1,600 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
8.00 kW
7.70 kW
El input
1.68 kW
2.70 kW
COP
4.75
2.85
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
193 %
131 %
Prated
8.09 kW
7.61 kW
SCOP
4.90
3.36
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
7.16 kW
6.73 kW
COP Tj = -7°C
3.08
2.03
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
4.33 kW
4.07 kW
COP Tj = +2°C
4.62
3.15
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
2.98 kW
3.40 kW
COP Tj = +7°C
6.91
4.92
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.06 kW
3.42 kW
COP Tj = 12°C
9.26
7.10
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
7.16 kW
6.73 kW
COP Tj = Tbiv
3.08
2.03
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.80 kW
6.62 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.78
1.74
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
62 °C
62 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.29 kW
0.99 kW
Annual energy consumption Qhe
3335 kWh
4590 kWh