1,450 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
18.06 kW
17.60 kW
El input
3.77 kW
5.57 kW
COP
4.79
3.16
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
70 dB(A)
70 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
206 %
148 %
Prated
16.20 kW
14.20 kW
SCOP
5.22
3.78
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
14.30 kW
12.57 kW
COP Tj = -7°C
3.30
2.48
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
8.99 kW
7.67 kW
COP Tj = +2°C
4.91
3.57
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
6.06 kW
5.31 kW
COP Tj = +7°C
7.38
5.19
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
6.82 kW
6.33 kW
COP Tj = 12°C
10.27
7.31
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
14.30 kW
12.57 kW
COP Tj = Tbiv
3.30
2.48
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
14.19 kW
12.38 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.92
2.22
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
16 W
16 W
PTO
60 W
60 W
PSB
16 W
16 W
PCK
93 W
93 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.01 kW
1.82 kW
Annual energy consumption Qhe
6398 kWh
7736 kWh