5,900 kg
Brine/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
35.44 kW
33.49 kW
El input
7.51 kW
10.82 kW
COP
4.72
3.10
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
207 %
165 %
Prated
58.48 kW
56.10 kW
SCOP
5.37
4.33
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
58.48 kW
56.10 kW
COP Tj = +2°C
3.96
2.85
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
37.59 kW
36.06 kW
COP Tj = +7°C
5.00
3.77
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
16.71 kW
16.03 kW
COP Tj = 12°C
6.00
5.23
Cdh Tj = +12 °C
1.000
1.000
Pdh Tj = Tbiv
58.48 kW
56.10 kW
COP Tj = Tbiv
3.96
2.85
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
58.48 kW
56.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.96
2.85
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
65 °C
65 °C
Poff
12 W
12 W
PTO
12 W
12 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
14551 kWh
17310 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
213 %
170 %
Prated
58.48 kW
56.10 kW
SCOP
5.54
4.46
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
35.40 kW
33.95 kW
COP Tj = -7°C
5.25
3.99
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
21.55 kW
20.67 kW
COP Tj = +2°C
5.95
4.95
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
15.95 kW
15.75 kW
COP Tj = +7°C
6.01
5.35
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
15.91 kW
15.76 kW
COP Tj = 12°C
5.78
5.39
Cdh Tj = +12 °C
1.000
1.000
Pdh Tj = Tbiv
58.48 kW
56.10 kW
COP Tj = Tbiv
3.96
2.85
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
58.48 kW
56.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.96
2.85
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
65 °C
65 °C
Poff
12 W
12 W
PTO
12 W
12 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
26039 kWh
30994 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
205 %
163 %
Prated
58.48 kW
56.10 kW
SCOP
5.32
4.27
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
51.73 kW
49.60 kW
COP Tj = -7°C
4.28
3.09
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
31.49 kW
30.21 kW
COP Tj = +2°C
5.33
4.25
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
20.24 kW
19.42 kW
COP Tj = +7°C
5.98
5.05
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
15.94 kW
15.72 kW
COP Tj = 12°C
5.92
5.29
Cdh Tj = +12 °C
1.000
1.000
Pdh Tj = Tbiv
58.48 kW
56.10 kW
COP Tj = Tbiv
3.96
2.85
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
58.48 kW
56.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.96
2.85
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
65 °C
65 °C
Poff
12 W
12 W
PTO
12 W
12 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
22720 kWh
27150 kWh
Water/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
47.43 kW
44.05 kW
El input
7.73 kW
11.14 kW
COP
6.13
3.95
Warmer Climate
EN 14825
Low temperature
Medium temperature
ηs
304 %
215 %
Prated
52.53 kW
54.94 kW
SCOP
7.79
5.57
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
52.53 kW
54.94 kW
COP Tj = +2°C
5.92
3.69
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
33.77 kW
35.32 kW
COP Tj = +7°C
7.49
4.97
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
20.03 kW
19.99 kW
COP Tj = 12°C
8.48
6.59
Cdh Tj = +12 °C
1.000
1.000
Pdh Tj = Tbiv
52.53 kW
54.94 kW
COP Tj = Tbiv
5.92
3.69
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
52.53 kW
54.94 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.92
3.69
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
65 °C
65 °C
Poff
12 W
12 W
PTO
12 W
12 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
9008 kWh
13182 kWh
Colder Climate
EN 14825
Low temperature
Medium temperature
ηs
314 %
223 %
Prated
52.53 kW
54.94 kW
SCOP
8.06
5.77
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
31.79 kW
33.25 kW
COP Tj = -7°C
7.78
5.27
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
19.35 kW
20.24 kW
COP Tj = +2°C
8.56
6.33
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
20.04 kW
20.02 kW
COP Tj = +7°C
8.59
6.79
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
20.02 kW
20.05 kW
COP Tj = 12°C
8.36
7.05
Cdh Tj = +12 °C
1.000
1.000
Pdh Tj = Tbiv
52.53 kW
54.94 kW
COP Tj = Tbiv
5.92
3.69
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
52.53 kW
54.94 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.92
3.69
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
65 °C
65 °C
Poff
12 W
12 W
PTO
12 W
12 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
16072 kWh
23456 kWh
Average Climate
EN 14825
Low temperature
Medium temperature
ηs
303 %
215 %
Prated
52.53 kW
54.94 kW
SCOP
7.77
5.58
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
46.47 kW
48.60 kW
COP Tj = -7°C
6.44
4.08
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
28.29 kW
29.58 kW
COP Tj = +2°C
7.83
5.59
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
20.03 kW
19.02 kW
COP Tj = +7°C
8.56
6.53
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
20.03 kW
20.02 kW
COP Tj = 12°C
8.56
6.83
Cdh Tj = +12 °C
1.000
1.000
Pdh Tj = Tbiv
52.53 kW
54.94 kW
COP Tj = Tbiv
5.92
3.69
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
52.53 kW
54.94 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.92
3.69
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
65 °C
65 °C
Poff
12 W
12 W
PTO
12 W
12 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
13969 kWh
20358 kWh