1,000 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.00 kW
4.00 kW
El input
0.83 kW
1.54 kW
COP
4.80
2.59
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
61 dB(A)
61 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
186 %
126 %
Prated
4.00 kW
4.01 kW
SCOP
4.73
3.33
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
3.55 kW
3.55 kW
COP Tj = -7°C
3.05
1.98
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
2.21 kW
2.35 kW
COP Tj = +2°C
4.58
3.10
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
2.03 kW
2.61 kW
COP Tj = +7°C
6.48
4.79
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
1.99 kW
2.51 kW
COP Tj = 12°C
9.42
7.08
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
3.55 kW
3.55 kW
COP Tj = Tbiv
3.05
1.98
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.35 kW
3.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.80
1.61
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
62 °C
62 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.65 kW
0.71 kW
Annual energy consumption Qhe
1725 kWh
2539 kWh