Certificate holders

Subtype

KITA LP PLUS 35-40 R290

Certificate Holder
Templari S.p.A.
Via C. Battisti, n° 169
35031 Abano Terme (PD)
Italy
Registration number
ICIM-PDC-000219
Certification Body
ICIM S.p.A.
Subtype title
KITA LP PLUS 35-40 R290
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R290
Mass of Refrigerant

4,500 kg

Certification Date
02.11.2023
Testing basis
n/a
Generate PDF Export model CSV
  • Number of models 2

Models

Unità esterna KITA-LP Plus-35, 3Ph, vers. MONOBLOCCO R-290
Configure model
Model name
Unità esterna KITA-LP Plus-35, 3Ph, vers. MONOBLOCCO R-290
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Colder Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

35.00 kW

33.62 kW

El input

7.11 kW

10.19 kW

COP

4.92

3.30

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

61 dB(A)

61 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

194 %

146 %

Prated

25.52 kW

24.62 kW

SCOP

4.92

3.72

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

15.45 kW

14.90 kW

COP Tj = -7°C

4.13

3.04

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

12.60 kW

12.27 kW

COP Tj = +2°C

6.43

4.89

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

11.57 kW

11.13 kW

COP Tj = +7°C

8.04

6.22

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

11.15 kW

10.89 kW

COP Tj = 12°C

10.58

8.88

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

20.82 kW

20.09 kW

COP Tj = Tbiv

2.79

2.06

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

17.11 kW

16.27 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.24

1.57

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

24 W

24 W

PTO

31 W

31 W

PSB

24 W

24 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

8.00 kW

8.00 kW

Annual energy consumption Qhe

12798 kWh

16325 kWh

Pdh Tj = -15°C (if TOL<-20°C)

20.82

20.09

COP Tj = -15°C (if TOL<-20°C)

2.79

2.06

Cdh Tj = -15 °C

0.900

0.900

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

61 dB(A)

61 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

226 %

164 %

Prated

29.00 kW

27.73 kW

SCOP

5.71

4.17

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

25.65 kW

24.53 kW

COP Tj = -7°C

3.26

2.35

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

15.61 kW

14.93 kW

COP Tj = +2°C

5.86

4.21

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

11.41 kW

10.90 kW

COP Tj = +7°C

7.43

5.53

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

11.15 kW

10.78 kW

COP Tj = 12°C

10.58

8.20

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

25.65 kW

24.53 kW

COP Tj = Tbiv

3.26

2.35

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

23.46 kW

22.36 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.95

2.07

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

24 W

24 W

PTO

31 W

31 W

PSB

24 W

24 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

5.20 kW

5.20 kW

Annual energy consumption Qhe

10497 kWh

13736 kWh

Unità esterna KITA-LP Plus-40, 3Ph, vers. MONOBLOCCO R-290
Configure model
Model name
Unità esterna KITA-LP Plus-40, 3Ph, vers. MONOBLOCCO R-290
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Colder Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

40.00 kW

37.50 kW

El input

8.48 kW

12.02 kW

COP

4.72

3.12

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

61 dB(A)

61 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

198 %

145 %

Prated

29.25 kW

28.23 kW

SCOP

5.03

3.72

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

17.70 kW

17.09 kW

COP Tj = -7°C

3.97

2.98

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

12.92 kW

12.60 kW

COP Tj = +2°C

6.99

4.92

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

11.60 kW

11.10 kW

COP Tj = +7°C

8.03

6.30

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

11.12 kW

10.87 kW

COP Tj = 12°C

10.50

8.83

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

23.86 kW

23.03 kW

COP Tj = Tbiv

2.68

1.98

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

19.63 kW

18.77 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.16

1.53

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

24 W

24 W

PTO

31 W

31 W

PSB

24 W

24 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

9.00 kW

9.00 kW

Annual energy consumption Qhe

14344 kWh

18728 kWh

Pdh Tj = -15°C (if TOL<-20°C)

23.86

23.03

COP Tj = -15°C (if TOL<-20°C)

2.68

1.98

Cdh Tj = -15 °C

0.900

0.900

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

61 dB(A)

61 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

219 %

162 %

Prated

33.25 kW

31.69 kW

SCOP

5.55

4.14

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

29.42 kW

28.04 kW

COP Tj = -7°C

3.10

2.23

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

17.90 kW

17.07 kW

COP Tj = +2°C

5.61

4.16

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

11.51 kW

10.97 kW

COP Tj = +7°C

7.40

5.60

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

11.12 kW

10.74 kW

COP Tj = 12°C

10.50

8.14

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

29.42 kW

28.04 kW

COP Tj = Tbiv

3.10

2.23

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

26.96 kW

25.79 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.88

1.99

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

24 W

24 W

PTO

31 W

31 W

PSB

24 W

24 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

5.80 kW

5.80 kW

Annual energy consumption Qhe

12369 kWh

15830 kWh