0,650 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.07 kW
4.14 kW
El input
0.85 kW
1.40 kW
COP
4.79
2.95
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
54 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
190 %
132 %
Prated
4.45 kW
4.47 kW
SCOP
4.83
3.36
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
3.94 kW
3.95 kW
COP Tj = -7°C
3.10
2.23
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
2.55 kW
2.57 kW
COP Tj = +2°C
4.87
3.34
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
2.01 kW
1.75 kW
COP Tj = +7°C
6.59
4.16
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
2.29 kW
2.19 kW
COP Tj = 12°C
7.21
6.13
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
3.94 kW
3.95 kW
COP Tj = Tbiv
3.10
2.23
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.08 kW
4.11 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.77
1.95
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
10 W
10 W
PTO
11 W
11 W
PSB
10 W
10 W
PCK
42 W
42 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.37 kW
0.36 kW
Annual energy consumption Qhe
1903 kWh
2744 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
7.00 kW
6.95 kW
El input
1.46 kW
2.31 kW
COP
4.78
3.01
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
56 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
188 %
138 %
Prated
7.01 kW
6.64 kW
SCOP
4.78
3.51
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
6.20 kW
5.87 kW
COP Tj = -7°C
2.93
2.29
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
3.78 kW
3.71 kW
COP Tj = +2°C
4.59
3.34
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
2.49 kW
2.42 kW
COP Tj = +7°C
6.75
4.69
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
2.49 kW
2.29 kW
COP Tj = 12°C
8.37
6.72
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
6.20 kW
5.87 kW
COP Tj = Tbiv
2.93
2.29
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.69 kW
5.04 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.72
1.94
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
10 W
10 W
PTO
11 W
11 W
PSB
10 W
10 W
PCK
42 W
42 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.33 kW
1.60 kW
Annual energy consumption Qhe
3033 kWh
3904 kWh