1,300 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.00 kW
4.40 kW
El input
0.82 kW
1.49 kW
COP
5.10
2.95
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
38 dB(A)
38 dB(A)
Sound power level outdoor
56 dB(A)
56 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
264 %
165 %
Prated
5.30 kW
5.00 kW
SCOP
6.68
4.20
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
5.30 kW
5.00 kW
COP Tj = +2°C
3.39
2.31
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
3.40 kW
3.20 kW
COP Tj = +7°C
5.81
3.68
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
1.70 kW
1.50 kW
COP Tj = 12°C
8.62
5.21
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
3.40 kW
3.20 kW
COP Tj = Tbiv
5.81
3.68
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.30 kW
5.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.39
2.31
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
10 W
10 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1065 kWh
1604 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
38 dB(A)
38 dB(A)
Sound power level outdoor
56 dB(A)
56 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
160 %
107 %
Prated
5.00 kW
3.70 kW
SCOP
4.08
2.75
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
3.00 kW
2.30 kW
COP Tj = -7°C
3.45
2.34
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
1.90 kW
1.40 kW
COP Tj = +2°C
5.00
3.22
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
1.20 kW
1.60 kW
COP Tj = +7°C
5.73
4.58
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
1.60 kW
1.50 kW
COP Tj = 12°C
7.84
6.33
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
4.10 kW
3.00 kW
COP Tj = Tbiv
2.51
1.69
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.30 kW
2.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.72
1.17
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
10 W
10 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.70 kW
1.20 kW
Annual energy consumption Qhe
3038 kWh
3308 kWh
Pdh Tj = -15°C (if TOL<-20°C)
4.10
3.00
COP Tj = -15°C (if TOL<-20°C)
2.51
1.69
Cdh Tj = -15 °C
0.900
0.900
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
38 dB(A)
38 dB(A)
Sound power level outdoor
56 dB(A)
56 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
182 %
131 %
Prated
5.70 kW
4.70 kW
SCOP
4.63
3.35
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
5.10 kW
4.20 kW
COP Tj = -7°C
2.82
2.14
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
3.10 kW
2.50 kW
COP Tj = +2°C
4.37
3.26
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
2.10 kW
1.70 kW
COP Tj = +7°C
6.57
4.44
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
1.70 kW
1.40 kW
COP Tj = 12°C
8.83
5.54
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
5.10 kW
4.20 kW
COP Tj = Tbiv
2.82
2.14
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.60 kW
3.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
1.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
10 W
10 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.10 kW
1.00 kW
Annual energy consumption Qhe
2559 kWh
2898 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.22 kW
6.00 kW
El input
1.27 kW
2.03 kW
COP
4.90
2.96
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
38 dB(A)
38 dB(A)
Sound power level outdoor
59 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
264 %
167 %
Prated
6.00 kW
5.00 kW
SCOP
6.68
4.25
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
5.90 kW
5.00 kW
COP Tj = +2°C
3.49
2.37
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
3.90 kW
3.20 kW
COP Tj = +7°C
5.71
3.72
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
2.00 kW
1.60 kW
COP Tj = 12°C
8.78
5.41
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
3.90 kW
3.20 kW
COP Tj = Tbiv
5.71
3.72
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.90 kW
5.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.49
2.37
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
10 W
10 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.10 kW
0.00 kW
Annual energy consumption Qhe
1202 kWh
1580 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
38 dB(A)
38 dB(A)
Sound power level outdoor
59 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
166 %
113 %
Prated
6.00 kW
5.00 kW
SCOP
4.23
2.90
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
3.60 kW
3.10 kW
COP Tj = -7°C
3.51
2.49
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
2.20 kW
1.80 kW
COP Tj = +2°C
5.36
3.52
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
1.50 kW
1.20 kW
COP Tj = +7°C
6.66
4.10
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
1.60 kW
1.40 kW
COP Tj = 12°C
7.97
6.18
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
4.90 kW
4.00 kW
COP Tj = Tbiv
2.39
1.74
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.60 kW
2.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.78
1.17
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
10 W
10 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.40 kW
2.50 kW
Annual energy consumption Qhe
3515 kWh
4211 kWh
Pdh Tj = -15°C (if TOL<-20°C)
4.90
4.00
COP Tj = -15°C (if TOL<-20°C)
2.39
1.74
Cdh Tj = -15 °C
0.900
0.900
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
38 dB(A)
38 dB(A)
Sound power level outdoor
59 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
184 %
137 %
Prated
7.00 kW
6.00 kW
SCOP
4.68
3.50
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.20 kW
5.30 kW
COP Tj = -7°C
2.74
2.12
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
3.60 kW
3.20 kW
COP Tj = +2°C
4.45
3.43
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
2.50 kW
2.10 kW
COP Tj = +7°C
6.80
4.63
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
1.40 kW
1.40 kW
COP Tj = 12°C
8.13
5.70
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
6.20 kW
5.30 kW
COP Tj = Tbiv
2.74
2.12
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.00 kW
5.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.54
1.81
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
10 W
10 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.00 kW
1.00 kW
Annual energy consumption Qhe
3093 kWh
3557 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.00 kW
4.40 kW
El input
0.82 kW
1.49 kW
COP
5.10
2.95
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
38 dB(A)
38 dB(A)
Sound power level outdoor
56 dB(A)
56 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
264 %
165 %
Prated
5.30 kW
5.00 kW
SCOP
6.68
4.20
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
5.30 kW
5.00 kW
COP Tj = +2°C
3.39
2.31
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
3.40 kW
3.20 kW
COP Tj = +7°C
5.81
3.68
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
1.70 kW
1.50 kW
COP Tj = 12°C
8.62
5.21
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
3.40 kW
3.20 kW
COP Tj = Tbiv
5.81
3.68
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.30 kW
5.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.39
2.31
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
10 W
10 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1065 kWh
1604 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
38 dB(A)
38 dB(A)
Sound power level outdoor
56 dB(A)
56 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
160 %
107 %
Prated
5.00 kW
3.70 kW
SCOP
4.08
2.75
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
3.00 kW
2.30 kW
COP Tj = -7°C
3.45
2.34
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
1.90 kW
1.40 kW
COP Tj = +2°C
5.00
3.22
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
1.20 kW
1.60 kW
COP Tj = +7°C
5.73
4.58
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
1.60 kW
1.50 kW
COP Tj = 12°C
7.84
6.33
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
4.10 kW
3.00 kW
COP Tj = Tbiv
2.51
1.69
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.30 kW
2.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.72
1.17
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
10 W
10 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.70 kW
1.20 kW
Annual energy consumption Qhe
3038 kWh
3308 kWh
Pdh Tj = -15°C (if TOL<-20°C)
4.10
3.00
COP Tj = -15°C (if TOL<-20°C)
2.51
1.69
Cdh Tj = -15 °C
0.900
0.900
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
38 dB(A)
38 dB(A)
Sound power level outdoor
56 dB(A)
56 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
182 %
131 %
Prated
5.70 kW
4.70 kW
SCOP
4.63
3.35
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
5.10 kW
4.20 kW
COP Tj = -7°C
2.82
2.14
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
3.10 kW
2.50 kW
COP Tj = +2°C
4.37
3.26
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
2.10 kW
1.70 kW
COP Tj = +7°C
6.57
4.44
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
1.70 kW
1.40 kW
COP Tj = 12°C
8.83
5.54
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
5.10 kW
4.20 kW
COP Tj = Tbiv
2.82
2.14
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.60 kW
3.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
1.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
10 W
10 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.10 kW
1.00 kW
Annual energy consumption Qhe
2559 kWh
2898 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.22 kW
6.00 kW
El input
1.27 kW
2.03 kW
COP
4.90
2.96
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
38 dB(A)
38 dB(A)
Sound power level outdoor
59 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
264 %
167 %
Prated
6.00 kW
5.00 kW
SCOP
6.68
4.25
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
5.90 kW
5.00 kW
COP Tj = +2°C
3.49
2.37
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
3.90 kW
3.20 kW
COP Tj = +7°C
5.71
3.72
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
2.00 kW
1.60 kW
COP Tj = 12°C
8.78
5.41
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
3.90 kW
3.20 kW
COP Tj = Tbiv
5.71
3.72
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.90 kW
5.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.49
2.37
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
10 W
10 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.10 kW
0.00 kW
Annual energy consumption Qhe
1202 kWh
1580 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
38 dB(A)
38 dB(A)
Sound power level outdoor
59 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
166 %
113 %
Prated
6.00 kW
5.00 kW
SCOP
4.23
2.90
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
3.60 kW
3.10 kW
COP Tj = -7°C
3.51
2.49
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
2.20 kW
1.80 kW
COP Tj = +2°C
5.36
3.52
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
1.50 kW
1.20 kW
COP Tj = +7°C
6.66
4.10
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
1.60 kW
1.40 kW
COP Tj = 12°C
7.97
6.18
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
4.90 kW
4.00 kW
COP Tj = Tbiv
2.39
1.74
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.60 kW
2.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.78
1.17
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
10 W
10 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.40 kW
2.50 kW
Annual energy consumption Qhe
3515 kWh
4211 kWh
Pdh Tj = -15°C (if TOL<-20°C)
4.90
4.00
COP Tj = -15°C (if TOL<-20°C)
2.39
1.74
Cdh Tj = -15 °C
0.900
0.900
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
38 dB(A)
38 dB(A)
Sound power level outdoor
59 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
184 %
137 %
Prated
7.00 kW
6.00 kW
SCOP
4.68
3.50
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.20 kW
5.30 kW
COP Tj = -7°C
2.74
2.12
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
3.60 kW
3.20 kW
COP Tj = +2°C
4.45
3.43
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
2.50 kW
2.10 kW
COP Tj = +7°C
6.80
4.63
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
1.40 kW
1.40 kW
COP Tj = 12°C
8.13
5.70
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
6.20 kW
5.30 kW
COP Tj = Tbiv
2.74
2.12
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.00 kW
5.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.54
1.81
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
10 W
10 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.00 kW
1.00 kW
Annual energy consumption Qhe
3093 kWh
3557 kWh