1,100 kg
Brine/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
4.54 kW
5.96 kW
El input
0.96 kW
2.04 kW
COP
4.71
2.92
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
32 dB(A)
35 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
208 %
151 %
Prated
9.10 kW
9.00 kW
SCOP
5.39
3.97
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
9.08 kW
9.02 kW
COP Tj = +2°C
4.50
2.95
Cdh Tj = +2 °C
0.997
0.998
Pdh Tj = +7°C
5.96 kW
6.02 kW
COP Tj = +7°C
5.27
3.60
Cdh Tj = +7 °C
0.995
0.996
Pdh Tj = 12°C
2.99 kW
3.01 kW
COP Tj = 12°C
5.69
4.53
Cdh Tj = +12 °C
0.989
0.991
Pdh Tj = Tbiv
9.08 kW
9.02 kW
COP Tj = Tbiv
4.50
2.95
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.08 kW
9.02 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.50
2.95
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.998
WTOL
67 °C
67 °C
Poff
6 W
6 W
PTO
6 W
6 W
PSB
6 W
6 W
PCK
6 W
6 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
kW
kW
Annual energy consumption Qhe
2254 kWh
3030 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
32 dB(A)
35 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
218 %
158 %
Prated
9.10 kW
9.00 kW
SCOP
5.64
4.15
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
5.51 kW
5.65 kW
COP Tj = -7°C
5.43
3.78
Cdh Tj = -7 °C
0.994
0.996
Pdh Tj = +2°C
3.52 kW
3.61 kW
COP Tj = +2°C
5.90
4.49
Cdh Tj = +2 °C
0.990
0.992
Pdh Tj = +7°C
3.00 kW
3.06 kW
COP Tj = +7°C
6.06
4.82
Cdh Tj = +7 °C
0.988
0.990
Pdh Tj = 12°C
3.04 kW
3.09 kW
COP Tj = 12°C
6.05
5.20
Cdh Tj = +12 °C
0.988
0.990
Pdh Tj = Tbiv
9.08 kW
9.02 kW
COP Tj = Tbiv
4.50
2.95
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.08 kW
9.02 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.50
2.95
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.998
WTOL
67 °C
67 °C
Poff
6 W
6 W
PTO
6 W
6 W
PSB
6 W
6 W
PCK
6 W
6 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
kW
kW
Annual energy consumption Qhe
3979 kWh
5346 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
32 dB(A)
35 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
210 %
154 %
Prated
9.10 kW
9.00 kW
SCOP
5.45
4.04
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
7.97 kW
8.09 kW
COP Tj = -7°C
4.71
3.14
Cdh Tj = -7 °C
0.996
0.998
Pdh Tj = +2°C
4.93 kW
4.97 kW
COP Tj = +2°C
5.43
4.00
Cdh Tj = +2 °C
0.993
0.995
Pdh Tj = +7°C
3.43 kW
3.39 kW
COP Tj = +7°C
5.88
4.55
Cdh Tj = +7 °C
0.990
0.992
Pdh Tj = 12°C
3.00 kW
3.09 kW
COP Tj = 12°C
6.07
5.07
Cdh Tj = +12 °C
0.988
0.990
Pdh Tj = Tbiv
9.08 kW
9.02 kW
COP Tj = Tbiv
4.50
2.95
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.08 kW
9.02 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.50
2.95
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.998
WTOL
67 °C
67 °C
Poff
6 W
6 W
PTO
6 W
6 W
PSB
6 W
6 W
PCK
6 W
6 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
kW
kW
Annual energy consumption Qhe
3448 kWh
4605 kWh
Water/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
4.52 kW
6.07 kW
El input
0.71 kW
1.61 kW
COP
6.40
3.77
Warmer Climate
EN 14825
Low temperature
Medium temperature
ηs
299 %
206 %
Prated
9.10 kW
9.10 kW
SCOP
7.68
5.34
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
9.09 kW
9.07 kW
COP Tj = +2°C
6.43
3.80
Cdh Tj = +2 °C
0.996
0.997
Pdh Tj = +7°C
5.95 kW
5.94 kW
COP Tj = +7°C
7.52
4.85
Cdh Tj = +7 °C
0.992
0.995
Pdh Tj = 12°C
3.00 kW
2.91 kW
COP Tj = 12°C
8.13
6.14
Cdh Tj = +12 °C
0.984
0.987
Pdh Tj = Tbiv
9.09 kW
9.07 kW
COP Tj = Tbiv
6.43
3.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.09 kW
9.07 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
6.43
3.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
67 °C
67 °C
Poff
6 W
6 W
PTO
6 W
6 W
PSB
6 W
6 W
PCK
6 W
6 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
kW
kW
Annual energy consumption Qhe
1582 kWh
2278 kWh
Colder Climate
EN 14825
Low temperature
Medium temperature
ηs
309 %
215 %
Prated
9.10 kW
9.10 kW
SCOP
7.93
5.57
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
5.62 kW
5.59 kW
COP Tj = -7°C
7.81
5.13
Cdh Tj = -7 °C
0.992
0.994
Pdh Tj = +2°C
3.44 kW
3.48 kW
COP Tj = +2°C
8.20
5.95
Cdh Tj = +2 °C
0.986
0.990
Pdh Tj = +7°C
2.98 kW
2.99 kW
COP Tj = +7°C
8.43
6.66
Cdh Tj = +7 °C
0.983
0.987
Pdh Tj = 12°C
3.00 kW
2.98 kW
COP Tj = 12°C
8.13
7.34
Cdh Tj = +12 °C
0.984
0.985
Pdh Tj = Tbiv
9.09 kW
9.07 kW
COP Tj = Tbiv
6.43
3.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.09 kW
9.07 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
6.43
3.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
67 °C
67 °C
Poff
6 W
6 W
PTO
6 W
6 W
PSB
6 W
6 W
PCK
6 W
6 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
kW
kW
Annual energy consumption Qhe
2827 kWh
4026 kWh
Average Climate
EN 14825
Low temperature
Medium temperature
ηs
299 %
207 %
Prated
9.10 kW
9.10 kW
SCOP
7.68
5.37
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
8.11 kW
8.08 kW
COP Tj = -7°C
6.81
4.12
Cdh Tj = -7 °C
0.995
0.997
Pdh Tj = +2°C
5.05 kW
4.99 kW
COP Tj = +2°C
7.65
5.35
Cdh Tj = +2 °C
0.991
0.993
Pdh Tj = +7°C
3.28 kW
3.24 kW
COP Tj = +7°C
8.19
6.01
Cdh Tj = +7 °C
0.985
0.989
Pdh Tj = 12°C
2.98 kW
3.01 kW
COP Tj = 12°C
8.43
7.00
Cdh Tj = +12 °C
0.983
0.986
Pdh Tj = Tbiv
9.09 kW
9.07 kW
COP Tj = Tbiv
6.43
3.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.09 kW
9.07 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
6.43
3.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
67 °C
67 °C
Poff
6 W
6 W
PTO
6 W
6 W
PSB
6 W
6 W
PCK
6 W
6 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
kW
kW
Annual energy consumption Qhe
2449 kWh
3498 kWh