1,200 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
10.28 kW
11.46 kW
El input
2.10 kW
3.81 kW
COP
4.91
3.01
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
59 dB(A)
60 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
189 %
145 %
Prated
12.48 kW
11.75 kW
SCOP
4.81
3.71
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.04 kW
10.39 kW
COP Tj = -7°C
3.15
2.45
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
6.77 kW
6.41 kW
COP Tj = +2°C
4.84
3.71
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
5.93 kW
5.58 kW
COP Tj = +7°C
6.30
4.80
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
6.74 kW
6.48 kW
COP Tj = 12°C
7.97
6.39
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
11.04 kW
10.39 kW
COP Tj = Tbiv
3.15
2.45
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.78 kW
10.07 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.88
2.21
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
24 W
24 W
PTO
85 W
85 W
PSB
24 W
24 W
PCK
41 W
41 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.70 kW
1.67 kW
Annual energy consumption Qhe
5366 kWh
6547 kWh