Certificate holders

Subtype

ETERA M

Certificate Holder
KRONOTERM d.o.o.
Trnava 5e
3303 Gomilsko
Slovenia
Registration number
011-1W0886
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
ETERA M
Driving energy
Electricity
Heat Pump Type
Brine/Water and Water/Water
Refrigerant
R452B
Mass of Refrigerant

1,300 kg

Certification Date
26.09.2024
Testing basis
HP KEYMARK certification scheme rules V14
Testing laboratory
TÜV Rheinland Energy GmbH, DE
Generate PDF Export model CSV
  • Number of models 3

Models

ETERA M-1 HT / HK 3F E
Configure model
Model name
ETERA M-1 HT / HK 3F E
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x230V 50Hz

Brine/Water Heat Pump

Heating

EN 14511-4

Starting and operating test

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

6.11 kW

8.11 kW

El input

1.24 kW

2.59 kW

COP

4.89

3.13

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

34 dB(A)

36 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

214 %

156 %

Prated

12.20 kW

12.10 kW

SCOP

5.55

4.09

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

12.20 kW

12.07 kW

COP Tj = +2°C

4.81

3.18

Cdh Tj = +2 °C

0.996

0.998

Pdh Tj = +7°C

7.87 kW

7.94 kW

COP Tj = +7°C

5.55

3.89

Cdh Tj = +7 °C

0.994

0.996

Pdh Tj = 12°C

3.78 kW

3.69 kW

COP Tj = 12°C

5.72

4.44

Cdh Tj = +12 °C

0.987

0.990

Pdh Tj = Tbiv

12.20 kW

12.07 kW

COP Tj = Tbiv

4.81

3.18

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.20 kW

12.07 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.81

3.18

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.996

0.998

WTOL

67 °C

67 °C

Poff

9 W

9 W

PTO

9 W

9 W

PSB

9 W

9 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

kW

kW

Annual energy consumption Qhe

2935 kWh

3956 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

34 dB(A)

36 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

225 %

158 %

Prated

12.20 kW

12.10 kW

SCOP

5.82

4.16

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

7.52 kW

7.36 kW

COP Tj = -7°C

5.77

3.91

Cdh Tj = -7 °C

0.993

0.995

Pdh Tj = +2°C

4.88 kW

4.56 kW

COP Tj = +2°C

6.03

4.38

Cdh Tj = +2 °C

0.989

0.992

Pdh Tj = +7°C

3.97 kW

3.55 kW

COP Tj = +7°C

5.96

4.61

Cdh Tj = +7 °C

0.987

0.989

Pdh Tj = 12°C

3.46 kW

3.59 kW

COP Tj = 12°C

5.80

5.09

Cdh Tj = +12 °C

0.986

0.988

Pdh Tj = Tbiv

12.20 kW

12.07 kW

COP Tj = Tbiv

4.81

3.18

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.20 kW

12.07 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.81

3.18

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.996

0.998

WTOL

67 °C

67 °C

Poff

9 W

9 W

PTO

9 W

9 W

PSB

9 W

9 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

kW

kW

Annual energy consumption Qhe

5167 kWh

7172 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

34 dB(A)

36 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

220 %

156 %

Prated

12.20 kW

12.10 kW

SCOP

5.70

4.10

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.81 kW

10.67 kW

COP Tj = -7°C

4.96

3.39

Cdh Tj = -7 °C

0.996

0.997

Pdh Tj = +2°C

7.07 kW

6.65 kW

COP Tj = +2°C

5.81

4.11

Cdh Tj = +2 °C

0.993

0.994

Pdh Tj = +7°C

4.68 kW

4.26 kW

COP Tj = +7°C

6.01

4.42

Cdh Tj = +7 °C

0.989

0.991

Pdh Tj = 12°C

3.97 kW

3.58 kW

COP Tj = 12°C

5.96

4.84

Cdh Tj = +12 °C

0.987

0.988

Pdh Tj = Tbiv

12.20 kW

12.07 kW

COP Tj = Tbiv

4.81

3.18

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.20 kW

12.07 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.81

3.18

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.996

0.998

WTOL

67 °C

67 °C

Poff

9 W

9 W

PTO

9 W

9 W

PSB

9 W

9 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

kW

kW

Annual energy consumption Qhe

4420 kWh

6095 kWh

Water/Water Heat Pump

Heating

EN 14511-4

Starting and operating test

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

6.06 kW

8.10 kW

El input

0.90 kW

2.09 kW

COP

6.72

3.88

Warmer Climate

EN 14825

Low temperature

Medium temperature

ηs

317 %

213 %

Prated

12.10 kW

12.00 kW

SCOP

8.13

5.52

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

12.15 kW

12.05 kW

COP Tj = +2°C

6.63

3.96

Cdh Tj = +2 °C

0.995

0.997

Pdh Tj = +7°C

7.97 kW

7.94 kW

COP Tj = +7°C

7.78

5.05

Cdh Tj = +7 °C

0.992

0.994

Pdh Tj = 12°C

4.04 kW

4.04 kW

COP Tj = 12°C

8.83

6.33

Cdh Tj = +12 °C

0.982

0.987

Pdh Tj = Tbiv

12.15 kW

12.05 kW

COP Tj = Tbiv

6.63

3.96

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.15 kW

12.05 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

6.63

3.96

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.997

WTOL

67 °C

67 °C

Poff

9 W

9 W

PTO

9 W

9 W

PSB

9 W

9 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

kW

kW

Annual energy consumption Qhe

1987 kWh

2902 kWh

Colder Climate

EN 14825

Low temperature

Medium temperature

ηs

324 %

220 %

Prated

12.20 kW

12.00 kW

SCOP

8.31

5.70

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

7.46 kW

7.46 kW

COP Tj = -7°C

8.02

5.35

Cdh Tj = -7 °C

0.991

0.994

Pdh Tj = +2°C

4.57 kW

4.58 kW

COP Tj = +2°C

8.67

6.03

Cdh Tj = +2 °C

0.984

0.989

Pdh Tj = +7°C

4.02 kW

4.03 kW

COP Tj = +7°C

9.05

6.62

Cdh Tj = +7 °C

0.982

0.986

Pdh Tj = 12°C

4.03 kW

4.04 kW

COP Tj = 12°C

8.81

7.20

Cdh Tj = +12 °C

0.982

0.985

Pdh Tj = Tbiv

12.15 kW

12.05 kW

COP Tj = Tbiv

6.63

3.96

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.15 kW

12.05 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

6.63

3.96

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.997

WTOL

67 °C

67 °C

Poff

9 W

9 W

PTO

9 W

9 W

PSB

9 W

9 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

kW

kW

Annual energy consumption Qhe

3621 kWh

5190 kWh

Average Climate

EN 14825

Low temperature

Medium temperature

ηs

313 %

213 %

Prated

12.10 kW

12.00 kW

SCOP

8.02

5.52

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.90 kW

10.83 kW

COP Tj = -7°C

6.89

4.20

Cdh Tj = -7 °C

0.994

0.997

Pdh Tj = +2°C

6.60 kW

6.56 kW

COP Tj = +2°C

8.07

5.58

Cdh Tj = +2 °C

0.990

0.993

Pdh Tj = +7°C

4.27 kW

4.28 kW

COP Tj = +7°C

8.50

6.14

Cdh Tj = +7 °C

0.984

0.988

Pdh Tj = 12°C

4.02 kW

4.01 kW

COP Tj = 12°C

9.05

6.81

Cdh Tj = +12 °C

0.982

0.986

Pdh Tj = Tbiv

12.15 kW

12.05 kW

COP Tj = Tbiv

6.63

3.96

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.15 kW

12.05 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

6.63

3.96

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.997

WTOL

67 °C

67 °C

Poff

9 W

9 W

PTO

9 W

9 W

PSB

9 W

9 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

kW

kW

Annual energy consumption Qhe

3118 kWh

4489 kWh

ETERA-C M-1 HT / HK 3F
Configure model
Model name
ETERA-C M-1 HT / HK 3F
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Brine/Water Heat Pump

Heating

EN 14511-4

Starting and operating test

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

6.05 kW

8.11 kW

El input

1.24 kW

2.59 kW

COP

4.89

3.13

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

34 dB(A)

36 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

214 %

156 %

Prated

12.20 kW

12.10 kW

SCOP

5.55

4.09

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

12.20 kW

12.07 kW

COP Tj = +2°C

4.81

3.18

Cdh Tj = +2 °C

0.996

0.998

Pdh Tj = +7°C

7.87 kW

7.94 kW

COP Tj = +7°C

5.55

3.89

Cdh Tj = +7 °C

0.994

0.996

Pdh Tj = 12°C

3.78 kW

3.69 kW

COP Tj = 12°C

5.72

4.44

Cdh Tj = +12 °C

0.987

0.990

Pdh Tj = Tbiv

12.20 kW

12.07 kW

COP Tj = Tbiv

4.81

3.18

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.20 kW

12.07 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.81

3.18

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.996

0.998

WTOL

67 °C

67 °C

Poff

9 W

9 W

PTO

9 W

9 W

PSB

9 W

9 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

kW

kW

Annual energy consumption Qhe

2935 kWh

3956 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

34 dB(A)

36 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

225 %

158 %

Prated

12.20 kW

12.10 kW

SCOP

5.82

4.16

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

7.52 kW

7.36 kW

COP Tj = -7°C

5.77

3.91

Cdh Tj = -7 °C

0.993

0.995

Pdh Tj = +2°C

4.88 kW

4.56 kW

COP Tj = +2°C

6.03

4.38

Cdh Tj = +2 °C

0.989

0.992

Pdh Tj = +7°C

3.97 kW

3.55 kW

COP Tj = +7°C

5.96

4.61

Cdh Tj = +7 °C

0.987

0.989

Pdh Tj = 12°C

3.46 kW

3.59 kW

COP Tj = 12°C

5.80

5.09

Cdh Tj = +12 °C

0.986

0.988

Pdh Tj = Tbiv

12.20 kW

12.07 kW

COP Tj = Tbiv

4.81

3.18

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.20 kW

12.07 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.81

3.18

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.996

0.998

WTOL

67 °C

67 °C

Poff

9 W

9 W

PTO

9 W

9 W

PSB

9 W

9 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

kW

kW

Annual energy consumption Qhe

5167 kWh

7172 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

34 dB(A)

36 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

220 %

156 %

Prated

12.20 kW

12.10 kW

SCOP

5.70

4.10

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.81 kW

10.67 kW

COP Tj = -7°C

4.96

3.39

Cdh Tj = -7 °C

0.996

0.997

Pdh Tj = +2°C

7.07 kW

6.65 kW

COP Tj = +2°C

5.81

4.11

Cdh Tj = +2 °C

0.993

0.994

Pdh Tj = +7°C

4.68 kW

4.26 kW

COP Tj = +7°C

6.01

4.42

Cdh Tj = +7 °C

0.989

0.991

Pdh Tj = 12°C

3.97 kW

3.58 kW

COP Tj = 12°C

5.96

4.84

Cdh Tj = +12 °C

0.987

0.988

Pdh Tj = Tbiv

12.20 kW

12.07 kW

COP Tj = Tbiv

4.81

3.18

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.20 kW

12.07 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.81

3.18

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.996

0.998

WTOL

67 °C

67 °C

Poff

9 W

9 W

PTO

9 W

9 W

PSB

9 W

9 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

kW

kW

Annual energy consumption Qhe

4420 kWh

6095 kWh

Water/Water Heat Pump

Heating

EN 14511-4

Starting and operating test

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

6.06 kW

8.10 kW

El input

0.90 kW

2.09 kW

COP

6.72

3.88

Warmer Climate

EN 14825

Low temperature

Medium temperature

ηs

317 %

213 %

Prated

12.10 kW

12.00 kW

SCOP

8.13

5.52

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

12.15 kW

12.05 kW

COP Tj = +2°C

6.63

3.96

Cdh Tj = +2 °C

0.995

0.997

Pdh Tj = +7°C

7.97 kW

7.94 kW

COP Tj = +7°C

7.78

5.05

Cdh Tj = +7 °C

0.992

0.994

Pdh Tj = 12°C

4.04 kW

4.04 kW

COP Tj = 12°C

8.83

6.33

Cdh Tj = +12 °C

0.982

0.987

Pdh Tj = Tbiv

12.15 kW

12.05 kW

COP Tj = Tbiv

6.63

3.96

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.15 kW

12.05 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

6.63

3.96

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.997

WTOL

67 °C

67 °C

Poff

9 W

9 W

PTO

9 W

9 W

PSB

9 W

9 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

kW

kW

Annual energy consumption Qhe

1987 kWh

2902 kWh

Colder Climate

EN 14825

Low temperature

Medium temperature

ηs

324 %

220 %

Prated

12.20 kW

12.00 kW

SCOP

8.31

5.70

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

7.46 kW

7.46 kW

COP Tj = -7°C

8.02

5.35

Cdh Tj = -7 °C

0.991

0.994

Pdh Tj = +2°C

4.57 kW

4.58 kW

COP Tj = +2°C

8.67

6.03

Cdh Tj = +2 °C

0.984

0.989

Pdh Tj = +7°C

4.02 kW

4.03 kW

COP Tj = +7°C

9.05

6.62

Cdh Tj = +7 °C

0.982

0.986

Pdh Tj = 12°C

4.03 kW

4.04 kW

COP Tj = 12°C

8.81

7.20

Cdh Tj = +12 °C

0.982

0.985

Pdh Tj = Tbiv

12.15 kW

12.05 kW

COP Tj = Tbiv

6.63

3.96

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.15 kW

12.05 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

6.63

3.96

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.997

WTOL

67 °C

67 °C

Poff

9 W

9 W

PTO

9 W

9 W

PSB

9 W

9 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

kW

kW

Annual energy consumption Qhe

3621 kWh

5190 kWh

Average Climate

EN 14825

Low temperature

Medium temperature

ηs

313 %

213 %

Prated

12.10 kW

12.00 kW

SCOP

8.02

5.52

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.90 kW

10.83 kW

COP Tj = -7°C

6.89

4.20

Cdh Tj = -7 °C

0.994

0.997

Pdh Tj = +2°C

6.60 kW

6.56 kW

COP Tj = +2°C

8.07

5.58

Cdh Tj = +2 °C

0.990

0.993

Pdh Tj = +7°C

4.27 kW

4.28 kW

COP Tj = +7°C

8.50

6.14

Cdh Tj = +7 °C

0.984

0.988

Pdh Tj = 12°C

4.02 kW

4.01 kW

COP Tj = 12°C

9.05

6.81

Cdh Tj = +12 °C

0.982

0.986

Pdh Tj = Tbiv

12.15 kW

12.05 kW

COP Tj = Tbiv

6.63

3.96

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.15 kW

12.05 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

6.63

3.96

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.997

WTOL

67 °C

67 °C

Poff

9 W

9 W

PTO

9 W

9 W

PSB

9 W

9 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

kW

kW

Annual energy consumption Qhe

3118 kWh

4489 kWh

ETERA M-1 HT / HK UF E
Configure model
Model name
ETERA M-1 HT / HK UF E
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Brine/Water Heat Pump

Heating

EN 14511-4

Starting and operating test

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

6.11 kW

8.10 kW

El input

1.23 kW

2.56 kW

COP

4.97

3.17

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

34 dB(A)

36 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

214 %

160 %

Prated

12.10 kW

12.10 kW

SCOP

5.55

4.20

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

12.18 kW

12.07 kW

COP Tj = +2°C

4.80

3.11

Cdh Tj = +2 °C

0.997

0.998

Pdh Tj = +7°C

7.93 kW

7.73 kW

COP Tj = +7°C

5.57

3.88

Cdh Tj = +7 °C

0.994

0.996

Pdh Tj = 12°C

3.61 kW

4.02 kW

COP Tj = 12°C

5.69

4.72

Cdh Tj = +12 °C

0.987

0.990

Pdh Tj = Tbiv

12.18 kW

12.07 kW

COP Tj = Tbiv

4.80

3.11

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.18 kW

12.07 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.80

3.11

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.997

0.998

WTOL

67 °C

67 °C

Poff

9 W

9 W

PTO

9 W

9 W

PSB

9 W

9 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2915 kWh

3852 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

34 dB(A)

36 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

226 %

165 %

Prated

12.10 kW

12.10 kW

SCOP

5.85

4.32

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

7.54 kW

7.46 kW

COP Tj = -7°C

5.79

4.10

Cdh Tj = -7 °C

0.994

0.995

Pdh Tj = +2°C

4.74 kW

4.57 kW

COP Tj = +2°C

6.02

4.53

Cdh Tj = +2 °C

0.990

0.992

Pdh Tj = +7°C

4.02 kW

4.09 kW

COP Tj = +7°C

6.14

4.99

Cdh Tj = +7 °C

0.988

0.990

Pdh Tj = 12°C

3.98 kW

4.01 kW

COP Tj = 12°C

6.09

5.16

Cdh Tj = +12 °C

0.988

0.990

Pdh Tj = Tbiv

12.18 kW

12.07 kW

COP Tj = Tbiv

4.80

3.11

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.18 kW

12.07 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.80

3.11

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.997

0.998

WTOL

67 °C

67 °C

Poff

9 W

9 W

PTO

9 W

9 W

PSB

9 W

9 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5094 kWh

6898 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

34 dB(A)

36 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

220 %

162 %

Prated

12.10 kW

12.10 kW

SCOP

5.71

4.24

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.80 kW

10.70 kW

COP Tj = -7°C

4.97

3.35

Cdh Tj = -7 °C

0.996

0.997

Pdh Tj = +2°C

6.84 kW

6.68 kW

COP Tj = +2°C

5.79

4.29

Cdh Tj = +2 °C

0.993

0.995

Pdh Tj = +7°C

4.50 kW

4.30 kW

COP Tj = +7°C

6.00

4.62

Cdh Tj = +7 °C

0.989

0.991

Pdh Tj = 12°C

4.02 kW

4.07 kW

COP Tj = 12°C

6.14

5.06

Cdh Tj = +12 °C

0.988

0.990

Pdh Tj = Tbiv

12.18 kW

12.07 kW

COP Tj = Tbiv

4.80

3.11

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.18 kW

12.07 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.80

3.11

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.997

0.998

WTOL

67 °C

67 °C

Poff

9 W

9 W

PTO

9 W

9 W

PSB

9 W

9 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

4378 kWh

5895 kWh

Water/Water Heat Pump

Heating

EN 14511-4

Starting and operating test

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

6.02 kW

8.07 kW

El input

0.94 kW

2.07 kW

COP

6.40

3.90

Warmer Climate

EN 14825

Low temperature

Medium temperature

ηs

301 %

207 %

Prated

12.10 kW

12.10 kW

SCOP

7.72

5.38

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

12.16 kW

12.15 kW

COP Tj = +2°C

6.74

4.05

Cdh Tj = +2 °C

0.995

0.997

Pdh Tj = +7°C

7.97 kW

7.89 kW

COP Tj = +7°C

7.49

4.96

Cdh Tj = +7 °C

0.992

0.995

Pdh Tj = 12°C

4.02 kW

3.97 kW

COP Tj = 12°C

8.19

6.06

Cdh Tj = +12 °C

0.984

0.988

Pdh Tj = Tbiv

12.16 kW

12.15 kW

COP Tj = Tbiv

6.74

4.05

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.16 kW

12.15 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

6.74

4.05

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.997

WTOL

67 °C

67 °C

Poff

9 W

9 W

PTO

9 W

9 W

PSB

9 W

9 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2093 kWh

3005 kWh

Colder Climate

EN 14825

Low temperature

Medium temperature

ηs

311 %

215 %

Prated

12.10 kW

12.10 kW

SCOP

7.97

5.58

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

7.44 kW

7.52 kW

COP Tj = -7°C

7.73

5.26

Cdh Tj = -7 °C

0.991

0.994

Pdh Tj = +2°C

4.53 kW

4.61 kW

COP Tj = +2°C

8.13

5.84

Cdh Tj = +2 °C

0.986

0.989

Pdh Tj = +7°C

4.02 kW

4.00 kW

COP Tj = +7°C

9.02

6.44

Cdh Tj = +7 °C

0.983

0.987

Pdh Tj = 12°C

3.98 kW

4.07 kW

COP Tj = 12°C

8.32

7.04

Cdh Tj = +12 °C

0.984

0.986

Pdh Tj = Tbiv

12.16 kW

12.15 kW

COP Tj = Tbiv

6.74

4.05

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.16 kW

12.15 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

6.74

4.05

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.997

WTOL

67 °C

67 °C

Poff

9 W

9 W

PTO

9 W

9 W

PSB

9 W

9 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

3744 kWh

5348 kWh

Average Climate

EN 14825

Low temperature

Medium temperature

ηs

301 %

211 %

Prated

12.10 kW

12.10 kW

SCOP

7.72

5.47

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.88 kW

10.87 kW

COP Tj = -7°C

6.94

4.28

Cdh Tj = -7 °C

0.995

0.997

Pdh Tj = +2°C

6.70 kW

6.67 kW

COP Tj = +2°C

7.65

5.52

Cdh Tj = +2 °C

0.991

0.993

Pdh Tj = +7°C

4.33 kW

4.35 kW

COP Tj = +7°C

8.06

5.98

Cdh Tj = +7 °C

0.985

0.989

Pdh Tj = 12°C

4.02 kW

3.99 kW

COP Tj = 12°C

9.02

6.66

Cdh Tj = +12 °C

0.983

0.986

Pdh Tj = Tbiv

12.16 kW

12.15 kW

COP Tj = Tbiv

6.74

4.05

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.16 kW

12.15 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

6.74

4.05

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.997

WTOL

67 °C

67 °C

Poff

9 W

9 W

PTO

9 W

9 W

PSB

9 W

9 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

3239 kWh

4572 kWh