2,500 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
15.20 kW
13.40 kW
El input
3.70 kW
4.65 kW
COP
4.11
2.88
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
167 %
131 %
Prated
14.60 kW
14.50 kW
SCOP
4.26
3.36
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.90 kW
12.80 kW
COP Tj = -7°C
2.66
2.05
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
7.90 kW
7.80 kW
COP Tj = +2°C
3.99
3.28
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
6.30 kW
6.30 kW
COP Tj = +7°C
6.21
4.58
Cdh Tj = +7 °C
0.980
0.980
Pdh Tj = 12°C
7.30 kW
7.40 kW
COP Tj = 12°C
7.82
5.75
Cdh Tj = +12 °C
0.980
0.980
Pdh Tj = Tbiv
12.90 kW
12.80 kW
COP Tj = Tbiv
2.66
2.05
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.20 kW
11.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.52
1.85
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
17 W
17 W
PTO
21 W
21 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.40 kW
3.00 kW
Annual energy consumption Qhe
7081 kWh
8924 kWh