1,700 kg
Brine/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
16.69 kW
15.10 kW
El input
3.77 kW
5.29 kW
COP
4.43
2.85
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
45 dB(A)
46 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
185 %
141 %
Prated
19.67 kW
18.61 kW
SCOP
4.84
3.73
Tbiv
4 °C
4 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
16.69 kW
15.77 kW
COP Tj = +2°C
4.43
2.96
Cdh Tj = +2 °C
0.998
0.998
Pdh Tj = +7°C
17.03 kW
16.10 kW
COP Tj = +7°C
4.76
3.45
Cdh Tj = +7 °C
0.997
0.998
Pdh Tj = 12°C
17.21 kW
16.53 kW
COP Tj = 12°C
5.08
4.20
Cdh Tj = +12 °C
0.997
0.998
Pdh Tj = Tbiv
16.86 kW
15.95 kW
COP Tj = Tbiv
4.61
3.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
16.69 kW
15.77 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.43
2.96
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.998
0.998
WTOL
65 °C
65 °C
Poff
6 W
6 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.98 kW
2.84 kW
Annual energy consumption Qhe
5433 kWh
6658 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
45 dB(A)
46 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
189 %
144 %
Prated
18.86 kW
19.03 kW
SCOP
4.92
3.80
Tbiv
-18 °C
-16 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
17.13 kW
16.18 kW
COP Tj = -7°C
4.84
3.58
Cdh Tj = -7 °C
0.997
0.998
Pdh Tj = +2°C
17.23 kW
16.42 kW
COP Tj = +2°C
5.03
3.99
Cdh Tj = +2 °C
0.997
0.998
Pdh Tj = +7°C
17.19 kW
16.64 kW
COP Tj = +7°C
5.14
4.36
Cdh Tj = +7 °C
0.997
0.998
Pdh Tj = 12°C
17.19 kW
16.82 kW
COP Tj = 12°C
5.17
4.68
Cdh Tj = +12 °C
0.997
0.997
Pdh Tj = Tbiv
16.88 kW
16.02 kW
COP Tj = Tbiv
4.63
3.31
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
16.69 kW
15.77 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.43
2.96
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.998
0.998
WTOL
65 °C
65 °C
Poff
6 W
6 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.17 kW
3.26 kW
Annual energy consumption Qhe
9456 kWh
12345 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
45 dB(A)
46 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
184 %
140 %
Prated
18.14 kW
19.84 kW
SCOP
4.79
3.70
Tbiv
-8 °C
-5 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
16.77 kW
15.92 kW
COP Tj = -7°C
4.54
3.16
Cdh Tj = -7 °C
0.997
0.998
Pdh Tj = +2°C
17.06 kW
16.25 kW
COP Tj = +2°C
4.78
3.71
Cdh Tj = +2 °C
0.997
0.998
Pdh Tj = +7°C
17.24 kW
16.46 kW
COP Tj = +7°C
5.01
4.08
Cdh Tj = +7 °C
0.997
0.998
Pdh Tj = 12°C
17.18 kW
16.72 kW
COP Tj = 12°C
5.19
4.50
Cdh Tj = +12 °C
0.997
0.997
Pdh Tj = Tbiv
16.74 kW
16.03 kW
COP Tj = Tbiv
4.50
3.32
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
16.69 kW
15.77 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.43
2.96
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.998
0.998
WTOL
65 °C
65 °C
Poff
6 W
6 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.45 kW
4.07 kW
Annual energy consumption Qhe
7818 kWh
11065 kWh
Water/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
20.95 kW
20.68 kW
El input
3.95 kW
5.61 kW
COP
5.31
3.68
Warmer Climate
EN 14825
Low temperature
Medium temperature
ηs
213 %
179 %
Prated
22.45 kW
24.49 kW
SCOP
5.53
4.67
Tbiv
3 °C
4 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
20.95 kW
20.68 kW
COP Tj = +2°C
5.31
3.68
Cdh Tj = +2 °C
0.997
0.998
Pdh Tj = +7°C
20.64 kW
21.27 kW
COP Tj = +7°C
5.51
4.35
Cdh Tj = +7 °C
0.996
0.997
Pdh Tj = 12°C
20.18 kW
21.58 kW
COP Tj = 12°C
5.69
5.24
Cdh Tj = +12 °C
0.996
0.997
Pdh Tj = Tbiv
20.84 kW
20.99 kW
COP Tj = Tbiv
5.39
4.01
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
20.95 kW
20.68 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.31
3.68
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.998
WTOL
65 °C
65 °C
Poff
8 W
8 W
PTO
14 W
14 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.50 kW
3.81 kW
Annual energy consumption Qhe
5427 kWh
7010 kWh
Colder Climate
EN 14825
Low temperature
Medium temperature
ηs
215 %
182 %
Prated
22.57 kW
24.24 kW
SCOP
5.58
4.76
Tbiv
-19 °C
-17 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
20.53 kW
21.39 kW
COP Tj = -7°C
5.57
4.51
Cdh Tj = -7 °C
0.996
0.997
Pdh Tj = +2°C
20.28 kW
21.58 kW
COP Tj = +2°C
5.66
5.01
Cdh Tj = +2 °C
0.996
0.997
Pdh Tj = +7°C
20.05 kW
21.49 kW
COP Tj = +7°C
5.72
5.37
Cdh Tj = +7 °C
0.996
0.997
Pdh Tj = 12°C
20.01 kW
21.32 kW
COP Tj = 12°C
5.74
5.63
Cdh Tj = +12 °C
0.996
0.997
Pdh Tj = Tbiv
20.79 kW
21.05 kW
COP Tj = Tbiv
5.43
4.08
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
20.95 kW
20.68 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.31
3.68
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.998
WTOL
65 °C
65 °C
Poff
8 W
8 W
PTO
14 W
14 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.62 kW
3.56 kW
Annual energy consumption Qhe
9978 kWh
12556 kWh
Average Climate
EN 14825
Low temperature
Medium temperature
ηs
213 %
178 %
Prated
21.73 kW
24.86 kW
SCOP
5.51
4.64
Tbiv
-9 °C
-6 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
20.82 kW
20.94 kW
COP Tj = -7°C
5.41
3.96
Cdh Tj = -7 °C
0.997
0.997
Pdh Tj = +2°C
20.59 kW
21.51 kW
COP Tj = +2°C
5.53
4.68
Cdh Tj = +2 °C
0.996
0.997
Pdh Tj = +7°C
20.31 kW
21.60 kW
COP Tj = +7°C
5.65
5.11
Cdh Tj = +7 °C
0.996
0.997
Pdh Tj = 12°C
19.97 kW
21.41 kW
COP Tj = 12°C
5.75
5.49
Cdh Tj = +12 °C
0.996
0.997
Pdh Tj = Tbiv
20.89 kW
21.03 kW
COP Tj = Tbiv
5.35
4.07
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
20.95 kW
20.68 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.31
3.68
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.998
WTOL
65 °C
65 °C
Poff
8 W
8 W
PTO
14 W
14 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.78 kW
4.18 kW
Annual energy consumption Qhe
8141 kWh
11062 kWh