3,150 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
40.10 kW
38.00 kW
El input
9.80 kW
13.10 kW
COP
4.10
2.90
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
9.20 kW
Cooling capacity
28.90
EER
3.14
EN 14825
+7°C/+12°C
Pdesignc
28.90 kW
SEER
4.86
Pdc Tj = 35°C
28.90 kW
EER Tj = 35°C
3.14
Cdc Tj = 35 °C
1.000
Pdc Tj = 30°C
21.20 kW
EER Tj = 30°C
4.14
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
17.80 kW
EER Tj = 25°C
5.29
Cdc Tj = 25 °C
1.000
Pdc Tj = 20°C
18.70 kW
EER Tj = 20°C
6.29
Cdc Tj = 20 °C
1.000
Poff
22 W
PTO
0 W
PSB
28 W
PCK
0 W
Annual energy consumption Qce
3565 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
74 dB(A)
74 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
165 %
130 %
Prated
36.00 kW
37.00 kW
SCOP
4.19
3.33
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
32.10 kW
32.50 kW
COP Tj = -7°C
2.64
1.84
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
20.10 kW
18.70 kW
COP Tj = +2°C
4.00
3.30
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
12.80 kW
13.10 kW
COP Tj = +7°C
5.61
4.54
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
16.90 kW
15.80 kW
COP Tj = 12°C
6.94
5.75
Cdh Tj = +12 °C
1.000
1.000
Pdh Tj = Tbiv
32.10 kW
32.50 kW
COP Tj = Tbiv
2.64
1.84
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
33.10 kW
31.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.43
1.63
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
78 °C
78 °C
Poff
45 W
45 W
PTO
45 W
45 W
PSB
41 W
41 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.90 kW
5.70 kW
Annual energy consumption Qhe
17869 kWh
22802 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
40.00 kW
38.10 kW
El input
9.76 kW
13.40 kW
COP
4.10
2.84
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
9.27 kW
Cooling capacity
28.80
EER
3.11
EN 14825
+7°C/+12°C
Pdesignc
28.80 kW
SEER
4.88
Pdc Tj = 35°C
28.80 kW
EER Tj = 35°C
3.11
Cdc Tj = 35 °C
1.000
Pdc Tj = 30°C
20.30 kW
EER Tj = 30°C
4.22
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
17.80 kW
EER Tj = 25°C
5.30
Cdc Tj = 25 °C
1.000
Pdc Tj = 20°C
18.70 kW
EER Tj = 20°C
6.29
Cdc Tj = 20 °C
1.000
Poff
22 W
PTO
0 W
PSB
28 W
PCK
0 W
Annual energy consumption Qce
3537 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
74 dB(A)
74 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
165 %
131 %
Prated
36.00 kW
37.00 kW
SCOP
4.21
3.36
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
32.00 kW
32.60 kW
COP Tj = -7°C
2.66
1.86
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
20.00 kW
18.80 kW
COP Tj = +2°C
4.00
3.33
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
12.90 kW
13.20 kW
COP Tj = +7°C
5.67
4.58
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
16.90 kW
15.90 kW
COP Tj = 12°C
6.98
5.80
Cdh Tj = +12 °C
1.000
1.000
Pdh Tj = Tbiv
32.00 kW
32.60 kW
COP Tj = Tbiv
2.66
1.86
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
32.90 kW
31.40 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.45
1.66
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
78 °C
78 °C
Poff
45 W
45 W
PTO
45 W
45 W
PSB
41 W
41 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.10 kW
5.60 kW
Annual energy consumption Qhe
17743 kWh
22660 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
40.40 kW
38.40 kW
El input
10.20 kW
13.80 kW
COP
3.96
2.78
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
9.73 kW
Cooling capacity
28.40
EER
2.92
EN 14825
+7°C/+12°C
Pdesignc
28.40 kW
SEER
4.21
Pdc Tj = 35°C
28.40 kW
EER Tj = 35°C
2.92
Cdc Tj = 35 °C
1.000
Pdc Tj = 30°C
20.90 kW
EER Tj = 30°C
3.69
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
17.40 kW
EER Tj = 25°C
4.48
Cdc Tj = 25 °C
1.000
Pdc Tj = 20°C
18.40 kW
EER Tj = 20°C
5.24
Cdc Tj = 20 °C
1.000
Poff
22 W
PTO
0 W
PSB
28 W
PCK
0 W
Annual energy consumption Qce
4050 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
74 dB(A)
74 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
154 %
124 %
Prated
36.00 kW
37.00 kW
SCOP
3.93
3.17
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
32.30 kW
32.90 kW
COP Tj = -7°C
2.61
1.84
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
20.10 kW
18.90 kW
COP Tj = +2°C
3.76
3.17
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
13.10 kW
13.40 kW
COP Tj = +7°C
5.09
4.13
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
17.10 kW
16.20 kW
COP Tj = 12°C
6.14
5.17
Cdh Tj = +12 °C
1.000
1.000
Pdh Tj = Tbiv
32.30 kW
32.90 kW
COP Tj = Tbiv
2.61
1.84
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
33.30 kW
31.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.42
1.64
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
78 °C
78 °C
Poff
45 W
45 W
PTO
45 W
45 W
PSB
41 W
41 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.70 kW
5.30 kW
Annual energy consumption Qhe
19163 kWh
24238 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
40.00 kW
38.10 kW
El input
9.76 kW
13.40 kW
COP
4.10
2.84
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
9.27 kW
Cooling capacity
28.80
EER
3.11
EN 14825
+7°C/+12°C
Pdesignc
28.80 kW
SEER
4.88
Pdc Tj = 35°C
28.80 kW
EER Tj = 35°C
3.11
Cdc Tj = 35 °C
1.000
Pdc Tj = 30°C
20.30 kW
EER Tj = 30°C
4.22
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
17.80 kW
EER Tj = 25°C
5.30
Cdc Tj = 25 °C
1.000
Pdc Tj = 20°C
18.70 kW
EER Tj = 20°C
6.29
Cdc Tj = 20 °C
1.000
Poff
22 W
PTO
0 W
PSB
28 W
PCK
0 W
Annual energy consumption Qce
3537 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
74 dB(A)
74 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
165 %
131 %
Prated
36.00 kW
37.00 kW
SCOP
4.21
3.36
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
32.00 kW
32.60 kW
COP Tj = -7°C
2.66
1.86
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
20.00 kW
18.80 kW
COP Tj = +2°C
4.00
3.33
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
12.90 kW
13.20 kW
COP Tj = +7°C
5.67
4.58
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
16.90 kW
15.90 kW
COP Tj = 12°C
6.98
5.80
Cdh Tj = +12 °C
1.000
1.000
Pdh Tj = Tbiv
32.00 kW
32.60 kW
COP Tj = Tbiv
2.66
1.86
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
32.90 kW
31.40 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.45
1.66
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
78 °C
78 °C
Poff
45 W
45 W
PTO
45 W
45 W
PSB
41 W
41 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.10 kW
5.60 kW
Annual energy consumption Qhe
17743 kWh
22660 kWh