3,500 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
50.10 kW
47.90 kW
El input
11.90 kW
16.50 kW
COP
4.21
2.90
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
11.00 kW
Cooling capacity
34.10
EER
3.10
EN 14825
+7°C/+12°C
Pdesignc
34.10 kW
SEER
4.81
Pdc Tj = 35°C
34.10 kW
EER Tj = 35°C
3.10
Cdc Tj = 35 °C
1.000
Pdc Tj = 30°C
23.80 kW
EER Tj = 30°C
4.10
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
16.20 kW
EER Tj = 25°C
5.24
Cdc Tj = 25 °C
1.000
Pdc Tj = 20°C
16.60 kW
EER Tj = 20°C
6.12
Cdc Tj = 20 °C
1.000
Poff
22 W
PTO
0 W
PSB
28 W
PCK
0 W
Annual energy consumption Qce
4252 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
75 dB(A)
75 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
165 %
132 %
Prated
43.00 kW
44.00 kW
SCOP
4.20
3.36
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
38.00 kW
39.20 kW
COP Tj = -7°C
2.53
1.93
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
25.20 kW
23.90 kW
COP Tj = +2°C
3.90
3.19
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
20.10 kW
19.40 kW
COP Tj = +7°C
6.27
4.87
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
23.10 kW
22.40 kW
COP Tj = 12°C
7.32
6.16
Cdh Tj = +12 °C
1.000
1.000
Pdh Tj = Tbiv
38.00 kW
39.20 kW
COP Tj = Tbiv
2.53
1.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
34.60 kW
34.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.19
1.65
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
78 °C
78 °C
Poff
22 W
22 W
PTO
22 W
22 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
8.40 kW
9.30 kW
Annual energy consumption Qhe
21106 kWh
27218 kWh