Certificate holders

Subtype

NIMBUS 35/50 S - Plus-H

Certificate Holder
Ariston Thermo Group
Viale Aristide Merloni 45
I-60044 Fabriano (AN)
Italy
Registration number
ICIM-PDC-000240
Certification Body
ICIM S.p.A.
Subtype title
NIMBUS 35/50 S - Plus-H
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

1,400 kg

Certification Date
12.02.2024
Testing basis
V12
Generate PDF Export model CSV
  • Number of models 2

Models

NIMBUS PLUS-H 35 S NET R32
Configure model
Model name
NIMBUS PLUS-H 35 S NET R32
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

3.50 kW

2.95 kW

El input

0.69 kW

1.09 kW

COP

5.10

2.70

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

1.03 kW

0.77 kW

Cooling capacity

3.50

4.08

EER

3.40

5.29

EN 14825

+7°C/+12°C

Pdesignc

3.5 kW

SEER

4.87

Pdc Tj = 35°C

3.5 kW

EER Tj = 35°C

3

Pdc Tj = 30°C

2.58 kW

EER Tj = 30°C

4.33

Cdc Tj = 30 °C

0.98

Pdc Tj = 25°C

1.72 kW

EER Tj = 25°C

5.86

Cdc Tj = 25 °C

0.95

Pdc Tj = 20°C

1.79 kW

EER Tj = 20°C

7.24

Cdc Tj = 20 °C

0.94

Poff

14 W

PTO

14 W

PSB

14 W

PCK

0 W

Annual energy consumption Qce

628 kWh

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

52 dB(A)

52 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

2.84 kW

2.35 kW

ηs

240 %

137 %

Prated

2.80 kW

2.35 kW

SCOP

6.06

3.50

Tbiv

2 °C

2 °C

TOL

-20 °C

-20 °C

Pdh Tj = +2°C

2.80 kW

2.35 kW

COP Tj = +2°C

4.10

2.26

Cdh Tj = +2 °C

0.981

0.987

Pdh Tj = +7°C

1.88 kW

1.60 kW

COP Tj = +7°C

5.57

2.80

Cdh Tj = +7 °C

0.961

0.977

Pdh Tj = 12°C

1.91 kW

1.81 kW

COP Tj = 12°C

7.94

5.10

Cdh Tj = +12 °C

0.946

0.963

Pdh Tj = Tbiv

2.80 kW

2.35 kW

COP Tj = Tbiv

4.10

2.26

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

3.03 kW

2.46 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.25

1.52

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.982

0.988

WTOL

60 °C

60 °C

Poff

13 W

13 W

PTO

13 W

13 W

PSB

13 W

13 W

PCK

13 W

13 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Backup Heater

4.00 kW

4.00 kW

Annual energy consumption Qhe

617 kWh

897 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

52 dB(A)

52 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

7.75 kW

7.43 kW

ηs

151 %

120 %

Prated

7.75 kW

7.43 kW

SCOP

3.85

3.07

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

4.69 kW

4.50 kW

COP Tj = -7°C

3.54

2.76

Cdh Tj = -7 °C

0.990

0.992

Pdh Tj = +2°C

2.95 kW

2.94 kW

COP Tj = +2°C

5.16

3.99

Cdh Tj = +2 °C

0.977

0.982

Pdh Tj = +7°C

1.89 kW

1.92 kW

COP Tj = +7°C

7.19

5.35

Cdh Tj = +7 °C

0.951

0.964

Pdh Tj = 12°C

1.92 kW

1.93 kW

COP Tj = 12°C

8.55

6.96

Cdh Tj = +12 °C

0.942

0.953

Pdh Tj = Tbiv

4.69 kW

4.50 kW

COP Tj = Tbiv

3.54

2.76

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

3.03 kW

2.46 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.25

1.52

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

0.992

WTOL

60 °C

60 °C

Poff

13 W

13 W

PTO

13 W

13 W

PSB

13 W

13 W

PCK

13 W

13 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

7.34 kW

7.04 kW

Backup Heater

4.00 kW

4.00 kW

Annual energy consumption Qhe

4964 kWh

5968 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

52 dB(A)

52 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

5.20 kW

4.63 kW

ηs

193 %

134 %

Prated

5.20 kW

4.63 kW

SCOP

4.89

3.43

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

4.60 kW

4.10 kW

COP Tj = -7°C

3.21

2.28

Cdh Tj = -7 °C

0.991

0.993

Pdh Tj = +2°C

2.88 kW

2.63 kW

COP Tj = +2°C

4.66

3.35

Cdh Tj = +2 °C

0.979

0.983

Pdh Tj = +7°C

1.85 kW

1.76 kW

COP Tj = +7°C

6.56

4.22

Cdh Tj = +7 °C

0.954

0.969

Pdh Tj = 12°C

1.92 kW

1.84 kW

COP Tj = 12°C

8.49

6.33

Cdh Tj = +12 °C

0.943

0.955

Pdh Tj = Tbiv

4.60 kW

4.10 kW

COP Tj = Tbiv

3.21

2.28

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

3.03 kW

2.46 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.25

1.52

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.991

0.993

WTOL

60 °C

60 °C

Poff

13 W

13 W

PTO

13 W

13 W

PSB

13 W

13 W

PCK

13 W

13 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

2.17 kW

2.17 kW

Backup Heater

4.00 kW

4.00 kW

Annual energy consumption Qhe

2198 kWh

2790 kWh

NIMBUS PLUS-H 50 S NET R32
Configure model
Model name
NIMBUS PLUS-H 50 S NET R32
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5.00 kW

3.80 kW

El input

1.00 kW

1.36 kW

COP

5.00

2.80

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

1.75 kW

Cooling capacity

5.00

EER

2.85

4.56

EN 14825

+7°C/+12°C

Pdesignc

5 kW

SEER

4.85

Pdc Tj = 35°C

5 kW

EER Tj = 35°C

2.85

Pdc Tj = 30°C

3.77 kW

EER Tj = 30°C

4.25

Cdc Tj = 30 °C

0.98

Pdc Tj = 25°C

2.32 kW

EER Tj = 25°C

5.38

Cdc Tj = 25 °C

0.97

Pdc Tj = 20°C

1.87 kW

EER Tj = 20°C

7.85

Cdc Tj = 20 °C

0.94

Poff

14 W

PTO

14 W

PSB

14 W

PCK

0 W

Annual energy consumption Qce

925 kWh

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

54 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

3.44 kW

2.97 kW

ηs

244 %

150 %

Prated

3.40 kW

2.90 kW

SCOP

6.17

3.83

Tbiv

2 °C

2 °C

TOL

-20 °C

-20 °C

Pdh Tj = +2°C

3.40 kW

2.90 kW

COP Tj = +2°C

3.75

2.30

Cdh Tj = +2 °C

0.985

0.989

Pdh Tj = +7°C

2.22 kW

2.02 kW

COP Tj = +7°C

5.66

3.16

Cdh Tj = +7 °C

0.964

0.978

Pdh Tj = 12°C

1.86 kW

1.76 kW

COP Tj = 12°C

8.01

5.40

Cdh Tj = +12 °C

0.940

0.957

Pdh Tj = Tbiv

3.40 kW

2.90 kW

COP Tj = Tbiv

3.75

2.30

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

3.69 kW

3.18 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.30

1.54

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.985

0.989

WTOL

60 °C

60 °C

Poff

14 W

14 W

PTO

14 W

14 W

PSB

14 W

14 W

PCK

14 W

14 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Backup Heater

4.00 kW

4.00 kW

Annual energy consumption Qhe

734 kWh

1012 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

54 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

8.26 kW

8.26 kW

ηs

152 %

118 %

Prated

8.26 kW

8.26 kW

SCOP

3.89

3.02

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

5.00 kW

5.00 kW

COP Tj = -7°C

3.50

2.71

Cdh Tj = -7 °C

0.990

0.992

Pdh Tj = +2°C

3.00 kW

3.11 kW

COP Tj = +2°C

5.15

3.81

Cdh Tj = +2 °C

0.976

0.983

Pdh Tj = +7°C

1.99 kW

2.28 kW

COP Tj = +7°C

7.22

5.29

Cdh Tj = +7 °C

0.949

0.968

Pdh Tj = 12°C

1.87 kW

1.87 kW

COP Tj = 12°C

8.70

6.88

Cdh Tj = +12 °C

0.935

0.948

Pdh Tj = Tbiv

5.00 kW

5.00 kW

COP Tj = Tbiv

3.50

2.71

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

3.69 kW

4.90 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.30

1.51

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.991

0.993

WTOL

60 °C

60 °C

Poff

14 W

14 W

PTO

14 W

14 W

PSB

14 W

14 W

PCK

14 W

14 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

7.83 kW

7.83 kW

Backup Heater

4.00 kW

4.00 kW

Annual energy consumption Qhe

5240 kWh

6739 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

54 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

5.65 kW

5.65 kW

ηs

184 %

136 %

Prated

5.65 kW

5.65 kW

SCOP

4.66

3.47

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

5.00 kW

5.00 kW

COP Tj = -7°C

3.11

2.28

Cdh Tj = -7 °C

0.991

0.994

Pdh Tj = +2°C

3.11 kW

3.11 kW

COP Tj = +2°C

4.32

3.30

Cdh Tj = +2 °C

0.981

0.985

Pdh Tj = +7°C

1.96 kW

2.19 kW

COP Tj = +7°C

6.48

4.58

Cdh Tj = +7 °C

0.954

0.971

Pdh Tj = 12°C

1.86 kW

1.84 kW

COP Tj = 12°C

8.41

6.33

Cdh Tj = +12 °C

0.937

0.952

Pdh Tj = Tbiv

5.00 kW

5.00 kW

COP Tj = Tbiv

3.11

2.28

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

3.69 kW

3.18 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.30

1.54

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.992

0.994

WTOL

60 °C

60 °C

Poff

14 W

14 W

PTO

14 W

14 W

PSB

14 W

14 W

PCK

14 W

14 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.96 kW

2.47 kW

Backup Heater

4.00 kW

4.00 kW

Annual energy consumption Qhe

2504 kWh

3360 kWh