Certificate holders

Subtype

ETERA S

Certificate Holder
KRONOTERM d.o.o.
Trnava 5e
3303 Gomilsko
Slovenia
Registration number
011-1W0885
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
ETERA S
Driving energy
Electricity
Heat Pump Type
Brine/Water and Water/Water
Refrigerant
R452B
Mass of Refrigerant

1,100 kg

Certification Date
26.09.2024
Testing basis
HP KEYMARK certification scheme rules V14
Testing laboratory
TÜV Rheinland Energy GmbH, DE
Generate PDF Export model CSV
  • Number of models 1

Models

ETERA S-1 HT / HK UF E
Configure model
Model name
ETERA S-1 HT / HK UF E
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x230V 50Hz

Brine/Water Heat Pump

Heating

EN 14511-4

Starting and operating test

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

4.54 kW

5.96 kW

El input

0.96 kW

2.04 kW

COP

4.71

2.92

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

32 dB(A)

35 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

208 %

151 %

Prated

9.10 kW

9.00 kW

SCOP

5.39

3.97

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

9.08 kW

9.02 kW

COP Tj = +2°C

4.50

2.95

Cdh Tj = +2 °C

0.997

0.998

Pdh Tj = +7°C

5.96 kW

6.02 kW

COP Tj = +7°C

5.27

3.60

Cdh Tj = +7 °C

0.995

0.996

Pdh Tj = 12°C

2.99 kW

3.01 kW

COP Tj = 12°C

5.69

4.53

Cdh Tj = +12 °C

0.989

0.991

Pdh Tj = Tbiv

9.08 kW

9.02 kW

COP Tj = Tbiv

4.50

2.95

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.08 kW

9.02 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.50

2.95

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.997

0.998

WTOL

67 °C

67 °C

Poff

6 W

6 W

PTO

6 W

6 W

PSB

6 W

6 W

PCK

6 W

6 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

kW

kW

Annual energy consumption Qhe

2254 kWh

3030 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

32 dB(A)

35 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

218 %

158 %

Prated

9.10 kW

9.00 kW

SCOP

5.64

4.15

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

5.51 kW

5.65 kW

COP Tj = -7°C

5.43

3.78

Cdh Tj = -7 °C

0.994

0.996

Pdh Tj = +2°C

3.52 kW

3.61 kW

COP Tj = +2°C

5.90

4.49

Cdh Tj = +2 °C

0.990

0.992

Pdh Tj = +7°C

3.00 kW

3.06 kW

COP Tj = +7°C

6.06

4.82

Cdh Tj = +7 °C

0.988

0.990

Pdh Tj = 12°C

3.04 kW

3.09 kW

COP Tj = 12°C

6.05

5.20

Cdh Tj = +12 °C

0.988

0.990

Pdh Tj = Tbiv

9.08 kW

9.02 kW

COP Tj = Tbiv

4.50

2.95

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.08 kW

9.02 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.50

2.95

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.997

0.998

WTOL

67 °C

67 °C

Poff

6 W

6 W

PTO

6 W

6 W

PSB

6 W

6 W

PCK

6 W

6 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

kW

kW

Annual energy consumption Qhe

3979 kWh

5346 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

32 dB(A)

35 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

210 %

154 %

Prated

9.10 kW

9.00 kW

SCOP

5.45

4.04

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

7.97 kW

8.09 kW

COP Tj = -7°C

4.71

3.14

Cdh Tj = -7 °C

0.996

0.998

Pdh Tj = +2°C

4.93 kW

4.97 kW

COP Tj = +2°C

5.43

4.00

Cdh Tj = +2 °C

0.993

0.995

Pdh Tj = +7°C

3.43 kW

3.39 kW

COP Tj = +7°C

5.88

4.55

Cdh Tj = +7 °C

0.990

0.992

Pdh Tj = 12°C

3.00 kW

3.09 kW

COP Tj = 12°C

6.07

5.07

Cdh Tj = +12 °C

0.988

0.990

Pdh Tj = Tbiv

9.08 kW

9.02 kW

COP Tj = Tbiv

4.50

2.95

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.08 kW

9.02 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.50

2.95

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.997

0.998

WTOL

67 °C

67 °C

Poff

6 W

6 W

PTO

6 W

6 W

PSB

6 W

6 W

PCK

6 W

6 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

kW

kW

Annual energy consumption Qhe

3448 kWh

4605 kWh

Water/Water Heat Pump

Heating

EN 14511-4

Starting and operating test

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

4.52 kW

6.07 kW

El input

0.71 kW

1.61 kW

COP

6.40

3.77

Warmer Climate

EN 14825

Low temperature

Medium temperature

ηs

299 %

206 %

Prated

9.10 kW

9.10 kW

SCOP

7.68

5.34

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

9.09 kW

9.07 kW

COP Tj = +2°C

6.43

3.80

Cdh Tj = +2 °C

0.996

0.997

Pdh Tj = +7°C

5.95 kW

5.94 kW

COP Tj = +7°C

7.52

4.85

Cdh Tj = +7 °C

0.992

0.995

Pdh Tj = 12°C

3.00 kW

2.91 kW

COP Tj = 12°C

8.13

6.14

Cdh Tj = +12 °C

0.984

0.987

Pdh Tj = Tbiv

9.09 kW

9.07 kW

COP Tj = Tbiv

6.43

3.80

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.09 kW

9.07 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

6.43

3.80

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.996

0.997

WTOL

67 °C

67 °C

Poff

6 W

6 W

PTO

6 W

6 W

PSB

6 W

6 W

PCK

6 W

6 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

kW

kW

Annual energy consumption Qhe

1582 kWh

2278 kWh

Colder Climate

EN 14825

Low temperature

Medium temperature

ηs

309 %

215 %

Prated

9.10 kW

9.10 kW

SCOP

7.93

5.57

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

5.62 kW

5.59 kW

COP Tj = -7°C

7.81

5.13

Cdh Tj = -7 °C

0.992

0.994

Pdh Tj = +2°C

3.44 kW

3.48 kW

COP Tj = +2°C

8.20

5.95

Cdh Tj = +2 °C

0.986

0.990

Pdh Tj = +7°C

2.98 kW

2.99 kW

COP Tj = +7°C

8.43

6.66

Cdh Tj = +7 °C

0.983

0.987

Pdh Tj = 12°C

3.00 kW

2.98 kW

COP Tj = 12°C

8.13

7.34

Cdh Tj = +12 °C

0.984

0.985

Pdh Tj = Tbiv

9.09 kW

9.07 kW

COP Tj = Tbiv

6.43

3.80

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.09 kW

9.07 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

6.43

3.80

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.996

0.997

WTOL

67 °C

67 °C

Poff

6 W

6 W

PTO

6 W

6 W

PSB

6 W

6 W

PCK

6 W

6 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

kW

kW

Annual energy consumption Qhe

2827 kWh

4026 kWh

Average Climate

EN 14825

Low temperature

Medium temperature

ηs

299 %

207 %

Prated

9.10 kW

9.10 kW

SCOP

7.68

5.37

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

8.11 kW

8.08 kW

COP Tj = -7°C

6.81

4.12

Cdh Tj = -7 °C

0.995

0.997

Pdh Tj = +2°C

5.05 kW

4.99 kW

COP Tj = +2°C

7.65

5.35

Cdh Tj = +2 °C

0.991

0.993

Pdh Tj = +7°C

3.28 kW

3.24 kW

COP Tj = +7°C

8.19

6.01

Cdh Tj = +7 °C

0.985

0.989

Pdh Tj = 12°C

2.98 kW

3.01 kW

COP Tj = 12°C

8.43

7.00

Cdh Tj = +12 °C

0.983

0.986

Pdh Tj = Tbiv

9.09 kW

9.07 kW

COP Tj = Tbiv

6.43

3.80

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.09 kW

9.07 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

6.43

3.80

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.996

0.997

WTOL

67 °C

67 °C

Poff

6 W

6 W

PTO

6 W

6 W

PSB

6 W

6 W

PCK

6 W

6 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

kW

kW

Annual energy consumption Qhe

2449 kWh

3498 kWh