1,400 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.00 kW
12.00 kW
El input
2.53 kW
4.00 kW
COP
4.75
3.00
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
56 dB(A)
56 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
193 %
148 %
Prated
12.20 kW
12.10 kW
SCOP
4.90
3.77
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.07 kW
10.73 kW
COP Tj = -7°C
2.90
2.20
Cdh Tj = -7 °C
0.995
0.996
Pdh Tj = +2°C
6.52 kW
6.43 kW
COP Tj = +2°C
4.52
3.58
Cdh Tj = +2 °C
0.987
0.989
Pdh Tj = +7°C
4.26 kW
4.24 kW
COP Tj = +7°C
7.19
5.34
Cdh Tj = +7 °C
0.968
0.976
Pdh Tj = 12°C
2.78 kW
2.56 kW
COP Tj = 12°C
10.18
6.76
Cdh Tj = +12 °C
0.930
0.950
Pdh Tj = Tbiv
11.07 kW
10.73 kW
COP Tj = Tbiv
2.90
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.55 kW
10.48 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.76
2.05
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.996
WTOL
75 °C
75 °C
Poff
12 W
12 W
PTO
19 W
19 W
PSB
12 W
12 W
PCK
2 W
2 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.60 kW
1.60 kW
Annual energy consumption Qhe
5141 kWh
6639 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
15.00 kW
15.00 kW
El input
3.33 kW
5.26 kW
COP
4.50
2.85
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
186 %
146 %
Prated
14.00 kW
14.00 kW
SCOP
4.73
3.73
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.53 kW
12.47 kW
COP Tj = -7°C
2.74
2.10
Cdh Tj = -7 °C
0.996
0.997
Pdh Tj = +2°C
7.58 kW
7.67 kW
COP Tj = +2°C
4.37
3.55
Cdh Tj = +2 °C
0.989
0.991
Pdh Tj = +7°C
4.83 kW
4.81 kW
COP Tj = +7°C
7.04
5.39
Cdh Tj = +7 °C
0.972
0.979
Pdh Tj = 12°C
2.78 kW
2.56 kW
COP Tj = 12°C
10.18
6.76
Cdh Tj = +12 °C
0.930
0.950
Pdh Tj = Tbiv
12.53 kW
12.47 kW
COP Tj = Tbiv
2.74
2.10
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.55 kW
12.12 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.76
2.00
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.997
WTOL
75 °C
75 °C
Poff
12 W
12 W
PTO
19 W
19 W
PSB
12 W
12 W
PCK
2 W
2 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.40 kW
1.90 kW
Annual energy consumption Qhe
6115 kWh
7763 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.00 kW
12.00 kW
El input
2.53 kW
4.00 kW
COP
4.75
3.00
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
56 dB(A)
56 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
192 %
148 %
Prated
12.20 kW
12.10 kW
SCOP
4.88
3.76
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.22 kW
11.18 kW
COP Tj = -7°C
2.79
2.21
Cdh Tj = -7 °C
0.997
0.997
Pdh Tj = +2°C
6.67 kW
6.45 kW
COP Tj = +2°C
4.57
3.58
Cdh Tj = +2 °C
0.991
0.993
Pdh Tj = +7°C
4.23 kW
4.18 kW
COP Tj = +7°C
7.10
5.17
Cdh Tj = +7 °C
0.978
0.984
Pdh Tj = 12°C
2.77 kW
2.71 kW
COP Tj = 12°C
10.01
7.54
Cdh Tj = +12 °C
0.953
0.964
Pdh Tj = Tbiv
11.22 kW
11.18 kW
COP Tj = Tbiv
2.79
2.21
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.57 kW
10.16 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.61
2.00
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.997
WTOL
75 °C
75 °C
Poff
12 W
12 W
PTO
13 W
13 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.60 kW
1.90 kW
Annual energy consumption Qhe
5168 kWh
6642 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
15.00 kW
15.00 kW
El input
3.33 kW
5.26 kW
COP
4.50
2.85
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
187 %
145 %
Prated
14.00 kW
14.00 kW
SCOP
4.74
3.69
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.39 kW
12.85 kW
COP Tj = -7°C
2.68
2.10
Cdh Tj = -7 °C
0.997
0.998
Pdh Tj = +2°C
7.55 kW
7.54 kW
COP Tj = +2°C
4.45
3.49
Cdh Tj = +2 °C
0.992
0.994
Pdh Tj = +7°C
4.83 kW
4.78 kW
COP Tj = +7°C
6.93
5.25
Cdh Tj = +7 °C
0.981
0.986
Pdh Tj = 12°C
2.77 kW
2.71 kW
COP Tj = 12°C
10.01
7.54
Cdh Tj = +12 °C
0.953
0.964
Pdh Tj = Tbiv
12.39 kW
12.85 kW
COP Tj = Tbiv
2.68
2.10
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.54 kW
11.77 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.56
1.89
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.998
WTOL
75 °C
75 °C
Poff
12 W
12 W
PTO
13 W
13 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.50 kW
2.20 kW
Annual energy consumption Qhe
6097 kWh
7837 kWh