Certificate holders

Subtype

Heat pump-R290 KS-90*

Certificate Holder
GZ AXEN Heat Pump Technology Co., Ltd.
No.22, Lianyun Erheng Road, Shiqi Village, Shiqi Town, Panyu District
511450 Guangzhou
China
Registration number
011-1W0799
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
Heat pump-R290 KS-90*
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R290
Mass of Refrigerant

1,000 kg

Certification Date
13.06.2024
Testing basis
European KEYMARK Scheme for Heat Pumps Rev. 14 (as of 2024-04)
Generate PDF Export model CSV
  • Number of models 1

Models

KS-90W/EN7BP
Configure model
Model name
KS-90W/EN7BP
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

9.10 kW

9.20 kW

El input

1.86 kW

2.97 kW

COP

4.90

3.10

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

55 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

186 %

151 %

Prated

9.10 kW

8.50 kW

SCOP

4.72

3.84

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

8.12 kW

7.74 kW

COP Tj = -7°C

2.75

2.33

Cdh Tj = -7 °C

0.990

0.990

Pdh Tj = +2°C

5.01 kW

5.20 kW

COP Tj = +2°C

4.61

3.84

Cdh Tj = +2 °C

0.990

0.990

Pdh Tj = +7°C

3.25 kW

3.20 kW

COP Tj = +7°C

6.44

4.87

Cdh Tj = +7 °C

0.990

0.990

Pdh Tj = 12°C

2.71 kW

2.54 kW

COP Tj = 12°C

8.87

6.59

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

8.12 kW

7.74 kW

COP Tj = Tbiv

2.75

2.33

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.46 kW

7.47 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.89

2.03

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

0.990

WTOL

75 °C

75 °C

Poff

7 W

7 W

PTO

27 W

27 W

PSB

7 W

7 W

PCK

28 W

28 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.71 kW

1.03 kW

Annual energy consumption Qhe

4020 kWh

4576 kWh