1,400 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
3.50 kW
2.95 kW
El input
0.69 kW
1.09 kW
COP
5.10
2.70
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
1.03 kW
0.77 kW
Cooling capacity
3.50
4.08
EER
3.40
5.29
EN 14825
+7°C/+12°C
Pdesignc
3.5 kW
SEER
4.87
Pdc Tj = 35°C
3.5 kW
EER Tj = 35°C
3
Pdc Tj = 30°C
2.58 kW
EER Tj = 30°C
4.33
Cdc Tj = 30 °C
0.98
Pdc Tj = 25°C
1.72 kW
EER Tj = 25°C
5.86
Cdc Tj = 25 °C
0.95
Pdc Tj = 20°C
1.79 kW
EER Tj = 20°C
7.24
Cdc Tj = 20 °C
0.94
Poff
14 W
PTO
14 W
PSB
14 W
PCK
0 W
Annual energy consumption Qce
628 kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
52 dB(A)
52 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
2.84 kW
2.35 kW
ηs
240 %
137 %
Prated
2.80 kW
2.35 kW
SCOP
6.06
3.50
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
2.80 kW
2.35 kW
COP Tj = +2°C
4.10
2.26
Cdh Tj = +2 °C
0.981
0.987
Pdh Tj = +7°C
1.88 kW
1.60 kW
COP Tj = +7°C
5.57
2.80
Cdh Tj = +7 °C
0.961
0.977
Pdh Tj = 12°C
1.91 kW
1.81 kW
COP Tj = 12°C
7.94
5.10
Cdh Tj = +12 °C
0.946
0.963
Pdh Tj = Tbiv
2.80 kW
2.35 kW
COP Tj = Tbiv
4.10
2.26
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.03 kW
2.46 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.25
1.52
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.982
0.988
WTOL
60 °C
60 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
13 W
13 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Backup Heater
4.00 kW
4.00 kW
Annual energy consumption Qhe
617 kWh
897 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
52 dB(A)
52 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
7.75 kW
7.43 kW
ηs
151 %
120 %
Prated
7.75 kW
7.43 kW
SCOP
3.85
3.07
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.69 kW
4.50 kW
COP Tj = -7°C
3.54
2.76
Cdh Tj = -7 °C
0.990
0.992
Pdh Tj = +2°C
2.95 kW
2.94 kW
COP Tj = +2°C
5.16
3.99
Cdh Tj = +2 °C
0.977
0.982
Pdh Tj = +7°C
1.89 kW
1.92 kW
COP Tj = +7°C
7.19
5.35
Cdh Tj = +7 °C
0.951
0.964
Pdh Tj = 12°C
1.92 kW
1.93 kW
COP Tj = 12°C
8.55
6.96
Cdh Tj = +12 °C
0.942
0.953
Pdh Tj = Tbiv
4.69 kW
4.50 kW
COP Tj = Tbiv
3.54
2.76
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.03 kW
2.46 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.25
1.52
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.992
WTOL
60 °C
60 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
13 W
13 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.34 kW
7.04 kW
Backup Heater
4.00 kW
4.00 kW
Annual energy consumption Qhe
4964 kWh
5968 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
52 dB(A)
52 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
5.20 kW
4.63 kW
ηs
193 %
134 %
Prated
5.20 kW
4.63 kW
SCOP
4.89
3.43
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.60 kW
4.10 kW
COP Tj = -7°C
3.21
2.28
Cdh Tj = -7 °C
0.991
0.993
Pdh Tj = +2°C
2.88 kW
2.63 kW
COP Tj = +2°C
4.66
3.35
Cdh Tj = +2 °C
0.979
0.983
Pdh Tj = +7°C
1.85 kW
1.76 kW
COP Tj = +7°C
6.56
4.22
Cdh Tj = +7 °C
0.954
0.969
Pdh Tj = 12°C
1.92 kW
1.84 kW
COP Tj = 12°C
8.49
6.33
Cdh Tj = +12 °C
0.943
0.955
Pdh Tj = Tbiv
4.60 kW
4.10 kW
COP Tj = Tbiv
3.21
2.28
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.03 kW
2.46 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.25
1.52
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.991
0.993
WTOL
60 °C
60 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
13 W
13 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.17 kW
2.17 kW
Backup Heater
4.00 kW
4.00 kW
Annual energy consumption Qhe
2198 kWh
2790 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.00 kW
3.80 kW
El input
1.00 kW
1.36 kW
COP
5.00
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
1.75 kW
Cooling capacity
5.00
EER
2.85
4.56
EN 14825
+7°C/+12°C
Pdesignc
5 kW
SEER
4.85
Pdc Tj = 35°C
5 kW
EER Tj = 35°C
2.85
Pdc Tj = 30°C
3.77 kW
EER Tj = 30°C
4.25
Cdc Tj = 30 °C
0.98
Pdc Tj = 25°C
2.32 kW
EER Tj = 25°C
5.38
Cdc Tj = 25 °C
0.97
Pdc Tj = 20°C
1.87 kW
EER Tj = 20°C
7.85
Cdc Tj = 20 °C
0.94
Poff
14 W
PTO
14 W
PSB
14 W
PCK
0 W
Annual energy consumption Qce
925 kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
54 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
3.44 kW
2.97 kW
ηs
244 %
150 %
Prated
3.40 kW
2.90 kW
SCOP
6.17
3.83
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
3.40 kW
2.90 kW
COP Tj = +2°C
3.75
2.30
Cdh Tj = +2 °C
0.985
0.989
Pdh Tj = +7°C
2.22 kW
2.02 kW
COP Tj = +7°C
5.66
3.16
Cdh Tj = +7 °C
0.964
0.978
Pdh Tj = 12°C
1.86 kW
1.76 kW
COP Tj = 12°C
8.01
5.40
Cdh Tj = +12 °C
0.940
0.957
Pdh Tj = Tbiv
3.40 kW
2.90 kW
COP Tj = Tbiv
3.75
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.69 kW
3.18 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.30
1.54
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.985
0.989
WTOL
60 °C
60 °C
Poff
14 W
14 W
PTO
14 W
14 W
PSB
14 W
14 W
PCK
14 W
14 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Backup Heater
4.00 kW
4.00 kW
Annual energy consumption Qhe
734 kWh
1012 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
54 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
8.26 kW
8.26 kW
ηs
152 %
118 %
Prated
8.26 kW
8.26 kW
SCOP
3.89
3.02
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
5.00 kW
5.00 kW
COP Tj = -7°C
3.50
2.71
Cdh Tj = -7 °C
0.990
0.992
Pdh Tj = +2°C
3.00 kW
3.11 kW
COP Tj = +2°C
5.15
3.81
Cdh Tj = +2 °C
0.976
0.983
Pdh Tj = +7°C
1.99 kW
2.28 kW
COP Tj = +7°C
7.22
5.29
Cdh Tj = +7 °C
0.949
0.968
Pdh Tj = 12°C
1.87 kW
1.87 kW
COP Tj = 12°C
8.70
6.88
Cdh Tj = +12 °C
0.935
0.948
Pdh Tj = Tbiv
5.00 kW
5.00 kW
COP Tj = Tbiv
3.50
2.71
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.69 kW
4.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.30
1.51
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.991
0.993
WTOL
60 °C
60 °C
Poff
14 W
14 W
PTO
14 W
14 W
PSB
14 W
14 W
PCK
14 W
14 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.83 kW
7.83 kW
Backup Heater
4.00 kW
4.00 kW
Annual energy consumption Qhe
5240 kWh
6739 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
54 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
5.65 kW
5.65 kW
ηs
184 %
136 %
Prated
5.65 kW
5.65 kW
SCOP
4.66
3.47
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
5.00 kW
5.00 kW
COP Tj = -7°C
3.11
2.28
Cdh Tj = -7 °C
0.991
0.994
Pdh Tj = +2°C
3.11 kW
3.11 kW
COP Tj = +2°C
4.32
3.30
Cdh Tj = +2 °C
0.981
0.985
Pdh Tj = +7°C
1.96 kW
2.19 kW
COP Tj = +7°C
6.48
4.58
Cdh Tj = +7 °C
0.954
0.971
Pdh Tj = 12°C
1.86 kW
1.84 kW
COP Tj = 12°C
8.41
6.33
Cdh Tj = +12 °C
0.937
0.952
Pdh Tj = Tbiv
5.00 kW
5.00 kW
COP Tj = Tbiv
3.11
2.28
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.69 kW
3.18 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.30
1.54
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.992
0.994
WTOL
60 °C
60 °C
Poff
14 W
14 W
PTO
14 W
14 W
PSB
14 W
14 W
PCK
14 W
14 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.96 kW
2.47 kW
Backup Heater
4.00 kW
4.00 kW
Annual energy consumption Qhe
2504 kWh
3360 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
3.50 kW
2.95 kW
El input
0.69 kW
1.09 kW
COP
5.10
2.70
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
1.03 kW
0.77 kW
Cooling capacity
3.50
4.08
EER
3.40
5.29
EN 14825
+7°C/+12°C
Pdesignc
3.5 kW
SEER
4.87
Pdc Tj = 35°C
3.5 kW
EER Tj = 35°C
3
Pdc Tj = 30°C
2.58 kW
EER Tj = 30°C
4.33
Cdc Tj = 30 °C
0.98
Pdc Tj = 25°C
1.72 kW
EER Tj = 25°C
5.86
Cdc Tj = 25 °C
0.95
Pdc Tj = 20°C
1.79 kW
EER Tj = 20°C
7.24
Cdc Tj = 20 °C
0.94
Poff
14 W
PTO
14 W
PSB
14 W
PCK
0 W
Annual energy consumption Qce
628 kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
Sound power level outdoor
52 dB(A)
52 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
2.84 kW
2.35 kW
ηs
240 %
137 %
Prated
2.80 kW
2.35 kW
SCOP
6.06
3.50
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
2.80 kW
2.35 kW
COP Tj = +2°C
4.10
2.26
Cdh Tj = +2 °C
0.981
0.987
Pdh Tj = +7°C
1.88 kW
1.60 kW
COP Tj = +7°C
5.57
2.80
Cdh Tj = +7 °C
0.961
0.977
Pdh Tj = 12°C
1.91 kW
1.81 kW
COP Tj = 12°C
7.94
5.10
Cdh Tj = +12 °C
0.946
0.963
Pdh Tj = Tbiv
2.80 kW
2.35 kW
COP Tj = Tbiv
4.10
2.26
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.03 kW
2.46 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.25
1.52
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.982
0.988
WTOL
60 °C
60 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
13 W
13 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Backup Heater
4.00 kW
4.00 kW
Annual energy consumption Qhe
617 kWh
897 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
Sound power level outdoor
52 dB(A)
52 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
7.75 kW
7.43 kW
ηs
151 %
120 %
Prated
7.75 kW
7.43 kW
SCOP
3.85
3.07
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.69 kW
4.50 kW
COP Tj = -7°C
3.54
2.76
Cdh Tj = -7 °C
0.990
0.992
Pdh Tj = +2°C
2.95 kW
2.94 kW
COP Tj = +2°C
5.16
3.99
Cdh Tj = +2 °C
0.977
0.982
Pdh Tj = +7°C
1.89 kW
1.92 kW
COP Tj = +7°C
7.19
5.35
Cdh Tj = +7 °C
0.951
0.964
Pdh Tj = 12°C
1.92 kW
1.93 kW
COP Tj = 12°C
8.55
6.96
Cdh Tj = +12 °C
0.942
0.953
Pdh Tj = Tbiv
4.69 kW
4.50 kW
COP Tj = Tbiv
3.54
2.76
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.03 kW
2.46 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.25
1.52
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.992
WTOL
60 °C
60 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
13 W
13 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.34 kW
7.04 kW
Backup Heater
4.00 kW
4.00 kW
Annual energy consumption Qhe
4964 kWh
5968 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
Sound power level outdoor
52 dB(A)
52 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
5.20 kW
4.63 kW
ηs
193 %
134 %
Prated
5.20 kW
4.63 kW
SCOP
4.89
3.43
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.60 kW
4.10 kW
COP Tj = -7°C
3.21
2.28
Cdh Tj = -7 °C
0.991
0.993
Pdh Tj = +2°C
2.88 kW
2.63 kW
COP Tj = +2°C
4.66
3.35
Cdh Tj = +2 °C
0.979
0.983
Pdh Tj = +7°C
1.85 kW
1.76 kW
COP Tj = +7°C
6.56
4.22
Cdh Tj = +7 °C
0.954
0.969
Pdh Tj = 12°C
1.92 kW
1.84 kW
COP Tj = 12°C
8.49
6.33
Cdh Tj = +12 °C
0.943
0.955
Pdh Tj = Tbiv
4.60 kW
4.10 kW
COP Tj = Tbiv
3.21
2.28
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.03 kW
2.46 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.25
1.52
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.991
0.993
WTOL
60 °C
60 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
13 W
13 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.17 kW
2.17 kW
Backup Heater
4.00 kW
4.00 kW
Annual energy consumption Qhe
2198 kWh
2790 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.00 kW
3.80 kW
El input
1.00 kW
1.36 kW
COP
5.00
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
1.75 kW
Cooling capacity
5.00
EER
2.85
4.56
EN 14825
+7°C/+12°C
Pdesignc
5 kW
SEER
4.85
Pdc Tj = 35°C
5 kW
EER Tj = 35°C
2.85
Pdc Tj = 30°C
3.77 kW
EER Tj = 30°C
4.25
Cdc Tj = 30 °C
0.98
Pdc Tj = 25°C
2.32 kW
EER Tj = 25°C
5.38
Cdc Tj = 25 °C
0.97
Pdc Tj = 20°C
1.87 kW
EER Tj = 20°C
7.85
Cdc Tj = 20 °C
0.94
Poff
14 W
PTO
14 W
PSB
14 W
PCK
0 W
Annual energy consumption Qce
925 kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
Sound power level outdoor
54 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
3.44 kW
2.97 kW
ηs
244 %
150 %
Prated
3.40 kW
2.90 kW
SCOP
6.17
3.83
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
3.40 kW
2.90 kW
COP Tj = +2°C
3.75
2.30
Cdh Tj = +2 °C
0.985
0.989
Pdh Tj = +7°C
2.22 kW
2.02 kW
COP Tj = +7°C
5.66
3.16
Cdh Tj = +7 °C
0.964
0.978
Pdh Tj = 12°C
1.86 kW
1.76 kW
COP Tj = 12°C
8.01
5.40
Cdh Tj = +12 °C
0.940
0.957
Pdh Tj = Tbiv
3.40 kW
2.90 kW
COP Tj = Tbiv
3.75
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.69 kW
3.18 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.30
1.54
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.985
0.989
WTOL
60 °C
60 °C
Poff
14 W
14 W
PTO
14 W
14 W
PSB
14 W
14 W
PCK
14 W
14 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Backup Heater
4.00 kW
4.00 kW
Annual energy consumption Qhe
734 kWh
1012 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
Sound power level outdoor
54 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
8.26 kW
8.26 kW
ηs
152 %
118 %
Prated
8.26 kW
8.26 kW
SCOP
3.89
3.02
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
5.00 kW
5.00 kW
COP Tj = -7°C
3.50
2.71
Cdh Tj = -7 °C
0.990
0.992
Pdh Tj = +2°C
3.00 kW
3.11 kW
COP Tj = +2°C
5.15
3.81
Cdh Tj = +2 °C
0.976
0.983
Pdh Tj = +7°C
1.99 kW
2.28 kW
COP Tj = +7°C
7.22
5.29
Cdh Tj = +7 °C
0.949
0.968
Pdh Tj = 12°C
1.87 kW
1.87 kW
COP Tj = 12°C
8.70
6.88
Cdh Tj = +12 °C
0.935
0.948
Pdh Tj = Tbiv
5.00 kW
5.00 kW
COP Tj = Tbiv
3.50
2.71
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.69 kW
4.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.30
1.51
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.991
0.993
WTOL
60 °C
60 °C
Poff
14 W
14 W
PTO
14 W
14 W
PSB
14 W
14 W
PCK
14 W
14 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.83 kW
7.83 kW
Backup Heater
4.00 kW
4.00 kW
Annual energy consumption Qhe
5240 kWh
6739 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
Sound power level outdoor
54 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
5.65 kW
5.65 kW
ηs
184 %
136 %
Prated
5.65 kW
5.65 kW
SCOP
4.66
3.47
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
5.00 kW
5.00 kW
COP Tj = -7°C
3.11
2.28
Cdh Tj = -7 °C
0.991
0.994
Pdh Tj = +2°C
3.11 kW
3.11 kW
COP Tj = +2°C
4.32
3.30
Cdh Tj = +2 °C
0.981
0.985
Pdh Tj = +7°C
1.96 kW
2.19 kW
COP Tj = +7°C
6.48
4.58
Cdh Tj = +7 °C
0.954
0.971
Pdh Tj = 12°C
1.86 kW
1.84 kW
COP Tj = 12°C
8.41
6.33
Cdh Tj = +12 °C
0.937
0.952
Pdh Tj = Tbiv
5.00 kW
5.00 kW
COP Tj = Tbiv
3.11
2.28
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.69 kW
3.18 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.30
1.54
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.992
0.994
WTOL
60 °C
60 °C
Poff
14 W
14 W
PTO
14 W
14 W
PSB
14 W
14 W
PCK
14 W
14 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.96 kW
2.47 kW
Backup Heater
4.00 kW
4.00 kW
Annual energy consumption Qhe
2504 kWh
3360 kWh