1,500 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.20 kW
4.40 kW
El input
0.82 kW
1.49 kW
COP
5.10
2.95
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
1.36 kW
0.82 kW
Cooling capacity
4.70
4.50
EER
3.45
5.50
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
4.70 kW
4.50 kW
SEER
4.96
7.73
Pdc Tj = 35°C
4.66 kW
4.51 kW
EER Tj = 35°C
3.52
5.54
Cdc Tj = 35 °C
0.900
0.900
Pdc Tj = 30°C
3.66 kW
3.44 kW
EER Tj = 30°C
4.76
7.23
Cdc Tj = 30 °C
0.900
0.900
Pdc Tj = 25°C
2.21 kW
2.19 kW
EER Tj = 25°C
5.72
8.94
Cdc Tj = 25 °C
0.900
0.900
Pdc Tj = 20°C
0.94 kW
1.13 kW
EER Tj = 20°C
5.72
10.48
Cdc Tj = 20 °C
0.900
0.900
Poff
14 W
14 W
PTO
10 W
10 W
PSB
14 W
14 W
PCK
0 W
0 W
Annual energy consumption Qce
569 kWh
349 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
55 dB(A)
56 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
191 %
129 %
Prated
5.50 kW
4.40 kW
SCOP
4.81
3.26
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.88 kW
3.89 kW
COP Tj = -7°C
3.19
2.17
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
3.05 kW
2.38 kW
COP Tj = +2°C
4.78
3.30
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
1.93 kW
2.94 kW
COP Tj = +7°C
6.13
4.41
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
1.48 kW
1.32 kW
COP Tj = 12°C
8.05
5.66
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
4.88 kW
3.89 kW
COP Tj = Tbiv
3.19
2.17
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.41 kW
3.42 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.86
1.91
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
60 °C
60 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.09 kW
0.98 kW
Annual energy consumption Qhe
2351 kWh
2744 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.35 kW
6.00 kW
El input
1.28 kW
2.03 kW
COP
4.95
2.95
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
2.17 kW
1.35 kW
Cooling capacity
6.50
6.50
EER
3.00
4.80
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
6.30 kW
6.50 kW
SEER
5.31
8.16
Pdc Tj = 35°C
6.35 kW
6.55 kW
EER Tj = 35°C
2.93
4.69
Cdc Tj = 35 °C
0.900
0.900
Pdc Tj = 30°C
4.76 kW
4.84 kW
EER Tj = 30°C
4.53
7.16
Cdc Tj = 30 °C
0.900
0.900
Pdc Tj = 25°C
3.02 kW
3.26 kW
EER Tj = 25°C
6.32
9.64
Cdc Tj = 25 °C
0.900
0.900
Pdc Tj = 20°C
1.39 kW
1.41 kW
EER Tj = 20°C
7.20
11.48
Cdc Tj = 20 °C
0.900
0.900
Poff
14 W
14 W
PTO
10 W
10 W
PSB
14 W
14 W
PCK
0 W
0 W
Annual energy consumption Qce
713 kWh
478 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
57 dB(A)
58 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
195 %
138 %
Prated
6.80 kW
5.70 kW
SCOP
4.91
3.48
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.03 kW
5.04 kW
COP Tj = -7°C
3.09
2.17
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
3.88 kW
3.12 kW
COP Tj = +2°C
4.85
3.51
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
2.39 kW
2.08 kW
COP Tj = +7°C
6.63
4.54
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
1.39 kW
1.28 kW
COP Tj = 12°C
7.93
5.59
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
6.03 kW
5.04 kW
COP Tj = Tbiv
3.09
2.17
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.36 kW
4.52 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.86
1.91
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
60 °C
60 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.44 kW
1.18 kW
Annual energy consumption Qhe
2845 kWh
3345 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.20 kW
4.40 kW
El input
0.82 kW
1.49 kW
COP
5.10
2.95
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
1.36 kW
0.82 kW
Cooling capacity
4.70
4.50
EER
3.45
5.50
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
4.70 kW
4.50 kW
SEER
4.96
7.73
Pdc Tj = 35°C
4.66 kW
4.51 kW
EER Tj = 35°C
3.52
5.54
Cdc Tj = 35 °C
0.900
0.900
Pdc Tj = 30°C
3.66 kW
3.44 kW
EER Tj = 30°C
4.76
7.23
Cdc Tj = 30 °C
0.900
0.900
Pdc Tj = 25°C
2.21 kW
2.19 kW
EER Tj = 25°C
5.72
8.94
Cdc Tj = 25 °C
0.900
0.900
Pdc Tj = 20°C
0.94 kW
1.13 kW
EER Tj = 20°C
5.72
10.48
Cdc Tj = 20 °C
0.900
0.900
Poff
14 W
14 W
PTO
10 W
10 W
PSB
14 W
14 W
PCK
0 W
0 W
Annual energy consumption Qce
569 kWh
349 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
55 dB(A)
56 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
191 %
129 %
Prated
5.50 kW
4.40 kW
SCOP
4.81
3.26
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.88 kW
3.89 kW
COP Tj = -7°C
3.19
2.17
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
3.05 kW
2.38 kW
COP Tj = +2°C
4.78
3.30
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
1.93 kW
2.94 kW
COP Tj = +7°C
6.13
4.41
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
1.48 kW
1.32 kW
COP Tj = 12°C
8.05
5.66
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
4.88 kW
3.89 kW
COP Tj = Tbiv
3.19
2.17
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.41 kW
3.42 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.86
1.91
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
60 °C
60 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.09 kW
0.98 kW
Annual energy consumption Qhe
2351 kWh
2744 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
123 %
COP
2.91
Heating up time
4:34 h:min
Standby power input
40.0 W
Reference hot water temperature
50.0 °C
Mixed water at 40°C
215 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.35 kW
6.00 kW
El input
1.28 kW
2.03 kW
COP
4.95
2.95
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
2.17 kW
1.35 kW
Cooling capacity
6.50
6.50
EER
3.00
4.80
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
6.30 kW
6.50 kW
SEER
5.31
8.16
Pdc Tj = 35°C
6.35 kW
6.55 kW
EER Tj = 35°C
2.93
4.69
Cdc Tj = 35 °C
0.900
0.900
Pdc Tj = 30°C
4.76 kW
4.84 kW
EER Tj = 30°C
4.53
7.16
Cdc Tj = 30 °C
0.900
0.900
Pdc Tj = 25°C
3.02 kW
3.26 kW
EER Tj = 25°C
6.32
9.64
Cdc Tj = 25 °C
0.900
0.900
Pdc Tj = 20°C
1.39 kW
1.41 kW
EER Tj = 20°C
7.20
11.48
Cdc Tj = 20 °C
0.900
0.900
Poff
14 W
14 W
PTO
10 W
10 W
PSB
14 W
14 W
PCK
0 W
0 W
Annual energy consumption Qce
713 kWh
478 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
57 dB(A)
58 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
195 %
138 %
Prated
6.80 kW
5.70 kW
SCOP
4.91
3.48
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.03 kW
5.04 kW
COP Tj = -7°C
3.09
2.17
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
3.88 kW
3.12 kW
COP Tj = +2°C
4.85
3.51
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
2.39 kW
2.08 kW
COP Tj = +7°C
6.63
4.54
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
1.39 kW
1.28 kW
COP Tj = 12°C
7.93
5.59
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
6.03 kW
5.04 kW
COP Tj = Tbiv
3.09
2.17
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.36 kW
4.52 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.86
1.91
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
60 °C
60 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.44 kW
1.18 kW
Annual energy consumption Qhe
2845 kWh
3345 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
126 %
COP
2.97
Heating up time
4:16 h:min
Standby power input
42.0 W
Reference hot water temperature
50.0 °C
Mixed water at 40°C
215 l