1,400 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
10.32 kW
9.30 kW
El input
2.00 kW
2.86 kW
COP
5.16
3.25
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
213 %
150 %
Prated
8.52 kW
7.92 kW
SCOP
5.40
3.82
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
7.54 kW
7.01 kW
COP Tj = -7°C
3.32
2.34
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
4.71 kW
4.45 kW
COP Tj = +2°C
5.29
3.77
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.27 kW
4.09 kW
COP Tj = +7°C
7.63
5.18
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.31 kW
4.20 kW
COP Tj = 12°C
10.77
8.07
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
7.54 kW
7.01 kW
COP Tj = Tbiv
3.32
2.34
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.93 kW
6.32 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.00
2.08
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
24 W
24 W
PTO
31 W
31 W
PSB
24 W
24 W
PCK
35 W
35 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.50 kW
1.50 kW
Annual energy consumption Qhe
3257 kWh
4282 kWh
Colder Climate
EN 14825
Low temperature
Medium temperature
ηs
178 %
131 %
Prated
7.39 kW
7.00 kW
SCOP
4.53
3.36
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
5.09 kW
4.82 kW
COP Tj = -7°C
3.98
2.90
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
4.75 kW
4.57 kW
COP Tj = +2°C
5.87
4.27
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.30 kW
4.18 kW
COP Tj = +7°C
7.42
6.06
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.31 kW
4.24 kW
COP Tj = 12°C
10.77
9.22
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
6.03 kW
5.71 kW
COP Tj = Tbiv
2.81
2.04
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.82 kW
4.49 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.18
1.55
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
24 W
24 W
PTO
31 W
31 W
PSB
24 W
24 W
PCK
35 W
35 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.50 kW
2.50 kW
Annual energy consumption Qhe
4024 kWh
5134 kWh
Pdh Tj = -15°C (if TOL<-20°C)
6.03
5.71
COP Tj = -15°C (if TOL<-20°C)
2.81
2.04
Cdh Tj = -15 °C
0.900
0.900
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.09 kW
10.95 kW
El input
2.47 kW
3.56 kW
COP
4.90
3.08
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
133 %
Prated
8.68 kW
8.28 kW
SCOP
4.57
3.40
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
5.19 kW
5.02 kW
COP Tj = -7°C
3.93
2.88
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
4.75 kW
4.57 kW
COP Tj = +2°C
5.87
4.27
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.30 kW
4.18 kW
COP Tj = +7°C
7.42
6.06
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.31 kW
4.24 kW
COP Tj = 12°C
10.78
9.22
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
7.08 kW
6.75 kW
COP Tj = Tbiv
2.70
1.96
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.68 kW
5.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.11
1.50
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
24 W
24 W
PTO
31 W
31 W
PSB
24 W
24 W
PCK
35 W
35 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.00 kW
3.00 kW
Annual energy consumption Qhe
4683 kWh
6005 kWh
Pdh Tj = -15°C (if TOL<-20°C)
7.08
6.75
COP Tj = -15°C (if TOL<-20°C)
2.70
1.96
Cdh Tj = -15 °C
0.900
0.900
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
210 %
149 %
Prated
9.97 kW
9.32 kW
SCOP
5.32
3.81
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
8.82 kW
8.25 kW
COP Tj = -7°C
3.16
2.22
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
5.35 kW
5.08 kW
COP Tj = +2°C
5.15
3.76
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.27 kW
4.09 kW
COP Tj = +7°C
7.63
5.18
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.31 kW
4.20 kW
COP Tj = 12°C
10.78
8.07
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
8.82 kW
8.25 kW
COP Tj = Tbiv
3.16
2.22
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.13 kW
7.46 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.88
1.98
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
24 W
24 W
PTO
31 W
31 W
PSB
24 W
24 W
PCK
35 W
35 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.80 kW
1.80 kW
Annual energy consumption Qhe
3870 kWh
5056 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
14.09 kW
12.78 kW
El input
3.06 kW
4.45 kW
COP
4.61
2.87
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
179 %
133 %
Prated
10.13 kW
9.71 kW
SCOP
4.54
3.39
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.19 kW
5.90 kW
COP Tj = -7°C
3.80
2.81
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
4.75 kW
4.57 kW
COP Tj = +2°C
5.87
4.27
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.30 kW
4.18 kW
COP Tj = +7°C
7.42
6.06
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.31 kW
4.24 kW
COP Tj = 12°C
10.77
9.22
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
8.26 kW
7.92 kW
COP Tj = Tbiv
2.58
1.86
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.66 kW
6.28 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.01
1.43
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
24 W
24 W
PTO
31 W
31 W
PSB
24 W
24 W
PCK
35 W
35 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.50 kW
3.50 kW
Annual energy consumption Qhe
5495 kWh
7067 kWh
Pdh Tj = -15°C (if TOL<-20°C)
8.26
7.92
COP Tj = -15°C (if TOL<-20°C)
2.58
1.86
Cdh Tj = -15 °C
0.900
0.900
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
207 %
148 %
Prated
11.65 kW
10.88 kW
SCOP
5.25
3.78
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.30 kW
9.62 kW
COP Tj = -7°C
3.02
2.08
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
6.23 kW
5.82 kW
COP Tj = +2°C
5.02
3.71
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.27 kW
4.09 kW
COP Tj = +7°C
7.63
5.18
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.31 kW
4.20 kW
COP Tj = 12°C
10.77
8.57
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
10.30 kW
9.62 kW
COP Tj = Tbiv
3.02
2.08
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.48 kW
8.73 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.73
1.86
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
24 W
24 W
PTO
31 W
31 W
PSB
24 W
24 W
PCK
35 W
35 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.10 kW
2.10 kW
Annual energy consumption Qhe
4588 kWh
5946 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
15.93 kW
13.38 kW
El input
3.75 kW
5.05 kW
COP
4.25
2.65
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
178 %
132 %
Prated
10.63 kW
10.09 kW
SCOP
4.51
3.37
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.49 kW
6.09 kW
COP Tj = -7°C
3.73
2.79
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
3.94 kW
4.57 kW
COP Tj = +2°C
5.72
4.27
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.30 kW
4.18 kW
COP Tj = +7°C
7.42
6.06
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.31 kW
4.24 kW
COP Tj = 12°C
10.77
9.02
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
8.67 kW
8.23 kW
COP Tj = Tbiv
2.53
1.81
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.00 kW
6.60 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.98
1.40
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
24 W
24 W
PTO
31 W
31 W
PSB
24 W
24 W
PCK
35 W
35 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.50 kW
3.50 kW
Annual energy consumption Qhe
5808 kWh
7374 kWh
Pdh Tj = -15°C (if TOL<-20°C)
8.67
8.23
COP Tj = -15°C (if TOL<-20°C)
2.53
1.81
Cdh Tj = -15 °C
0.900
0.900
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
204 %
147 %
Prated
12.47 kW
11.31 kW
SCOP
5.17
3.74
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.03 kW
10.01 kW
COP Tj = -7°C
2.95
2.03
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
6.73 kW
6.07 kW
COP Tj = +2°C
4.91
3.70
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.42 kW
4.09 kW
COP Tj = +7°C
7.63
5.18
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.31 kW
4.20 kW
COP Tj = 12°C
10.77
7.92
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
11.03 kW
10.01 kW
COP Tj = Tbiv
2.95
2.03
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.14 kW
9.17 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.67
1.81
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
24 W
24 W
PTO
31 W
31 W
PSB
24 W
24 W
PCK
35 W
35 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.20 kW
2.20 kW
Annual energy consumption Qhe
4985 kWh
6244 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
10.32 kW
9.30 kW
El input
2.00 kW
2.86 kW
COP
5.16
3.25
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
178 %
131 %
Prated
7.39 kW
7.00 kW
SCOP
4.53
3.36
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
5.09 kW
4.82 kW
COP Tj = -7°C
3.98
2.90
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
4.75 kW
4.57 kW
COP Tj = +2°C
5.87
4.27
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.30 kW
4.18 kW
COP Tj = +7°C
7.42
6.06
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.31 kW
4.24 kW
COP Tj = 12°C
10.77
9.22
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
6.03 kW
5.71 kW
COP Tj = Tbiv
2.81
2.04
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.82 kW
4.49 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.18
1.55
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
24 W
24 W
PTO
31 W
31 W
PSB
24 W
24 W
PCK
35 W
35 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.50 kW
2.50 kW
Annual energy consumption Qhe
4024 kWh
5134 kWh
Pdh Tj = -15°C (if TOL<-20°C)
6.03
5.71
COP Tj = -15°C (if TOL<-20°C)
2.81
2.04
Cdh Tj = -15 °C
0.900
0.900
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
213 %
150 %
Prated
8.52 kW
7.92 kW
SCOP
5.40
3.82
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
7.54 kW
7.01 kW
COP Tj = -7°C
3.32
2.34
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
4.71 kW
4.45 kW
COP Tj = +2°C
5.29
3.77
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.27 kW
4.09 kW
COP Tj = +7°C
7.63
5.18
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.31 kW
4.20 kW
COP Tj = 12°C
10.77
8.07
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
7.54 kW
7.01 kW
COP Tj = Tbiv
3.32
2.34
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.93 kW
6.32 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.00
2.08
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
24 W
24 W
PTO
31 W
31 W
PSB
24 W
24 W
PCK
35 W
35 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.50 kW
1.50 kW
Annual energy consumption Qhe
3257 kWh
4282 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.09 kW
10.95 kW
El input
2.47 kW
3.56 kW
COP
4.90
3.08
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
133 %
Prated
8.68 kW
8.28 kW
SCOP
4.57
3.40
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
5.19 kW
5.02 kW
COP Tj = -7°C
3.93
2.88
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
4.75 kW
4.57 kW
COP Tj = +2°C
5.87
4.27
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.30 kW
4.18 kW
COP Tj = +7°C
7.42
6.06
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.31 kW
4.24 kW
COP Tj = 12°C
10.78
9.22
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
7.08 kW
6.75 kW
COP Tj = Tbiv
2.70
1.96
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.68 kW
5.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.11
1.50
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
24 W
24 W
PTO
31 W
31 W
PSB
24 W
24 W
PCK
35 W
35 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.00 kW
3.00 kW
Annual energy consumption Qhe
4683 kWh
6005 kWh
Pdh Tj = -15°C (if TOL<-20°C)
7.08
6.75
COP Tj = -15°C (if TOL<-20°C)
2.70
1.96
Cdh Tj = -15 °C
0.900
0.900
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
210 %
149 %
Prated
9.97 kW
9.32 kW
SCOP
5.32
3.81
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
8.82 kW
8.25 kW
COP Tj = -7°C
3.16
2.22
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
5.35 kW
5.08 kW
COP Tj = +2°C
5.15
3.76
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.27 kW
4.09 kW
COP Tj = +7°C
7.63
5.18
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.31 kW
4.20 kW
COP Tj = 12°C
10.78
8.07
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
8.82 kW
8.25 kW
COP Tj = Tbiv
3.16
2.22
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.13 kW
7.46 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.88
1.98
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
24 W
24 W
PTO
31 W
31 W
PSB
24 W
24 W
PCK
35 W
35 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.80 kW
1.80 kW
Annual energy consumption Qhe
3870 kWh
5056 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
14.09 kW
12.78 kW
El input
3.06 kW
4.45 kW
COP
4.61
2.87
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
179 %
133 %
Prated
10.13 kW
9.71 kW
SCOP
4.54
3.39
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.19 kW
5.90 kW
COP Tj = -7°C
3.80
2.81
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
4.75 kW
4.57 kW
COP Tj = +2°C
5.87
4.27
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.30 kW
4.18 kW
COP Tj = +7°C
7.42
6.06
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.31 kW
4.24 kW
COP Tj = 12°C
10.77
9.22
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
8.26 kW
7.92 kW
COP Tj = Tbiv
2.58
1.86
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.66 kW
6.28 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.01
1.43
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
24 W
24 W
PTO
31 W
31 W
PSB
24 W
24 W
PCK
35 W
35 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.50 kW
3.50 kW
Annual energy consumption Qhe
5495 kWh
7067 kWh
Pdh Tj = -15°C (if TOL<-20°C)
8.26
7.92
COP Tj = -15°C (if TOL<-20°C)
2.58
1.86
Cdh Tj = -15 °C
0.900
0.900
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
207 %
148 %
Prated
11.65 kW
10.88 kW
SCOP
5.25
3.78
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.30 kW
9.62 kW
COP Tj = -7°C
3.02
2.08
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
6.23 kW
5.82 kW
COP Tj = +2°C
5.02
3.71
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.27 kW
4.09 kW
COP Tj = +7°C
7.63
5.18
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.31 kW
4.20 kW
COP Tj = 12°C
10.77
8.57
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
10.30 kW
9.62 kW
COP Tj = Tbiv
3.02
2.08
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.48 kW
8.73 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.73
1.86
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
24 W
24 W
PTO
31 W
31 W
PSB
24 W
24 W
PCK
35 W
35 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.10 kW
2.10 kW
Annual energy consumption Qhe
4588 kWh
5946 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
15.93 kW
13.38 kW
El input
3.75 kW
5.05 kW
COP
4.25
2.65
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
178 %
132 %
Prated
10.63 kW
10.09 kW
SCOP
4.51
3.37
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.49 kW
6.09 kW
COP Tj = -7°C
3.73
2.79
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
3.94 kW
4.57 kW
COP Tj = +2°C
5.72
4.27
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.30 kW
4.18 kW
COP Tj = +7°C
7.42
6.06
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.31 kW
4.24 kW
COP Tj = 12°C
10.77
9.02
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
8.67 kW
8.23 kW
COP Tj = Tbiv
2.53
1.81
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.00 kW
6.60 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.98
1.40
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
24 W
24 W
PTO
31 W
31 W
PSB
24 W
24 W
PCK
35 W
35 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.50 kW
3.50 kW
Annual energy consumption Qhe
5808 kWh
7374 kWh
Pdh Tj = -15°C (if TOL<-20°C)
8.67
8.23
COP Tj = -15°C (if TOL<-20°C)
2.53
1.81
Cdh Tj = -15 °C
0.900
0.900
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
204 %
147 %
Prated
12.47 kW
11.31 kW
SCOP
5.17
3.74
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.03 kW
10.01 kW
COP Tj = -7°C
2.95
2.03
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
6.73 kW
6.07 kW
COP Tj = +2°C
4.91
3.70
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.42 kW
4.09 kW
COP Tj = +7°C
7.63
5.18
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.31 kW
4.20 kW
COP Tj = 12°C
10.77
7.92
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
11.03 kW
10.01 kW
COP Tj = Tbiv
2.95
2.03
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.14 kW
9.17 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.67
1.81
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
24 W
24 W
PTO
31 W
31 W
PSB
24 W
24 W
PCK
35 W
35 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.20 kW
2.20 kW
Annual energy consumption Qhe
4985 kWh
6244 kWh