0,970 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.60 kW
4.50 kW
El input
0.95 kW
1.66 kW
COP
4.83
2.72
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
182 %
128 %
Prated
5.40 kW
4.80 kW
SCOP
4.61
3.29
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.80 kW
4.30 kW
COP Tj = -7°C
3.00
2.03
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
2.90 kW
2.60 kW
COP Tj = +2°C
4.45
3.14
Cdh Tj = +2 °C
0.980
0.980
Pdh Tj = +7°C
1.90 kW
2.20 kW
COP Tj = +7°C
6.21
4.55
Cdh Tj = +7 °C
0.960
0.970
Pdh Tj = 12°C
2.40 kW
2.30 kW
COP Tj = 12°C
7.99
6.29
Cdh Tj = +12 °C
0.960
0.960
Pdh Tj = Tbiv
4.80 kW
4.30 kW
COP Tj = Tbiv
3.00
2.03
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.30 kW
3.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.75
1.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
55 °C
55 °C
Poff
4 W
4 W
PTO
12 W
13 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.10 kW
0.90 kW
Annual energy consumption Qhe
2418 kWh
3018 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
132 %
COP
3.30
Heating up time
1:30 h:min
Standby power input
30.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
216 l