0,800 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
9.94 kW
10.10 kW
El input
2.16 kW
3.24 kW
COP
4.60
3.11
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
189 %
142 %
Prated
8.01 kW
7.90 kW
SCOP
4.80
3.63
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
7.09 kW
7.02 kW
COP Tj = -7°C
3.19
2.39
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
4.33 kW
4.29 kW
COP Tj = +2°C
4.47
3.41
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
2.88 kW
3.18 kW
COP Tj = +7°C
6.60
4.90
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.49 kW
3.24 kW
COP Tj = 12°C
10.07
7.63
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
7.09 kW
7.02 kW
COP Tj = Tbiv
3.19
2.39
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.13 kW
7.28 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.80
2.15
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
56 W
56 W
PSB
13 W
13 W
PCK
93 W
93 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.88 kW
0.62 kW
Annual energy consumption Qhe
3450 kWh
4513 kWh