A)
50 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
226 %
174 %
Prated
38.06 kW
35.62 kW
SCOP
5.86
4.55
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
23.04 kW
21.56 kW
COP Tj = -7°C
5.57
4.12
Pdh Tj = +2°C
14.02 kW
13.12 kW
COP Tj = +2°C
6.27
5.02
Pdh Tj = +7°C
12.71 kW
12.56 kW
COP Tj = +7°C
6.35
5.32
Pdh Tj = 12°C
12.70 kW
12.65 kW
COP Tj = 12°C
6.19
5.49
Pdh Tj = Tbiv
38.06 kW
35.62 kW
COP Tj = Tbiv
4.29
2.95
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
38.06 kW
35.62 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.29
2.95
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
0.99
WTOL
65 °C
65 °C
Poff
7 W
7 W
PTO
7 W
7 W
PSB
7 W
7 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
16014 kWh
19290 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
48 dB(A)
50 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
218 %
168 %
Prated
38.06 kW
35.62 kW
SCOP
5.65
4.39
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
33.67 kW
31.51 kW
COP Tj = -7°C
4.56
3.21
Pdh Tj = +2°C
20.49 kW
19.18 kW
COP Tj = +2°C
5.68
4.39
Pdh Tj = +7°C
13.18 kW
12.33 kW
COP Tj = +7°C
6.28
5.16
Pdh Tj = 12°C
12.70 kW
12.57 kW
COP Tj = 12°C
6.31
5.34
Pdh Tj = Tbiv
38.06 kW
35.62 kW
COP Tj = Tbiv
4.29
2.95
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
38.06 kW
35.62 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.29
2.95
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
0.99
WTOL
65 °C
65 °C
Poff
7 W
7 W
PTO
7 W
7 W
PSB
7 W
7 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
13917 kWh
16768 kWh
Water/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
30.84 kW
42.37 kW
El input
4.88 kW
11.23 kW
COP
6.31
3.77
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
48 dB(A)
50 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
327 %
220 %
Prated
52.17 kW
53.25 kW
SCOP
8.37
5.69
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
52.17 kW
53.25 kW
COP Tj = +2°C
4.19
3.25
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
33.54 kW
34.23 kW
COP Tj = +7°C
7.30
4.71
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
14.90 kW
15.21 kW
COP Tj = 12°C
10.66
7.43
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
52.17 kW
53.25 kW
COP Tj = Tbiv
4.19
3.25
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
52.17 kW
53.25 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.19
3.25
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
65 °C
65 °C
Poff
12 W
12 W
PTO
12 W
12 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
8327 kWh
12498 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
48 dB(A)
50 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
334 %
225 %
Prated
52.17 kW
53.25 kW
SCOP
8.55
5.81
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
31.57 kW
32.23 kW
COP Tj = -7°C
7.69
5.03
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
19.22 kW
19.62 kW
COP Tj = +2°C
9.86
6.61
Cdh Tj = +2 °C
0.990
1.000
Pdh Tj = +7°C
15.62 kW
15.45 kW
COP Tj = +7°C
10.62
7.68
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
15.54 kW
15.47 kW
COP Tj = 12°C
9.93
7.81
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
52.17 kW
53.25 kW
COP Tj = Tbiv
4.19
3.25
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
52.17 kW
53.25 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.19
3.25
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
65 °C
65 °C
Poff
12 W
12 W
PTO
12 W
12 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
15035 kWh
22576 kWh
Pdh Tj = -15°C (if TOL<-20°C)
25.16
34.57
COP Tj = -15°C (if TOL<-20°C)
7.15
4.59
Cdh Tj = -15 °C
1.00
1.00
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
48 dB(A)
50 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
315 %
214 %
Prated
52.17 kW
53.25 kW
SCOP
8.08
5.54
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
46.15 kW
47.11 kW
COP Tj = -7°C
5.81
3.83
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
28.09 kW
28.67 kW
COP Tj = +2°C
7.97
5.43
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
18.06 kW
18.43 kW
COP Tj = +7°C
9.93
6.88
Cdh Tj = +7 °C
0.990
1.000
Pdh Tj = 12°C
15.60 kW
15.43 kW
COP Tj = 12°C
10.39
7.59
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
52.17 kW
53.25 kW
COP Tj = Tbiv
4.19
3.25
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
52.17 kW
53.25 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.19
3.25
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
65 °C
65 °C
Poff
12 W
12 W
PTO
12 W
12 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
13342 kWh
19861 kWh