1,200 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
10.73 kW
9.63 kW
El input
2.35 kW
3.18 kW
COP
4.57
3.03
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
60 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
185 %
143 %
Prated
10.58 kW
9.62 kW
SCOP
4.71
3.64
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
9.36 kW
8.51 kW
COP Tj = -7°C
2.67
2.26
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
5.83 kW
5.43 kW
COP Tj = +2°C
4.86
3.68
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
5.96 kW
5.53 kW
COP Tj = +7°C
6.62
4.93
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
6.76 kW
6.39 kW
COP Tj = 12°C
8.44
6.44
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
9.36 kW
8.51 kW
COP Tj = Tbiv
2.67
2.26
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.20 kW
9.22 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.42
2.05
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
25 W
25 W
PTO
36 W
36 W
PSB
25 W
25 W
PCK
38 W
38 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.38 kW
0.39 kW
Annual energy consumption Qhe
4643 kWh
5458 kWh