1,200 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.40 kW
5.70 kW
El input
1.28 kW
1.97 kW
COP
5.00
2.90
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
2.10 kW
1.36 kW
Cooling capacity
6.50
7.00
EER
3.09
5.14
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
6.50 kW
7.00 kW
SEER
4.01
6.49
Pdc Tj = 35°C
6.50 kW
7.00 kW
EER Tj = 35°C
3.09
5.14
Pdc Tj = 30°C
4.90 kW
5.39 kW
EER Tj = 30°C
3.99
6.65
Pdc Tj = 25°C
3.10 kW
3.32 kW
EER Tj = 25°C
4.55
4.93
Pdc Tj = 20°C
1.37 kW
1.78 kW
EER Tj = 20°C
3.96
12.82
Poff
12 W
12 W
PTO
12 W
12 W
PSB
12 W
12 W
PCK
0 W
0 W
Annual energy consumption Qce
973 kWh
647 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
33 dB(A)
33 dB(A)
Sound power level outdoor
58 dB(A)
58 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
178 %
132 %
Prated
6.50 kW
6.00 kW
SCOP
4.52
3.38
Tbiv
-10 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
5.90 kW
5.50 kW
COP Tj = -7°C
3.16
2.22
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
3.50 kW
3.40 kW
COP Tj = +2°C
4.48
3.37
Cdh Tj = +2 °C
0.980
0.980
Pdh Tj = +7°C
2.25 kW
2.10 kW
COP Tj = +7°C
5.61
4.07
Cdh Tj = +7 °C
0.960
0.970
Pdh Tj = 12°C
2.50 kW
2.50 kW
COP Tj = 12°C
6.92
6.58
Cdh Tj = +12 °C
0.960
0.970
Pdh Tj = Tbiv
6.60 kW
5.50 kW
COP Tj = Tbiv
2.68
2.22
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.60 kW
5.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.68
1.82
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
12 W
12 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.70 kW
Annual energy consumption Qhe
2974 kWh
3667 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
7.60 kW
8.00 kW
El input
1.59 kW
2.91 kW
COP
4.77
2.75
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
2.15 kW
1.45 kW
Cooling capacity
6.50
7.10
EER
3.02
4.88
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
6.50 kW
7.10 kW
SEER
4.43
5.89
Pdc Tj = 35°C
6.50 kW
7.10 kW
EER Tj = 35°C
3.02
4.88
Pdc Tj = 30°C
4.97 kW
5.65 kW
EER Tj = 30°C
4.12
6.81
Pdc Tj = 25°C
3.35 kW
3.18 kW
EER Tj = 25°C
4.74
5.26
Pdc Tj = 20°C
1.55 kW
1.67 kW
EER Tj = 20°C
5.50
7.40
Poff
12 W
12 W
PTO
12 W
12 W
PSB
12 W
12 W
PCK
0 W
0 W
Annual energy consumption Qce
881 kWh
723 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
33 dB(A)
33 dB(A)
Sound power level outdoor
59 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
177 %
131 %
Prated
7.00 kW
7.00 kW
SCOP
4.50
3.34
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.19 kW
6.19 kW
COP Tj = -7°C
2.97
2.09
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
4.12 kW
3.79 kW
COP Tj = +2°C
4.46
3.24
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
2.78 kW
2.49 kW
COP Tj = +7°C
5.70
4.57
Cdh Tj = +7 °C
0.970
0.970
Pdh Tj = 12°C
2.67 kW
2.55 kW
COP Tj = 12°C
7.80
6.10
Cdh Tj = +12 °C
0.960
0.960
Pdh Tj = Tbiv
6.19 kW
6.19 kW
COP Tj = Tbiv
2.97
2.09
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.64 kW
4.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.58
1.66
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
12 W
12 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.36 kW
2.10 kW
Annual energy consumption Qhe
3213 kWh
4334 kWh