Certificate holders

Subtype

KITA LR 35 R32

Certificate Holder
Templari S.p.A.
Via C. Battisti, n° 169
35031 Abano Terme (PD)
Italy
Registration number
ICIM-PDC-000220
Certification Body
ICIM S.p.A.
Subtype title
KITA LR 35 R32
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

6,500 kg

Certification Date
02.11.2023
Testing basis
n/a
Generate PDF Export model CSV
  • Number of models 1

Models

Unità esterna KITA-LR-35-COLD, 3Ph, vers. MONOBLOCCO R-32
Configure model
Model name
Unità esterna KITA-LR-35-COLD, 3Ph, vers. MONOBLOCCO R-32
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Colder Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

35.42 kW

34.81 kW

El input

7.67 kW

11.16 kW

COP

4.62

3.12

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

61 dB(A)

61 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

160 %

137 %

Prated

34.25 kW

33.77 kW

SCOP

4.08

3.50

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

20.73 kW

20.44 kW

COP Tj = -7°C

3.43

3.15

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

18.51 kW

18.57 kW

COP Tj = +2°C

4.94

4.10

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

16.32 kW

16.39 kW

COP Tj = +7°C

6.69

5.87

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

14.09 kW

15.37 kW

COP Tj = 12°C

8.39

8.56

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

27.94 kW

27.55 kW

COP Tj = Tbiv

2.85

2.18

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

23.90 kW

21.97 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.32

1.80

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

24 W

24 W

PTO

31 W

31 W

PSB

24 W

24 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

11.00 kW

11.00 kW

Annual energy consumption Qhe

20701 kWh

23807 kWh

Pdh Tj = -15°C (if TOL<-20°C)

27.94

27.55

COP Tj = -15°C (if TOL<-20°C)

2.85

2.18

Cdh Tj = -15 °C

0.900

0.900

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

61 dB(A)

61 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

190 %

149 %

Prated

38.25 kW

36.66 kW

SCOP

4.81

3.79

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

33.84 kW

32.43 kW

COP Tj = -7°C

3.22

2.41

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

20.60 kW

19.74 kW

COP Tj = +2°C

4.58

3.57

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

16.28 kW

16.45 kW

COP Tj = +7°C

6.59

5.22

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

14.09 kW

15.44 kW

COP Tj = 12°C

8.39

8.04

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

33.84 kW

32.43 kW

COP Tj = Tbiv

3.22

2.41

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

30.69 kW

29.82 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.91

2.08

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

24 W

24 W

PTO

31 W

31 W

PSB

24 W

24 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

7.00 kW

7.00 kW

Annual energy consumption Qhe

16421 kWh

20029 kWh