7,400 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
48.67 kW
44.97 kW
El input
10.63 kW
16.35 kW
COP
4.58
2.75
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
61 dB(A)
61 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
134 %
Prated
42.15 kW
40.75 kW
SCOP
4.58
3.41
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
25.62 kW
24.58 kW
COP Tj = -7°C
4.24
2.85
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
19.67 kW
18.82 kW
COP Tj = +2°C
5.16
4.28
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
17.42 kW
16.60 kW
COP Tj = +7°C
7.29
6.43
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
16.53 kW
15.58 kW
COP Tj = 12°C
10.42
9.51
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
34.39 kW
33.24 kW
COP Tj = Tbiv
2.99
1.74
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
29.61 kW
27.54 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.45
1.55
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
55 °C
55 °C
Poff
24 W
24 W
PTO
31 W
31 W
PSB
24 W
24 W
PCK
35 W
35 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
12.50 kW
12.50 kW
Annual energy consumption Qhe
22765 kWh
29423 kWh
Pdh Tj = -15°C (if TOL<-20°C)
34.39
33.24
COP Tj = -15°C (if TOL<-20°C)
2.99
1.74
Cdh Tj = -15 °C
0.900
0.900
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
61 dB(A)
61 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
195 %
149 %
Prated
47.26 kW
44.10 kW
SCOP
4.95
3.79
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
41.81 kW
39.01 kW
COP Tj = -7°C
3.47
2.14
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
25.51 kW
23.73 kW
COP Tj = +2°C
4.38
3.55
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
17.54 kW
16.65 kW
COP Tj = +7°C
7.04
5.59
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
16.53 kW
15.64 kW
COP Tj = 12°C
10.42
8.79
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
41.81 kW
39.01 kW
COP Tj = Tbiv
3.47
2.14
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
39.02 kW
36.79 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.16
1.90
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
55 °C
55 °C
Poff
24 W
24 W
PTO
31 W
31 W
PSB
24 W
24 W
PCK
31 W
31 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.60 kW
7.60 kW
Annual energy consumption Qhe
19725 kWh
24010 kWh