3,500 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
50.00 kW
47.90 kW
El input
11.90 kW
16.50 kW
COP
4.20
2.90
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
11.00 kW
Cooling capacity
34.10
EER
3.10
EN 14825
+7°C/+12°C
Pdesignc
34.10 kW
SEER
4.80
Pdc Tj = 35°C
34.10 kW
EER Tj = 35°C
3.10
Cdc Tj = 35 °C
1.000
Pdc Tj = 30°C
24.00 kW
EER Tj = 30°C
4.12
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
16.10 kW
EER Tj = 25°C
5.24
Cdc Tj = 25 °C
1.000
Pdc Tj = 20°C
16.60 kW
EER Tj = 20°C
6.05
Cdc Tj = 20 °C
1.000
Poff
22 W
PTO
0 W
PSB
28 W
PCK
0 W
Annual energy consumption Qce
4259 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
75 dB(A)
75 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
165 %
131 %
Prated
43.00 kW
44.00 kW
SCOP
4.20
3.34
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
38.20 kW
39.10 kW
COP Tj = -7°C
2.53
1.94
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
23.50 kW
23.80 kW
COP Tj = +2°C
3.88
3.15
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
20.30 kW
19.40 kW
COP Tj = +7°C
6.30
4.84
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
23.20 kW
22.40 kW
COP Tj = 12°C
7.31
6.20
Cdh Tj = +12 °C
1.000
1.000
Pdh Tj = Tbiv
38.20 kW
39.10 kW
COP Tj = Tbiv
2.53
1.94
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
34.70 kW
34.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.18
1.66
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
78 °C
78 °C
Poff
22 W
22 W
PTO
22 W
22 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
8.30 kW
9.30 kW
Annual energy consumption Qhe
21240 kWh
27332 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
50.10 kW
47.90 kW
El input
11.90 kW
16.50 kW
COP
4.21
2.90
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
11.00 kW
Cooling capacity
34.10
EER
3.10
EN 14825
+7°C/+12°C
Pdesignc
34.10 kW
SEER
4.81
Pdc Tj = 35°C
34.10 kW
EER Tj = 35°C
3.10
Cdc Tj = 35 °C
1.000
Pdc Tj = 30°C
23.80 kW
EER Tj = 30°C
4.10
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
16.20 kW
EER Tj = 25°C
5.24
Cdc Tj = 25 °C
1.000
Pdc Tj = 20°C
16.60 kW
EER Tj = 20°C
6.12
Cdc Tj = 20 °C
1.000
Poff
22 W
PTO
0 W
PSB
28 W
PCK
0 W
Annual energy consumption Qce
4252 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
75 dB(A)
75 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
165 %
132 %
Prated
43.00 kW
44.00 kW
SCOP
4.20
3.36
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
38.00 kW
39.20 kW
COP Tj = -7°C
2.53
1.93
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
25.20 kW
23.90 kW
COP Tj = +2°C
3.90
3.19
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
20.10 kW
19.40 kW
COP Tj = +7°C
6.27
4.87
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
23.10 kW
22.40 kW
COP Tj = 12°C
7.32
6.16
Cdh Tj = +12 °C
1.000
1.000
Pdh Tj = Tbiv
38.00 kW
39.20 kW
COP Tj = Tbiv
2.53
1.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
34.60 kW
34.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.19
1.65
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
78 °C
78 °C
Poff
22 W
22 W
PTO
22 W
22 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
8.40 kW
9.30 kW
Annual energy consumption Qhe
21106 kWh
27218 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
50.10 kW
48.30 kW
El input
12.20 kW
17.10 kW
COP
4.11
2.82
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
11.40 kW
Cooling capacity
33.70
EER
2.96
EN 14825
+7°C/+12°C
Pdesignc
33.70 kW
SEER
4.20
Pdc Tj = 35°C
33.70 kW
EER Tj = 35°C
2.96
Cdc Tj = 35 °C
1.000
Pdc Tj = 30°C
23.70 kW
EER Tj = 30°C
3.76
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
16.00 kW
EER Tj = 25°C
4.46
Cdc Tj = 25 °C
1.000
Pdc Tj = 20°C
16.30 kW
EER Tj = 20°C
5.04
Cdc Tj = 20 °C
1.000
Poff
22 W
PTO
0 W
PSB
28 W
PCK
0 W
Annual energy consumption Qce
4811 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
75 dB(A)
75 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
152 %
125 %
Prated
43.00 kW
45.00 kW
SCOP
3.89
3.20
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
38.30 kW
39.60 kW
COP Tj = -7°C
2.49
1.90
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
23.30 kW
24.00 kW
COP Tj = +2°C
3.63
3.05
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
20.40 kW
19.80 kW
COP Tj = +7°C
5.40
4.49
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
23.30 kW
22.70 kW
COP Tj = 12°C
6.68
5.59
Cdh Tj = +12 °C
1.000
1.000
Pdh Tj = Tbiv
38.30 kW
39.60 kW
COP Tj = Tbiv
2.49
1.90
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
34.80 kW
35.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.15
1.63
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
78 °C
78 °C
Poff
22 W
22 W
PTO
22 W
22 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
8.20 kW
9.90 kW
Annual energy consumption Qhe
23015 kWh
28905 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
50.10 kW
47.90 kW
El input
11.90 kW
16.50 kW
COP
4.21
2.90
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
11.00 kW
Cooling capacity
34.10
EER
3.10
EN 14825
+7°C/+12°C
Pdesignc
34.10 kW
SEER
4.81
Pdc Tj = 35°C
34.10 kW
EER Tj = 35°C
3.10
Cdc Tj = 35 °C
1.000
Pdc Tj = 30°C
23.80 kW
EER Tj = 30°C
4.10
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
16.20 kW
EER Tj = 25°C
5.24
Cdc Tj = 25 °C
1.000
Pdc Tj = 20°C
16.60 kW
EER Tj = 20°C
6.12
Cdc Tj = 20 °C
1.000
Poff
22 W
PTO
0 W
PSB
28 W
PCK
0 W
Annual energy consumption Qce
4252 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
75 dB(A)
75 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
165 %
132 %
Prated
43.00 kW
44.00 kW
SCOP
4.20
3.36
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
38.00 kW
39.20 kW
COP Tj = -7°C
2.53
1.93
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
25.20 kW
23.90 kW
COP Tj = +2°C
3.90
3.19
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
20.10 kW
19.40 kW
COP Tj = +7°C
6.27
4.87
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
23.10 kW
22.40 kW
COP Tj = 12°C
7.32
6.16
Cdh Tj = +12 °C
1.000
1.000
Pdh Tj = Tbiv
38.00 kW
39.20 kW
COP Tj = Tbiv
2.53
1.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
34.60 kW
34.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.19
1.65
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
78 °C
78 °C
Poff
22 W
22 W
PTO
22 W
22 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
8.40 kW
9.30 kW
Annual energy consumption Qhe
21106 kWh
27218 kWh