Certificate holders

Subtype

Ecodan Power Inverter 10 AA

Certificate Holder
Mitsubishi Electric Air Conditioning Systems Europe LTD
Nettlehill Road, Houston Industrial Estate
EH54 5EQ Livingston
United Kingdom
Registration number
037-0050-20 / rev. 2
Certification Body
SZU - Strojirensky zkusebni ustav (Engineering Test Institute, Public Enterprise)
Subtype title
Ecodan Power Inverter 10 AA
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R410A
Mass of Refrigerant

4,200 kg

Certification Date
09.04.2020
Testing basis
HP Keymark scheme rules rev. no. 7
Generate PDF Export model CSV Download certificate
  • Number of models 14

Models

PUHZ-SW100VAA(-BS) + EHST20C-M*D
Configure model
Model name
PUHZ-SW100VAA(-BS) + EHST20C-M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.2 kW

11.2 kW

El input

2.52 kW

4.31 kW

COP

4.45

2.6

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

167 %

130 %

Prated

10.6 kW

10 kW

SCOP

4.25

3.33

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

9.4 kW

8.9 kW

COP Tj = -7°C

2.75

1.95

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

5.7 kW

5.4 kW

COP Tj = +2°C

4.16

3.2

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

4.5 kW

4.7 kW

COP Tj = +7°C

5.55

4.79

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

4.3 kW

5.3 kW

COP Tj = 12°C

7.47

6.12

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

9.4 kW

8.9 kW

COP Tj = Tbiv

2.75

1.95

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.96 kW

8.58 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.44

1.84

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.64 kW

1.42 kW

Annual energy consumption Qhe

5156 kWh

6204 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

145 %

COP

3.41

Heating up time

01:58 h:min

Standby power input

35 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

278 l

PUHZ-SW100YAA(-BS) + EHST20C-M*D
Configure model
Model name
PUHZ-SW100YAA(-BS) + EHST20C-M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.2 kW

11.2 kW

El input

2.52 kW

4.31 kW

COP

4.45

2.6

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

165 %

129 %

Prated

10.6 kW

10 kW

SCOP

4.21

3.3

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

9.4 kW

8.9 kW

COP Tj = -7°C

2.75

1.95

Cdh Tj = -7 °C

0.99

1

Pdh Tj = +2°C

5.7 kW

5.4 kW

COP Tj = +2°C

4.14

3.18

Cdh Tj = +2 °C

0.98

0.99

Pdh Tj = +7°C

4.5 kW

4.7 kW

COP Tj = +7°C

5.55

4.79

Cdh Tj = +7 °C

0.97

0.98

Pdh Tj = 12°C

4.3 kW

5.3 kW

COP Tj = 12°C

7.47

6.12

Cdh Tj = +12 °C

0.96

0.98

Pdh Tj = Tbiv

9.4 kW

8.9 kW

COP Tj = Tbiv

2.75

1.95

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.96 kW

8.58 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.44

1.84

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

22 W

22 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.64 kW

1.42 kW

Annual energy consumption Qhe

5204 kWh

6262 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

145 %

COP

3.41

Heating up time

01:58 h:min

Standby power input

35 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

278 l

PUHZ-SW100YAA(-BS) + EHST20C-*M*D
Configure model
Model name
PUHZ-SW100YAA(-BS) + EHST20C-*M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.2 kW

11.2 kW

El input

2.52 kW

4.31 kW

COP

4.45

2.6

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

165 %

129 %

Prated

10.6 kW

10 kW

SCOP

4.21

3.3

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

9.4 kW

8.9 kW

COP Tj = -7°C

2.75

1.95

Cdh Tj = -7 °C

0.99

1

Pdh Tj = +2°C

5.7 kW

5.4 kW

COP Tj = +2°C

4.14

3.18

Cdh Tj = +2 °C

0.98

0.99

Pdh Tj = +7°C

4.5 kW

4.7 kW

COP Tj = +7°C

5.55

4.79

Cdh Tj = +7 °C

0.97

0.98

Pdh Tj = 12°C

4.3 kW

5.3 kW

COP Tj = 12°C

7.47

6.12

Cdh Tj = +12 °C

0.96

0.98

Pdh Tj = Tbiv

9.4 kW

8.9 kW

COP Tj = Tbiv

2.75

1.95

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.96 kW

8.58 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.44

1.84

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

22 W

22 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.64 kW

1.42 kW

Annual energy consumption Qhe

5204 kWh

6262 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

145 %

COP

3.41

Heating up time

01:58 h:min

Standby power input

35 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

278 l

PUHZ-SW100YAA(-BS) + EHSC-M*D
Configure model
Model name
PUHZ-SW100YAA(-BS) + EHSC-M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.2 kW

11.2 kW

El input

2.52 kW

4.31 kW

COP

4.45

2.6

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

165 %

129 %

Prated

10.6 kW

10 kW

SCOP

4.21

3.3

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

9.4 kW

8.9 kW

COP Tj = -7°C

2.75

1.95

Cdh Tj = -7 °C

0.99

1

Pdh Tj = +2°C

5.7 kW

5.4 kW

COP Tj = +2°C

4.14

3.18

Cdh Tj = +2 °C

0.98

0.99

Pdh Tj = +7°C

4.5 kW

4.7 kW

COP Tj = +7°C

5.55

4.79

Cdh Tj = +7 °C

0.97

0.98

Pdh Tj = 12°C

4.3 kW

5.3 kW

COP Tj = 12°C

7.47

6.12

Cdh Tj = +12 °C

0.96

0.98

Pdh Tj = Tbiv

9.4 kW

8.9 kW

COP Tj = Tbiv

2.75

1.95

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.96 kW

8.58 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.44

1.84

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

22 W

22 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.64 kW

1.42 kW

Annual energy consumption Qhe

5204 kWh

6262 kWh

PUHZ-SW100YAA(-BS) + EHSC-*M*D
Configure model
Model name
PUHZ-SW100YAA(-BS) + EHSC-*M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.2 kW

11.2 kW

El input

2.52 kW

4.31 kW

COP

4.45

2.6

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

165 %

129 %

Prated

10.6 kW

10 kW

SCOP

4.21

3.3

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

9.4 kW

8.9 kW

COP Tj = -7°C

2.75

1.95

Cdh Tj = -7 °C

0.99

1

Pdh Tj = +2°C

5.7 kW

5.4 kW

COP Tj = +2°C

4.14

3.18

Cdh Tj = +2 °C

0.98

0.99

Pdh Tj = +7°C

4.5 kW

4.7 kW

COP Tj = +7°C

5.55

4.79

Cdh Tj = +7 °C

0.97

0.98

Pdh Tj = 12°C

4.3 kW

5.3 kW

COP Tj = 12°C

7.47

6.12

Cdh Tj = +12 °C

0.96

0.98

Pdh Tj = Tbiv

9.4 kW

8.9 kW

COP Tj = Tbiv

2.75

1.95

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.96 kW

8.58 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.44

1.84

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

22 W

22 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.64 kW

1.42 kW

Annual energy consumption Qhe

5204 kWh

6262 kWh

PUHZ-SW100YAA(-BS) + ERST20C-*M*D
Configure model
Model name
PUHZ-SW100YAA(-BS) + ERST20C-*M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.2 kW

11.2 kW

El input

2.52 kW

4.31 kW

COP

4.45

2.6

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

169 %

132 %

Prated

10.6 kW

10 kW

SCOP

4.31

3.36

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

9.4 kW

8.9 kW

COP Tj = -7°C

2.75

1.95

Cdh Tj = -7 °C

0.99

1

Pdh Tj = +2°C

5.7 kW

5.4 kW

COP Tj = +2°C

4.2

3.22

Cdh Tj = +2 °C

0.98

0.99

Pdh Tj = +7°C

4.5 kW

4.7 kW

COP Tj = +7°C

5.55

4.79

Cdh Tj = +7 °C

0.97

0.98

Pdh Tj = 12°C

4.3 kW

5.3 kW

COP Tj = 12°C

7.47

6.12

Cdh Tj = +12 °C

0.96

0.98

Pdh Tj = Tbiv

9.4 kW

8.9 kW

COP Tj = Tbiv

2.75

1.95

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.96 kW

8.58 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.44

1.84

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

22 W

22 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.64 kW

1.42 kW

Annual energy consumption Qhe

5086 kWh

6141 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

145 %

COP

3.41

Heating up time

01:58 h:min

Standby power input

35 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

278 l

PUHZ-SW100YAA(-BS) + ERSC-M*D
Configure model
Model name
PUHZ-SW100YAA(-BS) + ERSC-M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.2 kW

11.2 kW

El input

2.52 kW

4.31 kW

COP

4.45

2.6

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

169 %

132 %

Prated

10.6 kW

10 kW

SCOP

4.31

3.36

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

9.4 kW

8.9 kW

COP Tj = -7°C

2.75

1.95

Cdh Tj = -7 °C

0.99

1

Pdh Tj = +2°C

5.7 kW

5.4 kW

COP Tj = +2°C

4.2

3.22

Cdh Tj = +2 °C

0.98

0.99

Pdh Tj = +7°C

4.5 kW

4.7 kW

COP Tj = +7°C

5.55

4.79

Cdh Tj = +7 °C

0.97

0.98

Pdh Tj = 12°C

4.3 kW

5.3 kW

COP Tj = 12°C

7.47

6.12

Cdh Tj = +12 °C

0.96

0.98

Pdh Tj = Tbiv

9.4 kW

8.9 kW

COP Tj = Tbiv

2.75

1.95

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.96 kW

8.58 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.44

1.84

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

22 W

22 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.64 kW

1.42 kW

Annual energy consumption Qhe

5086 kWh

6141 kWh

PUHZ-SW100YAA(-BS) + ERSC-*M*D
Configure model
Model name
PUHZ-SW100YAA(-BS) + ERSC-*M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.2 kW

11.2 kW

El input

2.52 kW

4.31 kW

COP

4.45

2.6

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

169 %

132 %

Prated

10.6 kW

10 kW

SCOP

4.31

3.36

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

9.4 kW

8.9 kW

COP Tj = -7°C

2.75

1.95

Cdh Tj = -7 °C

0.99

1

Pdh Tj = +2°C

5.7 kW

5.4 kW

COP Tj = +2°C

4.2

3.22

Cdh Tj = +2 °C

0.98

0.99

Pdh Tj = +7°C

4.5 kW

4.7 kW

COP Tj = +7°C

5.55

4.79

Cdh Tj = +7 °C

0.97

0.98

Pdh Tj = 12°C

4.3 kW

5.3 kW

COP Tj = 12°C

7.47

6.12

Cdh Tj = +12 °C

0.96

0.98

Pdh Tj = Tbiv

9.4 kW

8.9 kW

COP Tj = Tbiv

2.75

1.95

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.96 kW

8.58 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.44

1.84

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

22 W

22 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.64 kW

1.42 kW

Annual energy consumption Qhe

5086 kWh

6141 kWh

PUHZ-SW100VAA(-BS) + EHST20C-*M*D
Configure model
Model name
PUHZ-SW100VAA(-BS) + EHST20C-*M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.2 kW

11.2 kW

El input

2.52 kW

4.31 kW

COP

4.45

2.6

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

167 %

130 %

Prated

10.6 kW

10 kW

SCOP

4.25

3.33

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

9.4 kW

8.9 kW

COP Tj = -7°C

2.75

1.95

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

5.7 kW

5.4 kW

COP Tj = +2°C

4.16

3.2

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

4.5 kW

4.7 kW

COP Tj = +7°C

5.55

4.79

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

4.3 kW

5.3 kW

COP Tj = 12°C

7.47

6.12

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

9.4 kW

8.9 kW

COP Tj = Tbiv

2.75

1.95

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.96 kW

8.58 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.44

1.84

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.64 kW

1.42 kW

Annual energy consumption Qhe

5156 kWh

6204 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

145 %

COP

3.41

Heating up time

01:58 h:min

Standby power input

35 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

278 l

PUHZ-SW100VAA(-BS) + EHSC-M*D
Configure model
Model name
PUHZ-SW100VAA(-BS) + EHSC-M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.2 kW

11.2 kW

El input

2.52 kW

4.31 kW

COP

4.45

2.6

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

167 %

130 %

Prated

10.6 kW

10 kW

SCOP

4.25

3.33

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

9.4 kW

8.9 kW

COP Tj = -7°C

2.75

1.95

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

5.7 kW

5.4 kW

COP Tj = +2°C

4.16

3.2

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

4.5 kW

4.7 kW

COP Tj = +7°C

5.55

4.79

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

4.3 kW

5.3 kW

COP Tj = 12°C

7.47

6.12

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

9.4 kW

8.9 kW

COP Tj = Tbiv

2.75

1.95

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.96 kW

8.58 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.44

1.84

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.64 kW

1.42 kW

Annual energy consumption Qhe

5156 kWh

6204 kWh

PUHZ-SW100VAA(-BS) + EHSC-*M*D
Configure model
Model name
PUHZ-SW100VAA(-BS) + EHSC-*M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.2 kW

11.2 kW

El input

2.52 kW

4.31 kW

COP

4.45

2.6

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

167 %

130 %

Prated

10.6 kW

10 kW

SCOP

4.25

3.33

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

9.4 kW

8.9 kW

COP Tj = -7°C

2.75

1.95

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

5.7 kW

5.4 kW

COP Tj = +2°C

4.16

3.2

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

4.5 kW

4.7 kW

COP Tj = +7°C

5.55

4.79

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

4.3 kW

5.3 kW

COP Tj = 12°C

7.47

6.12

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

9.4 kW

8.9 kW

COP Tj = Tbiv

2.75

1.95

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.96 kW

8.58 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.44

1.84

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.64 kW

1.42 kW

Annual energy consumption Qhe

5156 kWh

6204 kWh

PUHZ-SW100VAA(-BS) + ERST20C-*M*D
Configure model
Model name
PUHZ-SW100VAA(-BS) + ERST20C-*M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.2 kW

11.2 kW

El input

2.52 kW

4.31 kW

COP

4.45

2.6

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

170 %

132 %

Prated

10.6 kW

10 kW

SCOP

4.32

3.37

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

9.4 kW

8.9 kW

COP Tj = -7°C

2.75

1.95

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

5.7 kW

5.4 kW

COP Tj = +2°C

4.21

3.22

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

4.5 kW

4.7 kW

COP Tj = +7°C

5.55

4.79

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

4.3 kW

5.3 kW

COP Tj = 12°C

7.47

6.12

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

9.4 kW

8.9 kW

COP Tj = Tbiv

2.75

1.95

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.96 kW

8.58 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.44

1.84

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.64 kW

1.42 kW

Annual energy consumption Qhe

5070 kWh

6130 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

145 %

COP

3.41

Heating up time

01:58 h:min

Standby power input

35 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

278 l

PUHZ-SW100VAA(-BS) + ERSC-M*D
Configure model
Model name
PUHZ-SW100VAA(-BS) + ERSC-M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.2 kW

11.2 kW

El input

2.52 kW

4.31 kW

COP

4.45

2.6

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

170 %

132 %

Prated

10.6 kW

10 kW

SCOP

4.32

3.37

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

9.4 kW

8.9 kW

COP Tj = -7°C

2.75

1.95

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

5.7 kW

5.4 kW

COP Tj = +2°C

4.21

3.22

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

4.5 kW

4.7 kW

COP Tj = +7°C

5.55

4.79

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

4.3 kW

5.3 kW

COP Tj = 12°C

7.47

6.12

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

9.4 kW

8.9 kW

COP Tj = Tbiv

2.75

1.95

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.96 kW

8.58 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.44

1.84

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.64 kW

1.42 kW

Annual energy consumption Qhe

5070 kWh

6130 kWh

PUHZ-SW100VAA(-BS) + ERSC-*M*D
Configure model
Model name
PUHZ-SW100VAA(-BS) + ERSC-*M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.2 kW

11.2 kW

El input

2.52 kW

4.31 kW

COP

4.45

2.6

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

170 %

132 %

Prated

10.6 kW

10 kW

SCOP

4.32

3.37

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

9.4 kW

8.9 kW

COP Tj = -7°C

2.75

1.95

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

5.7 kW

5.4 kW

COP Tj = +2°C

4.21

3.22

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

4.5 kW

4.7 kW

COP Tj = +7°C

5.55

4.79

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

4.3 kW

5.3 kW

COP Tj = 12°C

7.47

6.12

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

9.4 kW

8.9 kW

COP Tj = Tbiv

2.75

1.95

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.96 kW

8.58 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.44

1.84

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.64 kW

1.42 kW

Annual energy consumption Qhe

5070 kWh

6130 kWh