1,200 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.09 kW
4.26 kW
El input
0.78 kW
1.47 kW
COP
5.23
2.89
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
39 dB(A)
Sound power level outdoor
54 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
191 %
133 %
Prated
4.06 kW
4.11 kW
SCOP
4.85
3.39
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
3.59 kW
3.63 kW
COP Tj = -7°C
3.17
2.11
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
2.22 kW
2.26 kW
COP Tj = +2°C
4.84
3.40
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
2.01 kW
2.30 kW
COP Tj = +7°C
6.21
4.47
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
2.38 kW
2.38 kW
COP Tj = 12°C
8.77
6.96
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
3.59 kW
3.63 kW
COP Tj = Tbiv
3.17
2.11
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.29 kW
3.52 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.93
1.70
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
60 °C
60 °C
Poff
17 W
17 W
PTO
17 W
17 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.59 kW
Annual energy consumption Qhe
1729 kWh
2501 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.04 kW
6.09 kW
El input
1.20 kW
2.12 kW
COP
5.05
2.88
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
39 dB(A)
Sound power level outdoor
60 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
194 %
131 %
Prated
5.96 kW
5.94 kW
SCOP
4.92
3.34
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
5.27 kW
5.26 kW
COP Tj = -7°C
3.25
2.12
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
3.30 kW
3.30 kW
COP Tj = +2°C
4.89
3.27
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
2.35 kW
2.21 kW
COP Tj = +7°C
6.10
4.29
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
2.88 kW
2.78 kW
COP Tj = 12°C
9.38
7.01
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
5.27 kW
5.26 kW
COP Tj = Tbiv
3.25
2.12
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.13 kW
3.92 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.89
1.52
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
60 °C
60 °C
Poff
17 W
17 W
PTO
17 W
17 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.83 kW
2.02 kW
Annual energy consumption Qhe
2501 kWh
3671 kWh