Certificate holders

Subtype

Acond Grandis-L

Certificate Holder
Acond a.s.
Štěrboholská 1434/102a
102 00 Hostivař, Praha
Czech Republic
Registration number
037-0154-24
Certification Body
SZU - Strojirensky zkusebni ustav (Engineering Test Institute, Public Enterprise)
Subtype title
Acond Grandis-L
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R290
Mass of Refrigerant

2,600 kg

Certification Date
31.01.2024
Testing basis
HP Keymark scheme rules rev. no. 12
Testing laboratory
SZU Brno, CZ
Generate PDF Export model CSV Download certificate
  • Number of models 3

Models

Acond Grandis-L16
Configure model
Model name
Acond Grandis-L16
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.41 kW

10.20 kW

El input

2.22 kW

3.22 kW

COP

5.14

3.17

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

0 dB(A)

0 dB(A)

Sound power level outdoor

0 dB(A)

48 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

217 %

158 %

Prated

15.50 kW

16.00 kW

SCOP

5.49

4.03

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

13.71 kW

14.49 kW

COP Tj = -7°C

3.34

2.52

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

8.35 kW

8.62 kW

COP Tj = +2°C

5.31

3.81

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

6.03 kW

5.54 kW

COP Tj = +7°C

7.35

5.33

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

7.12 kW

7.04 kW

COP Tj = 12°C

9.57

7.96

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

15.50 kW

16.00 kW

COP Tj = Tbiv

2.74

2.10

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

15.50 kW

16.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.74

2.10

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

75 °C

75 °C

Poff

12 W

12 W

PTO

13 W

13 W

PSB

12 W

12 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5835 kWh

8201 kWh

Acond Grandis-L18
Configure model
Model name
Acond Grandis-L18
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

13.15 kW

11.77 kW

El input

2.55 kW

3.67 kW

COP

5.16

3.21

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

0 dB(A)

0 dB(A)

Sound power level outdoor

0 dB(A)

50 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

200 %

158 %

Prated

18.80 kW

18.00 kW

SCOP

5.07

4.02

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

16.70 kW

15.92 kW

COP Tj = -7°C

3.22

2.49

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

10.12 kW

9.69 kW

COP Tj = +2°C

4.59

3.79

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

6.51 kW

6.23 kW

COP Tj = +7°C

7.38

5.35

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

7.13 kW

7.05 kW

COP Tj = 12°C

9.58

7.97

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

18.80 kW

18.00 kW

COP Tj = Tbiv

2.71

2.08

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

18.80 kW

18.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.71

2.08

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

75 °C

75 °C

Poff

12 W

12 W

PTO

13 W

13 W

PSB

12 W

12 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

7650 kWh

9259 kWh

Acond Grandis-L21
Configure model
Model name
Acond Grandis-L21
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16.69 kW

14.98 kW

El input

3.24 kW

4.57 kW

COP

5.15

3.28

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

0 dB(A)

0 dB(A)

Sound power level outdoor

0 dB(A)

53 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

195 %

142 %

Prated

21.00 kW

22.00 kW

SCOP

4.95

3.62

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

18.50 kW

19.42 kW

COP Tj = -7°C

2.74

2.24

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

10.50 kW

11.85 kW

COP Tj = +2°C

4.60

3.22

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

7.38 kW

7.62 kW

COP Tj = +7°C

7.59

5.45

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

7.14 kW

7.05 kW

COP Tj = 12°C

9.60

7.99

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

18.50 kW

19.42 kW

COP Tj = Tbiv

2.74

2.24

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

18.50 kW

19.42 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.74

2.24

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

75 °C

75 °C

Poff

12 W

12 W

PTO

13 W

13 W

PSB

12 W

12 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

2.50 kW

2.58 kW

Annual energy consumption Qhe

8729 kWh

12543 kWh