Certificate holders

Subtype

Beretta AGILE T 4M/6M WH

Certificate Holder
Riello S.p.A.
Via Ing. Pilade Riello 7
37045 Legnago (VR)
Italy
Registration number
011-1W0723
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
Beretta AGILE T 4M/6M WH
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

0,900 kg

Certification Date
24.10.2023
Testing basis
HP KEYMARK certification scheme rules V12
Generate PDF Export model CSV
  • Number of models 4

Models

HP ODU AGILE 4M / HP IDU AGILE M3WS
Configure model
Model name
HP ODU AGILE 4M / HP IDU AGILE M3WS
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

4 kW

6.51 kW

El input

0.77 kW

2.15 kW

COP

5.2

3.03

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

Sound power level outdoor

65 dB(A)

65 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

178 %

135 %

Prated

4.97 kW

4.54 kW

SCOP

4.53

3.45

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

4.4 kW

4 kW

COP Tj = -7°C

3.11

2.18

Cdh Tj = -7 °C

0.97

0.98

Pdh Tj = +2°C

2.99 kW

2.5 kW

COP Tj = +2°C

4.45

3.48

Cdh Tj = +2 °C

0.94

0.94

Pdh Tj = +7°C

1.8 kW

1.6 kW

COP Tj = +7°C

5.87

4.28

Cdh Tj = +7 °C

0.9

0.9

Pdh Tj = 12°C

1.48 kW

1.5 kW

COP Tj = 12°C

7.38

6.35

Cdh Tj = +12 °C

0.9

0.9

Pdh Tj = Tbiv

4.4 kW

4 kW

COP Tj = Tbiv

3.11

2.18

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4 kW

3.5 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.88

1.83

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.8

0.8

WTOL

55 °C

55 °C

Poff

8 W

8 W

PTO

40 W

40 W

PSB

8 W

8 W

PCK

8 W

8 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.97 kW

1.04 kW

Annual energy consumption Qhe

2268 kWh

2721 kWh

HP ODU AGILE 6M / HP IDU AGILE M3WS
Configure model
Model name
HP ODU AGILE 6M / HP IDU AGILE M3WS
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6 kW

7.53 kW

El input

1.25 kW

2.61 kW

COP

4.8

2.89

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

Sound power level outdoor

65 dB(A)

65 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

180 %

132 %

Prated

5.97 kW

5.7 kW

SCOP

4.58

3.37

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

5.28 kW

5 kW

COP Tj = -7°C

3.02

2.1

Cdh Tj = -7 °C

0.98

0.98

Pdh Tj = +2°C

3.41 kW

3.4 kW

COP Tj = +2°C

4.45

3.22

Cdh Tj = +2 °C

0.95

0.96

Pdh Tj = +7°C

2.14 kW

2 kW

COP Tj = +7°C

6.05

4.58

Cdh Tj = +7 °C

0.9

0.91

Pdh Tj = 12°C

1.48 kW

1.5 kW

COP Tj = 12°C

7.38

6.35

Cdh Tj = +12 °C

0.9

0.9

Pdh Tj = Tbiv

5.28 kW

5 kW

COP Tj = Tbiv

3.02

2.1

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.1 kW

4.5 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.83

1.81

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.8

0.8

WTOL

55 °C

55 °C

Poff

8 W

8 W

PTO

40 W

40 W

PSB

8 W

8 W

PCK

8 W

8 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.87 kW

1.2 kW

Annual energy consumption Qhe

2691 kWh

3497 kWh

HP ODU AGILE 4M / HP IDU AGILE M6WS
Configure model
Model name
HP ODU AGILE 4M / HP IDU AGILE M6WS
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

4 kW

6.51 kW

El input

0.77 kW

2.15 kW

COP

5.2

3.03

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

Sound power level outdoor

65 dB(A)

65 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

178 %

135 %

Prated

4.97 kW

4.54 kW

SCOP

4.53

3.45

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

4.4 kW

4 kW

COP Tj = -7°C

3.11

2.18

Pdh Tj = +2°C

2.99 kW

2.5 kW

COP Tj = +2°C

4.45

3.48

Pdh Tj = +7°C

1.8 kW

1.6 kW

COP Tj = +7°C

5.87

4.28

Pdh Tj = 12°C

1.48 kW

1.5 kW

COP Tj = 12°C

7.38

6.35

Pdh Tj = Tbiv

4.4 kW

4 kW

COP Tj = Tbiv

3.11

2.18

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4 kW

3.5 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.88

1.83

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.8

0.8

WTOL

55 °C

55 °C

Poff

8 W

8 W

PTO

40 W

40 W

PSB

8 W

8 W

PCK

8 W

8 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.97 kW

1.04 kW

Annual energy consumption Qhe

2268 kWh

2721 kWh

HP ODU AGILE 6M / HP IDU AGILE M6WS
Configure model
Model name
HP ODU AGILE 6M / HP IDU AGILE M6WS
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6 kW

7.53 kW

El input

1.25 kW

2.61 kW

COP

4.8

2.89

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

Sound power level outdoor

65 dB(A)

65 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

180 %

132 %

Prated

5.97 kW

5.7 kW

SCOP

4.58

3.37

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

5.28 kW

5 kW

COP Tj = -7°C

3.02

2.1

Pdh Tj = +2°C

3.41 kW

3.4 kW

COP Tj = +2°C

4.45

3.22

Pdh Tj = +7°C

2.14 kW

2 kW

COP Tj = +7°C

6.05

4.58

Pdh Tj = 12°C

1.48 kW

1.5 kW

COP Tj = 12°C

7.38

6.35

Pdh Tj = Tbiv

5.28 kW

5 kW

COP Tj = Tbiv

3.02

2.1

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.1 kW

4.5 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.83

1.81

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.8

0.8

WTOL

55 °C

55 °C

Poff

8 W

8 W

PTO

40 W

40 W

PSB

8 W

8 W

PCK

8 W

8 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.87 kW

1.2 kW

Annual energy consumption Qhe

2691 kWh

3497 kWh