Certificate holders

Subtype

Split Heat pump 10KW

Certificate Holder
Guangdong Carrier Heating, Ventilation & Air Conditioning Company Limited
No.28-5, Eastern Industrial Park, Lishui Town, Nanhai District
528244 Foshan Guangdong
China
Registration number
011-1W0698
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
Split Heat pump 10KW
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

2,000 kg

Certification Date
09.10.2023
Testing basis
HP KEYMARK certification scheme rules V12
Generate PDF Export model CSV
  • Number of models 1

Models

CS-D010H/R4-D01(CHD-010EP/R4)
Configure model
Model name
CS-D010H/R4-D01(CHD-010EP/R4)
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

10.00 kW

9.50 kW

El input

2.17 kW

3.52 kW

COP

4.60

2.70

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

42 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

183 %

127 %

Prated

9.50 kW

9.00 kW

SCOP

4.65

3.25

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

8.36 kW

8.04 kW

COP Tj = -7°C

2.88

2.03

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

5.25 kW

4.91 kW

COP Tj = +2°C

4.43

3.15

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

3.54 kW

3.25 kW

COP Tj = +7°C

6.47

4.38

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.77 kW

3.70 kW

COP Tj = 12°C

9.82

7.21

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

8.36 kW

8.04 kW

COP Tj = Tbiv

2.88

2.03

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.23 kW

7.30 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.49

1.72

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

62 °C

62 °C

Poff

10 W

10 W

PTO

20 W

20 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.27 kW

1.70 kW

Annual energy consumption Qhe

4150 kWh

5585 kWh