1,100 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
10.00 kW
10.00 kW
El input
2.08 kW
3.33 kW
COP
4.80
3.00
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
194 %
144 %
Prated
11.00 kW
11.00 kW
SCOP
4.93
3.68
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
9.77 kW
9.85 kW
COP Tj = -7°C
3.23
2.38
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
6.03 kW
5.96 kW
COP Tj = +2°C
4.62
3.44
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.06 kW
4.00 kW
COP Tj = +7°C
6.65
5.00
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.70 kW
4.10 kW
COP Tj = 12°C
9.15
6.76
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
9.77 kW
9.85 kW
COP Tj = Tbiv
3.23
2.38
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.78 kW
11.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.83
2.11
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
14 W
14 W
PTO
14 W
14 W
PSB
14 W
14 W
PCK
43 W
43 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.22 kW
0.00 kW
Annual energy consumption Qhe
4643 kWh
6259 kWh