1,700 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
8.00 kW
7.70 kW
El input
1.60 kW
2.70 kW
COP
5.00
2.85
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
42 dB(A)
42 dB(A)
Sound power level outdoor
66 dB(A)
66 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
190 %
129 %
Prated
8.00 kW
7.50 kW
SCOP
4.90
3.30
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
7.07 kW
6.61 kW
COP Tj = -7°C
2.96
2.03
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
4.37 kW
4.09 kW
COP Tj = +2°C
4.38
3.14
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
2.95 kW
2.75 kW
COP Tj = +7°C
6.46
4.61
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.16 kW
2.75 kW
COP Tj = 12°C
9.86
4.61
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
7.07 kW
6.61 kW
COP Tj = Tbiv
2.96
2.03
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.71 kW
6.57 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.57
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
62 °C
62 °C
Poff
10 W
10 W
PTO
20 W
20 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.29 kW
0.93 kW
Annual energy consumption Qhe
3514 kWh
4611 kWh