1,700 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
15.00 kW
15.00 kW
El input
3.33 kW
5.00 kW
COP
4.50
3.00
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
195 %
143 %
Prated
15.00 kW
15.00 kW
SCOP
4.95
3.65
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
13.46 kW
13.37 kW
COP Tj = -7°C
3.21
2.55
Cdh Tj = -7 °C
0.997
0.998
Pdh Tj = +2°C
8.23 kW
8.39 kW
COP Tj = +2°C
4.76
3.39
Cdh Tj = +2 °C
0.993
0.995
Pdh Tj = +7°C
7.22 kW
7.22 kW
COP Tj = +7°C
6.51
5.02
Cdh Tj = +7 °C
0.989
0.992
Pdh Tj = 12°C
8.79 kW
7.92 kW
COP Tj = 12°C
8.85
6.32
Cdh Tj = +12 °C
0.988
0.990
Pdh Tj = Tbiv
13.46 kW
13.37 kW
COP Tj = Tbiv
3.21
2.55
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.58 kW
9.41 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.77
1.51
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.998
WTOL
75 °C
75 °C
Poff
10 W
10 W
PTO
12 W
12 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.40 kW
5.60 kW
Annual energy consumption Qhe
6258 kWh
8479 kWh