Certificate holders

Subtype

Split Air-to-Water Heat Pump System- R32- W082+ W102

Certificate Holder
Qingdao Haier Air Conditioner Electric Co., Ltd.
Haier Development Zone Industrial Park, Economic Development Zone, Qingdao City,
Shandong Province
China
Registration number
041-K073-06
Certification Body
BRE Global Limited
Subtype title
Split Air-to-Water Heat Pump System- R32- W082+ W102
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

1,600 kg

Certification Date
06.11.2023
Testing basis
Heat Pump Keymark Scheme Rules Rev 12
Generate PDF Export model CSV Download certificate
  • Number of models 2

Models

Indoor unit: HU102WAMNA, Outdoor unit: AW082SNCHA
Configure model
Model name
Indoor unit: HU102WAMNA, Outdoor unit: AW082SNCHA
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

8.07 kW

8.08 kW

El input

1.60 kW

2.71 kW

COP

5.05

2.98

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

37 dB(A)

43 dB(A)

Sound power level outdoor

65 dB(A)

65 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

178 %

132 %

Prated

8.05 kW

8.09 kW

SCOP

4.53

3.37

Tbiv

-7 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

7.12 kW

7.16 kW

COP Tj = -7°C

3.39

2.15

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

4.83 kW

4.52 kW

COP Tj = +2°C

5.01

3.39

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

3.83 kW

3.84 kW

COP Tj = +7°C

6.15

4.39

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

4.71 kW

4.51 kW

COP Tj = 12°C

3.52

6.41

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

7.12 kW

7.16 kW

COP Tj = Tbiv

3.39

2.15

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.15 kW

6.05 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.95

1.41

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

60 °C

60 °C

Poff

18 W

18 W

PTO

19 W

19 W

PSB

19 W

19 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

2.05 kW

Annual energy consumption Qhe

3665 kWh

4964 kWh

Indoor unit: HU102WAMNA, Outdoor unit: AW102SNCHA
Configure model
Model name
Indoor unit: HU102WAMNA, Outdoor unit: AW102SNCHA
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

9.84 kW

10.03 kW

El input

2.10 kW

3.54 kW

COP

4.69

2.83

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

39 dB(A)

39 dB(A)

Sound power level outdoor

68 dB(A)

69 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

188 %

126 %

Prated

10.23 kW

9.65 kW

SCOP

4.77

3.24

Tbiv

-7 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

9.05 kW

8.53 kW

COP Tj = -7°C

3.09

2.07

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

5.46 kW

5.34 kW

COP Tj = +2°C

4.66

3.11

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

3.90 kW

3.72 kW

COP Tj = +7°C

6.40

4.34

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

4.62 kW

4.23 kW

COP Tj = 12°C

9.26

6.36

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

9.05 kW

8.53 kW

COP Tj = Tbiv

3.09

2.07

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.09 kW

6.70 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.64

1.66

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

60 °C

60 °C

Poff

18 W

18 W

PTO

18 W

18 W

PSB

19 W

19 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

2.14 kW

2.95 kW

Annual energy consumption Qhe

4432 kWh

6160 kWh